Type MV-105 Cable (5 kV, 15 kV & 35 kV): EPR vs XLPE Insulation, 100% vs 133% Levels and Mining/Industrial Feeder Selection

Engineering selection guide for 5 kV, 15 kV, 25 kV and 35 kV Type MV-105 medium-voltage distribution and mining feeder cables: MV-105 vs MV-90 thermal ratings, EPR vs TR-XLPE dielectrics, 100% vs 133% insulation wall thicknesses (90 to 420 mil), copper tape vs wire shield grounding and when to step to Type MP-GC or SHD-GC.

Medium-Voltage Distribution & Mining Feeders · 5 kV, 15 kV, 25 kV & 35 kV

Type MV-105 cable is a shielded medium-voltage power cable engineered to UL 1072 and ICEA S-93-639 reference constructions for 5 kV through 35 kV fixed industrial, substation, renewable and mine-infrastructure distribution at a continuous conductor temperature of +105 °C (+140 °C emergency overload, +250 °C short-circuit). Getting a Type MV-105 specification right hinges on four decisions: selecting the 100% vs 133% insulation level for your ground-fault clearing time, choosing EPR vs TR-XLPE insulation, sizing metallic copper-tape or concentric-wire shields for circulating current, and confirming whether a mining route actually requires Type MP-GC or portable Type SHD-GC instead.

Thermal Rating+105 °C continuous · +140 °C emergency
Classes de tensão5 kV, 8 kV, 15 kV, 25 kV & 35 kV
Insulation Levels100% (≤ 1 min clear) vs 133% (≤ 1 hr)
Primary DielectricsEPR / HEPR (flexible) or TR-XLPE

How does Type MV-105 differ from Type MV-90 and IEC 60502-2 medium-voltage feeders?

Across North American, Latin American (such as Peru, Chile and Mexico) and Middle East industrial projects, tenders routinely mix North American Type MV-105 (UL 1072 / ICEA S-93-639) alongside European or international IEC 60502-2 feeders (such as NA2XSEY or N2XS2Y). Recognizing the exact thermal and voltage-designation split avoids incompatible terminations and ampacity errors:

  • MV-105 vs MV-90 thermal ceiling: Type MV-90 is rated +90 °C continuous / +130 °C emergency, whereas Type MV-105 elevates continuous conductor operation to +105 °C (+140 °C emergency, +250 °C short-circuit). Under NEC Article 310 tables, +105 °C EPR Type MV-105 typically yields 7 % to 11 % higher ampacity in identical conduit or tray conditions—or provides extra insulation-aging life when terminations limit actual load temperature to 90 °C.
  • Phase-to-phase vs U₀/U rating convention: UL 1072 / ICEA S-93-639 names Type MV-105 by phase-to-phase system voltage class (5 kV, 15 kV, 25 kV, 35 kV) paired with an explicit 100% or 133% insulation level. IEC 60502-2 names U₀/U (Um), such as 12/20(24) kV or 18/30(36) kV. Never substitute a 12/20 kV IEC feeder onto a 35 kV MV-105 tender, and verify stress-cone outer diameter compatibility when mixing AWG/kcmil and metric mm² lugs.
Type MV-105 medium-voltage cable architecture: 35 kV single-core EPR layers, 100% vs 133% insulation wall thicknesses and MV-105 vs MP-GC vs SHD-GC selection Panel 1 illustrates single-core 35 kV Type MV-105 concentric layers: Class B or Class 2 copper conductor, extruded semiconductive conductor screen, EPR insulation, extruded strippable semiconductive insulation screen, overlapping copper tape metallic shield and PVC or CPE outer jacket. Panel 2 bars compare UL 1072 / ICEA S-93-639 nominal insulation wall thicknesses at 5 kV (90 vs 115 mil), 15 kV (175 vs 220 mil), 25 kV (260 vs 320 mil) and 35 kV (345 vs 420 mil) for 100% and 133% levels. Panel 3 maps fixed Type MV-105 against semi-permanent Type MP-GC and mobile portable Type SHD-GC. 1. Single-Core 35 kV MV-105 2. 100% vs 133% Wall (mils) 3. MV-105 vs MP-GC vs SHD-GC Triple-Extruded Semicon + EPR 5 mil Cu tape shield (CTS) or wire +105 °C continuous · +140 °C emerg. PVC, CPE or LSZH sunlight jacket 100% level (≤ 1 min clear) 133% level (≤ 1 hr / ungrounded) 5 kV 90 115 15 kV 175 220 25 kV 260 320 35 kV 345 420 UL 1072 / ICEA S-93-639 nominal mils Type MV-105 (5–35 kV) Fixed tray, conduit, direct burial 1C or 3C · +105 °C · no ground-check Type MP-GC (5–25 kV) Semi-permanent mine distribution 3C + 2G + 1GC · +90 °C · armored/CPE Type SHD-GC (2–25 kV) Portable mobile trailing shovels Extra-flex Class 5/6 · braid shield + GC
Type MV-105 engineering architecture: concentric triple-extruded EPR + semiconductive screens + copper-tape metallic shield, UL 1072 / ICEA S-93-639 100% vs 133% wall thicknesses (5 kV to 35 kV), and the mechanical duty progression from fixed MV-105 to MP-GC and mobile SHD-GC.

