3GSEYQY 18/30 kV Screened Tunnel Cable
18/30 kV screened tunnel cable with EPR insulation, copper tape screens and minimum 90% galvanized steel wire braid.
3GSEYQY is an 18/30 kV screened tunnel cable for mobile mine and tunnelling equipment and for stationary connections at high-voltage transformers, main panels and switchboards. The supplied VDE datasheet specifies three concentrically laid screened cores, circular stranded plain annealed copper Class 2 conductors, 3GI3 EPR insulation with inner and outer semiconductive layers, copper tape over each main core, PVC filler, galvanized steel wire braid with minimum 90% coverage and a red 5GM5 elastomer sheath. The source lists 48 kV AC testing, 90 °C maximum conductor temperature and 250 °C short-circuit temperature. Fixed service is −25 °C to +90 °C and mobile service is +5 °C to +90 °C. Conductor sizes in the supplied table range from 3 × 25/16 to 3 × 120/16. The braid and screening arrangement should be checked against the specified mechanical protection and installation environment before quotation. For mobile service, coordinate the requested bending and torsional duty with the support system, protective routing and termination space; verify the applicable current-carrying table for the actual ambient condition. Confirm the final conductor size, route, current calculation, termination, earthing arrangement, test documentation and delivery schedule with TEBAOFLEX.
3GSEYQY screened tunnel-cable construction
3GSEYQY uses three screened medium-voltage cores laid concentrically. Each main core has EPR insulation with inner and outer semiconductive layers, followed by a copper tape screen; PVC filler, galvanized steel wire braid and a red elastomer sheath complete the supplied arrangement.

| Parámetro | Valor indicado en la fuente |
|---|---|
| Conductor | Cable circular trenzado de cobre recocido liso, clase 2 según IEC 60228. |
| Insulation / field control | 3GI3 quality EPR rubber compound with extruded inner and outer semi-conductive layers |
| Identificación central | Natural colouring with black semi-conductive layer |
| Pantalla | Copper tapes applied over each main core |
| bandeja | Three screened cores laid up concentrically |
| Lecho | Relleno de PVC |
| Armadura | Trenza de alambre de acero galvanizado con cobertura mínima 90% |
| Cubierta exterior | 5GM5 type elastomer compound, red |
The copper tape screens provide the documented electrical-screening layer while the ≥90% braid supplies mechanical protection. Confirm the termination and earthing arrangement against the project drawing.
Applications for 3GSEYQY
The supplied application positions this 18/30 kV screened tunnel cable for mobile operating equipment in mines, underground excavations and tunnelling environments. It is also listed for stationary connections to high-voltage transformers, main panels and switchboards.

- Mobile mining and tunnelling equipment using the stated 18/30 kV system
- Stationary high-voltage transformer, main-panel and switchboard connections listed in the source
- Underground excavation and tunnel routes where screening and mechanical braid protection are required
- Confirm route movement, cable support, terminations, earthing, current calculation and final bending arrangement before quotation
The cable is not selected by voltage alone. Provide the equipment, route, installation mode and protection requirements so the supplied construction can be checked against the actual duty.
3GSEYQY specifications
Nominal electrical and dimensional values are transcribed from the supplied 3GSEYQY datasheet. Confirm the final size, route and termination drawing before order release.
| Parámetro | Valor indicado en la fuente |
|---|---|
| Rated voltage U₀/U | 18/30 KV |
| Voltaje de prueba de CA | 48 kV |
| Maximum permissible AC operating voltage | 20,8/36 kV |
| Maximum permissible DC operating voltage | 27/54 kV |
| Temperatura máxima del conductor | 90 °C |
| Temperatura máxima de cortocircuito | 250 °C |
| Fixed working temperature | −25 °C to +90 °C |
| Mobile working temperature | +5 °C to +90 °C |
| Carga de tracción máxima | 15 N/mm2 |
| torsión máxima | 25°/m |
| Radio de curvatura mínimo | Según DIN VDE 0298-3 |
| Current carrying capacity | Según DIN VDE 0298-4 |
| Sección transversal (mm²) | Overall diameter min–max (mm) | Max. DC resistance at 20 °C (Ω/km) | Approx. weight (kg/km) |
|---|---|---|---|
| 3 × 25/16 | 65.1–72.0 | 0.727 | 6860 |
| 3 × 35/16 | 68.0–75.1 | 0.524 | 7640 |
| 3 × 50/16 | 70.8–78.3 | 0.387 | 8520 |
| 3 × 70/16 | 74.5–82.4 | 0.268 | 9760 |
| 3 × 95/16 | 79.0–87.2 | 0.193 | 11280 |
| 3 × 120/16 | 82.2–90.9 | 0.153 | 12600 |
The datasheet notes that dimensions may vary with manufacturing tolerances. Other conductor sizes, packing forms and delivery lengths are available on request.
3GSEYQY standards and test references
The following references are recorded as they appear in the supplied datasheet. They are presented as standards and test references, not as a broader approval claim.
| Parámetro | Valor indicado en la fuente |
|---|---|
| Construcción | DIN VDE 0250-605 e IEC 60502-2 |
| General requirements | DIN VDE 0250-1 |
| Guide use | DIN VDE 0298-3 |
| Electrical tests | DIN VDE 0472-501 503 508 |
| Non-electrical tests | DIN VDE 0472-401 402, 602, 303, 615 |
| Under-fire-condition tests | DIN VDE 0472-803 804 |
| Retardante de llama | VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 |
State the required standard edition, inspection scope and test documentation with the RFQ. Current carrying capacity and minimum bending radius follow the supplied DIN VDE references.
Opciones de cable relacionadas
Compare estas opciones de cable según la combinación de servicios, el movimiento, la carga, el voltaje y los requisitos de transmisión.
Cable de alimentación para túneles de media tensión 2XSEYQY de 6/10 kV
Una opción de cable relacionada para una aplicación o perfil de trabajo diferente.
Ver productoCable (N)TSCGEWÖU de 3,6/6 kV a 12/20 kV para distribución minera
Una opción de cable relacionada para una aplicación o perfil de trabajo diferente.
Ver producto(N)TSCGECECWÖU Cable de enrollado para tuneladora de 8,7/15 kV y 12/20 kV
Una opción de cable relacionada para una aplicación o perfil de trabajo diferente.
Ver productoSolicite una recomendación y un presupuesto de cables.
Indique los servicios requeridos, la longitud del cable, la carga mecánica, el entorno, el tipo de terminación y la cantidad. Nuestro equipo revisará la solicitud antes de elaborar un presupuesto.
- Incluya el nombre del producto o SKU, así como la longitud y la cantidad de cable requeridas.
- Adjunte una especificación, un dibujo o una hoja de datos cuando esté disponible.