Obtenir un devis
CÂBLES MINIERS ET DE TUNNELAGE Modèle / construction

3GSEYQY 18/30 kV Screened Tunnel Cable

18/30 kV screened tunnel cable with EPR insulation, copper tape screens and minimum 90% galvanized steel wire braid.

Informations sur le produit
Marque
Modèle / construction
Présentation du produit

3GSEYQY is an 18/30 kV screened tunnel cable for mobile mine and tunnelling equipment and for stationary connections at high-voltage transformers, main panels and switchboards. The supplied VDE datasheet specifies three concentrically laid screened cores, circular stranded plain annealed copper Class 2 conductors, 3GI3 EPR insulation with inner and outer semiconductive layers, copper tape over each main core, PVC filler, galvanized steel wire braid with minimum 90% coverage and a red 5GM5 elastomer sheath. The source lists 48 kV AC testing, 90 °C maximum conductor temperature and 250 °C short-circuit temperature. Fixed service is −25 °C to +90 °C and mobile service is +5 °C to +90 °C. Conductor sizes in the supplied table range from 3 × 25/16 to 3 × 120/16. The braid and screening arrangement should be checked against the specified mechanical protection and installation environment before quotation. For mobile service, coordinate the requested bending and torsional duty with the support system, protective routing and termination space; verify the applicable current-carrying table for the actual ambient condition. Confirm the final conductor size, route, current calculation, termination, earthing arrangement, test documentation and delivery schedule with TEBAOFLEX.

Construction

3GSEYQY screened tunnel-cable construction

3GSEYQY uses three screened medium-voltage cores laid concentrically. Each main core has EPR insulation with inner and outer semiconductive layers, followed by a copper tape screen; PVC filler, galvanized steel wire braid and a red elastomer sheath complete the supplied arrangement.

3GSEYQY cable cross-section showing three screened power cores, copper tape screens, steel wire braid and red outer sheath
Supplied 3GSEYQY cross-section showing the screened three-core and galvanized steel wire braid arrangement.
Construction identified in the supplied VDE datasheet
ParamètreValeur indiquée dans la source
ConducteurCâble circulaire en cuivre nu recuit, classe 2 selon la norme IEC 60228
Insulation / field control3GI3 quality EPR rubber compound with extruded inner and outer semi-conductive layers
Identification du noyauNatural colouring with black semi-conductive layer
ÉcranCopper tapes applied over each main core
Lay-upThree screened cores laid up concentrically
Literieremplissage en PVC
ArmureTresse en fil d'acier galvanisé avec une couverture minimale de 90%
Gaine extérieure5GM5 type elastomer compound, red

The copper tape screens provide the documented electrical-screening layer while the ≥90% braid supplies mechanical protection. Confirm the termination and earthing arrangement against the project drawing.

Applications

Applications for 3GSEYQY

The supplied application positions this 18/30 kV screened tunnel cable for mobile operating equipment in mines, underground excavations and tunnelling environments. It is also listed for stationary connections to high-voltage transformers, main panels and switchboards.

3GSEYQY tunnel cable application with medium-voltage transformer and switchgear in an open-cast mining environment
Existing Media Library application image illustrating the medium-voltage transformer and switchgear context; confirm the actual route and equipment interface for 3GSEYQY.
  • Mobile mining and tunnelling equipment using the stated 18/30 kV system
  • Stationary high-voltage transformer, main-panel and switchboard connections listed in the source
  • Underground excavation and tunnel routes where screening and mechanical braid protection are required
  • Confirm route movement, cable support, terminations, earthing, current calculation and final bending arrangement before quotation

The cable is not selected by voltage alone. Provide the equipment, route, installation mode and protection requirements so the supplied construction can be checked against the actual duty.

Caractéristiques

3GSEYQY specifications

Nominal electrical and dimensional values are transcribed from the supplied 3GSEYQY datasheet. Confirm the final size, route and termination drawing before order release.

3GSEYQY electrical and mechanical characteristics
ParamètreValeur indiquée dans la source
Rated voltage U₀/U18/30 kV
tension d'essai CA48 kV
Maximum permissible AC operating voltage20,8/36 kV
Maximum permissible DC operating voltage27/54 kV
Température maximale du conducteur90 °C
température maximale de court-circuit250 °C
Fixed working temperature−25 °C to +90 °C
Mobile working temperature+5 °C to +90 °C
charge de traction maximale15 N/mm²
torsion maximale25°/m
rayon de courbure minimalConformément à la norme DIN VDE 0298-3
Current carrying capacityConformément à la norme DIN VDE 0298-4
3GSEYQY size and weight data
Section transversale (mm²)Overall diameter min–max (mm)Max. DC resistance at 20 °C (Ω/km)Approx. weight (kg/km)
3 × 25/1665.1–72.00.7276860
3 × 35/1668.0–75.10.5247640
3 × 50/1670.8–78.30.3878520
3 × 70/1674.5–82.40.2689760
3 × 95/1679.0–87.20.19311280
3 × 120/1682.2–90.90.15312600

The datasheet notes that dimensions may vary with manufacturing tolerances. Other conductor sizes, packing forms and delivery lengths are available on request.

Normes

3GSEYQY standards and test references

The following references are recorded as they appear in the supplied datasheet. They are presented as standards and test references, not as a broader approval claim.

Standards, tests and approvals referenced for this product
ParamètreValeur indiquée dans la source
ConstructionDIN VDE 0250-605 et CEI 60502-2
General requirementsDIN VDE 0250-1
Guide useDIN VDE 0298-3
Electrical testsDIN VDE 0472-501, 503, 508
Non-electrical testsDIN VDE 0472-401, 402, 602, 303, 615
Under-fire-condition testsDIN VDE 0472-803, 804
retardateur de flammeVDE 0482-332-1-2, DIN EN 60332-1-2, CEI 60332-1

State the required standard edition, inspection scope and test documentation with the RFQ. Current carrying capacity and minimum bending radius follow the supplied DIN VDE references.

Comparer par fonction

Options de câbles associées

Comparez ces options de câbles en fonction de la combinaison de services, du mouvement, de la charge, de la tension et des exigences de transmission.

devis basé sur l'ingénierie

Demandez une recommandation et un devis pour un câble.

Veuillez nous indiquer les services requis, la longueur du câble, les contraintes mécaniques, l'environnement, le type de terminaison et la quantité. Notre équipe examinera votre demande avant de vous établir un devis.

  • Veuillez inclure le nom du produit ou son SKU, ainsi que la longueur et la quantité de câble requises.
  • Joignez une fiche technique, un dessin ou une fiche de spécifications si disponible.

    Facultatif : joindre une spécification de câble, un dessin, une fiche technique ou une image du produit (PDF, DOC, DOCX, XLS, XLSX, CSV, JPG ou PNG ; maximum 10 Mo).

    En soumettant ce formulaire, vous acceptez que TEBAOFLEX utilise vos coordonnées et les fichiers fournis pour examiner votre demande et y répondre. Les fichiers servent à l'établissement du devis et aux échanges techniques relatifs à votre demande. Consultez notre politique de confidentialité. politique de confidentialité pour obtenir des informations à jour sur le traitement et la conservation des données.

    * Champs obligatoires. Veuillez inclure les détails du câble principal ou de l'application pour examen.