What are the 100% vs 133% insulation wall thicknesses from 5 kV to 35 kV?

Choosing between the 100% insulation level e o 133% insulation level is a system-grounding decision, not a quality grade. During a single-line-to-ground fault on a resistance-grounded or ungrounded industrial bus, healthy phases experience line-to-line voltage (1.732 × normal phase-to-ground voltage) until relays isolate the faulted feeder. Thicker 133% dielectric walls absorb that elevated electrical stress safely for up to 1 hour without premature partial-discharge inception.

UL 1072 / ICEA S-93-639 nominal EPR/XLPE insulation wall thicknesses for shielded Type MV-105 cables (5 kV to 35 kV)
Classe de tensão nominal100% level wall (≤ 1 min fault clear)133% level wall (≤ 1 hr / ungrounded)Minimum conductor size (ICEA/UL ref.)Typical industrial & substation role
5 kV (shielded)90 mil (2.29 mm)115 mil (2.92 mm)8 AWG (shielded)4.16 kV plant motors, crushers, pump feeders
8 kV (shielded)115 mil (2.92 mm)140 mil (3.56 mm)6 AWG6.6–7.2 kV industrial & mine substations
15 kV (shielded)175 mil (4.45 mm)220 mil (5.59 mm)2 AWG13.8 kV primary plant loops, wind/solar collectors
25 kV (shielded)260 mil (6.60 mm)320 mil (8.13 mm)1 AWG22–25 kV mine perimeter & utility feeders
35 kV (shielded)345 mil (8.76 mm)420 mil (10.67 mm)1/0 AWG33–35 kV unipolar substation tie & Andean mine feeds
Straight-on factory cross-section of a 33/35 kV single-core HEPR distribution cable clearly showing compacted Class 2 copper strands, inner conductor screen, thick HEPR dielectric, outer insulation screen, overlapping copper tape shield and outer jacket
Straight-on factory cross-section of a TEBAOFLEX 33/35 kV single-core Class 2 copper HEPR medium-voltage distribution cable—showing the compacted conductor, inner semiconductive screen, thick void-free HEPR dielectric wall, outer strippable insulation screen and overlapping copper tape shield.

Should your 15 kV or 35 kV Type MV-105 feeder use EPR or TR-XLPE insulation?

Although UL 1072 permits both ethylene propylene rubber (EPR / HEPR) and cross-linked polyethylene (TR-XLPE) at 105 °C on select qualified compounds, industrial, refinery and mining engineers overwhelmingly favor EPR para 15 kV to 35 kV Type MV-105 EPR distribution cables e 5 kV to 15 kV flexible EPR MV-105 feeders. For deep polymer physics, compare our dedicated guia sobre o isolamento EPR e XLPE / TR-XLPE insulation guide:

  • Tight switchgear & wet-duct bending: EPR retains rubbery flexibility even at 345 to 420 mil (8.8 to 10.7 mm) wall thickness, lowering pulling sidewall pressure around conduit elbows and simplifying termination inside cramped 15 kV or 35 kV metal-clad switchgear cabinets.
  • Water-treeing & partial-discharge resistance: Mineral-filled EPR resists moisture-driven water treeing and localized electrical tree propagation in flooded underground ducts and mine drainage trenches, whereas standard XLPE relies on tree-retardant additives (TR-XLPE) and strict moisture exclusion.
  • Emergency thermal stability (+140 °C): XLPE is semicrystalline and softens sharply near its ~105–110 °C crystalline melting range under heavy overload, increasing thermo-mechanical deformation at sharp cable-tray rungs; amorphous cross-linked EPR maintains modulus smoothly up to +140 °C emergency duty.
Macro cross-section of a TEBAOFLEX 25 kV 1×2/0 AWG CU/EPR/CTS/PVC single-core medium-voltage cable with red outer jacket, copper tape metallic shield and concentric semiconductive screens
TEBAOFLEX 25 kV single-core 1×2/0 AWG CU/EPR/CTS/PVC medium-voltage distribution cable cross-section—illustrating clean concentricity across the copper conductor, triple-extruded EPR insulation screens and overlapping copper tape metallic shield.

How do copper tape shields (CTS) vs concentric wire shields affect 15 kV and 35 kV bonding?

Every shielded Type MV-105 cable encloses its outer semiconductive layer in a metallic shield that confines the radial electric field and drains capacitive charging current and ground-fault current safely to earth. Two metallic shield styles dominate industrial MV-105 schedules:

  1. Helically applied 5 mil bare copper tape shield (CTS, ≥ 12.5 % to 25 % overlap): The most compact, economical shield for fixed trays, ducts and substations where short-circuit ground-fault current is moderate or supplemented by an external equipment grounding conductor.
  2. Concentric copper wire shield (drain wires / LC longitudinal corrugated tape): Provides much higher symmetrical fault-current cross-section and superior mechanical tolerance against longitudinal thermal expansion—preferred on high-fault utility tie lines and direct-buried 25 kV / 35 kV circuits.

Critical 35 kV single-core bonding rule: On three single-core 15 kV or 35 kV Type MV-105 cables routed in flat or trefoil formation, bonding metallic shields solidly at both ends induces continuous circulating shield current driven by phase load current—which can cut continuous ampacity by 5 % to 20 % on large conductors (250 kcmil to 1,000 kcmil). For short substation runs (< 100 m) or moderate current, engineers often apply single-point shield bonding with a surge-limiting arrestor (SVL) at the unbonded end, or verify exact trefoil derating before sizing conductors.

Flexible 5 to 15 kV EPR-insulated medium-voltage jumper and switchgear interconnect cable sample on the TEBAOFLEX factory mat
TEBAOFLEX 5 to 15 kV flexible EPR medium-voltage jumper and switchgear interconnect sample—bridging fixed MV-105 distribution buses to transformers, circuit breakers and compact indoor switchgear cubicles.

When should mines and plants step from Type MV-105 to Type MP-GC or portable Type SHD-GC?

Selecting the wrong mechanical duty class is the most expensive mistake in medium-voltage mining procurement. While a fixed Type MV-105 feeder carries the highest thermal ceiling (+105 °C), it is built with Class B (7–61 wire) stranded conductors and lacks the extra-flexible rope-lay copper, heavy ground-check pilot core and double-reinforced CPE jacket required for mobile drag or shovel trailing. Compare the three families across our guia de seleção de cabos de mineração de média tensão, armored and static mining cable guide e SHD-GC 2 kV to 25 kV voltage ratings guide:

Duty-boundary comparison: Type MV-105 vs Type MP-GC vs Type SHD-GC (and 35-CHVU) medium-voltage cables
Parâmetro de engenhariaType MV-105 (Fixed Distribution)Type MP-GC (Semi-Permanent Mine Feeder)Type SHD-GC / 35-CHVU (Mobile Trailing)
Governing referenceUL 1072 / ICEA S-93-639ICEA S-75-381 (mine power feeder)ICEA S-75-381 (portable trailing)
Voltage & thermal class5–35 kV · +105 °C continuous5–25 kV · +90 °C continuous2–25 kV (SHD-GC) / 20/35 kV (35-CHVU) · +90 °C
Conductor flexibilityClass B / Class 2 (or flexible MV-105 Class G/H)Class B or flexible Class C/G strandedExtra-flexible Class 5 / Class 6 / rope-lay
Ground-check (GC) monitor coreNot included (unless hybrid MV-105/MP-GC)Integrated 2 grounding + 1 insulated GC coreIntegrated 2 grounding + 1 yellow GC pilot core
Mechanical installation modeFixed cable tray, conduit, duct bank, direct burialMine shafts, haulage drifts, relocatable substation feedsContinuous dragging behind shovels, drills & draglines
TEBAOFLEX product & proofType MV-105 15–35 kV · Armored MV-105/MP-GCType MP-GC EPR/CPE Mine FeederSHD-GC · 35-CHVU 20/35 kV · Peru 8 kV Case
Three-core 8.7/15 kV round EPR medium-voltage feeder cable cross-section with individually shielded phase cores, interstitial grounding and red heavy-duty outer sheath
Three-core 8.7/15 kV round EPR medium-voltage shielded feeder sample—combining individually screened phase cores, symmetrical grounding geometry and a rugged red outer sheath for industrial and mining distribution.

What factory tests and 6 RFQ items prevent costly Type MV-105 specification delays?

Medium-voltage EPR cables from 5 kV to 35 kV must pass strict routine electrical screening before leaving the factory floor—specifically conductor DC resistance, high-voltage AC withstand testing and partial-discharge (PD) extinction testing verifying void-free triple extrusion across the inner screen, EPR dielectric and outer insulation screen (see our cable factory acceptance test guide for routine vs sample vs type test definitions).

When requesting a quotation for single-core or three-core Type MV-105 cable (including short custom replacement lengths such as 300 m per phase), confirm six items upfront:

  1. Exact system voltage & insulation level: State 5 kV, 8 kV, 15 kV, 25 kV or 35 kV and confirm 100% vs 133% insulation wall based on your relay ground-fault clearing time.
  2. Single-core vs three-core & conductor metal: Specify unipolar (1/C) or triplexed/jacketed 3/C, copper vs aluminum conductor, and AWG/kcmil or mm² cross-section (confirming compatibility with your existing termination kits).
  3. Dielectric & shield style: Confirm EPR vs TR-XLPE insulation and 5 mil copper tape shield (CTS) vs concentric copper wire shield (plus required short-circuit fault-current duration).
  4. Outer sheath & optional armor: Specify sunlight-resistant PVC, heavy-duty oil-resistant CPE, halogen-free LSZH, or interlocked/polymeric armor for tray or direct-burial exposure.
  5. Reel length, net/gross drum mass & freight mode: Confirm continuous cut length per wooden or steel export drum and port Incoterms (e.g., FOB Shanghai vs CIF Callao/Antofagasta/Jebel Ali—note that multi-ton MV drums carry substantial air-freight premiums if emergency schedules bypass ocean transit).
  6. Lead time & minimum order quantity: Custom Type MV-105 cables are manufactured to order from a 50 m MOQ with standard 7 to 45 working-day production windows. Send your Type MV-105 voltage class, insulation level and length schedule to TEBAOFLEX engineers for a tailored datasheet and factory quotation.

Perguntas frequentes

What is the difference between Type MV-105 and Type MV-90 medium-voltage cables?

Both Type MV-90 and Type MV-105 follow UL 1072 and ICEA S-93-639 medium-voltage power-cable reference rules for 5 kV through 35 kV systems, but Type MV-105 is rated for +105 °C continuous wet/dry conductor temperature (+140 °C emergency overload, +250 °C short-circuit) versus +90 °C continuous (+130 °C emergency) for Type MV-90. That +15 °C thermal margin lets a Type MV-105 feeder carry higher ampacity in hot underground ducts or tropical ambient yards—or maintain safety margin when equipment terminations are rated at 90 °C.

How do you choose between the 100% and 133% insulation level on 5 kV, 15 kV or 35 kV Type MV-105 cable?

Under ICEA S-93-639 and UL 1072, the 100% insulation level applies to solidly grounded systems where protective relays clear a single-phase-to-ground fault within 1 minute (e.g., 175 mil at 15 kV, 345 mil at 35 kV). The thicker 133% insulation level (e.g., 220 mil at 15 kV, 420 mil at 35 kV) is required on resistance-grounded, ungrounded or industrial/mining networks where clearing a ground fault may take up to 1 hour, or where extra dielectric safety margin is specified against switching surges.

Should a 15 kV or 35 kV Type MV-105 feeder use EPR or TR-XLPE insulation?

Ethylene propylene rubber (EPR / HEPR) provides markedly higher flexibility, smaller bending radius, stronger corona and water-treeing resistance and superior thermal-cycling stability in wet trays, mine substations and tight switchgear cubicles—making EPR the dominant dielectric for industrial and mining Type MV-105 feeders. Tree-retardant XLPE (TR-XLPE) delivers slightly lower dielectric losses and smaller outer diameter on long, straight utility duct runs where pulling tension dominates over tight bends.

Why do 35 kV single-core Type MV-105 copper-tape shields require careful single-point vs both-end grounding analysis?

When three single-core 15 kV or 35 kV shielded cables run in parallel, AC magnetic flux induces circulating current in metallic copper-tape or concentric-wire shields if both ends are bonded directly to earth. On long, high-current feeders, circulating shield current adds I²R heat that derates conductor ampacity; engineers verify shield-bond topology (single-point bonding with sheath voltage limiters, cross-bonding, or both-end bonding with trefoil spacing) before commissioning.

When should an underground or open-pit mine specify Type MV-105 versus Type MP-GC or Type SHD-GC?

Specify Type MV-105 (single-core or three-core, unarmored or interlocked/polymeric armored) for fixed primary distribution in cable trays, underground conduits, substation tie feeders and direct-buried trenches. Step up to Type MP-GC when a semi-permanent mine feeder requires an integrated ground-check conductor for continuous ground-monitoring relays, and step up to flexible portable Type SHD-GC (or 35-CHVU) whenever the cable trails across rock behind mobile shovels, drills or substations.

Can TEBAOFLEX supply short custom lengths such as 300 m of 35 kV unipolar EPR Type MV-105 cable?

Yes. Utility distributors often enforce multi-kilometer factory minimums on 15 kV to 35 kV EPR medium-voltage cable, whereas TEBAOFLEX builds custom single-core and three-core Type MV-105 (5 kV, 15 kV, 25 kV and 35 kV) and polymeric-armored MV-105/MP-GC feeders starting from a 50 m MOQ, with standard manufacturing lead times of 7 to 45 working days and routine partial-discharge and AC withstand factory testing.