

Type 441.1 Class 2 Screened Mining Cable 1.1/1.1 kV
Type 441.1 Class 2 mining cable is a 1.1/1.1 kV semiconductive screened cable for general mine use outside underground coal applications.
- Three tinned-copper power cores, three interstitial earth cores and one central pilot
- Class 2 EPR R-EP-90 insulation with semiconductive layer
- Semiconductive cradle and bedding
- Open-weave braid reinforcement and heavy-duty elastomer sheath
- 4.2 kV test voltage listed in the source
- +90 °C maximum continuous; −25 °C minimum installation
Confirm conductor area, route and termination configuration before ordering.
Type 441.1 Class 2 mining cable for 1.1 kV service
Type 441.1 Class 2 mining cable is a 1.1/1.1 kV screened cable for general mine use outside underground coal-mine applications, according to the supplied datasheet. It is a focused low-voltage product page rather than a catch-all Type 441 listing: the source gives one voltage designation, one Class 2 construction and its own area, diameter and mass tables.
The construction combines three flexible tinned-copper power cores, three interstitial earth cores and one central pilot. Power-core insulation is Class 2 EPR R-EP-90 with a semiconductive layer; the cores are laid over a semiconductive cradle. The earth cores are not insulated, and the assembly is completed by semiconductive elastomer bedding, an open-weave reinforcing braid and a heavy-duty elastomer outer sheath.
Selection should start with the 1.1 kV machine supply and the required conductor area, then move to the cable-entry, support and handling conditions. The datasheet records a 4.2 kV test voltage, but it does not provide current capacity, bend radius, pulling load or travel speed. Those details belong in the equipment-specific RFQ.
Type 441.1 Class 2 screened arrangement
This Type 441.1 variant uses a compact screened assembly with three power cores, interstitial earth cores and one central extensible pilot. The Class 2 designation and 1.1/1.1 kV rating should remain visible in every size cross-reference.

| Параметр | Значение по исходным данным |
|---|---|
| Дирижер | Tinned copper rope lay to AS/NZS 1125-2.10 |
| Power insulation | Class 2 EPR R-EP-90 to AS/NZS 3808 |
| Power screening | Semiconductive layer over power-core insulation |
| Ядра Земли | Three interstitial earth cores; not insulated |
| Pilot | One central pilot |
| Усиление | Open-weave braid |
| Ножны | Heavy-duty elastomer outer sheath |
The supplied cross-section is placed here because the earth-core and pilot positions are part of the product identity. Termination and screening continuity must be checked against the machine design.
Type 441.1 Class 2 application boundary
The source describes Type 441.1 for general use in mines except underground coal mines, where screened cores and reinforcement are required. That boundary is important when this 1.1 kV product is compared with other mine-feeder families.
- General mine installations outside underground coal-mine service
- Underground or open mines needing screened cores and reinforcement, as stated in the source
- Mobile equipment cable routes where a three-earth/one-pilot arrangement is specified
- Confirm the machine voltage, cable-entry space, screening termination and mechanical handling before substitution
The sheet does not state water, oil or UV ratings or a minimum bending radius. Do not turn the application description into a broader environmental or mechanical guarantee.
Type 441.1 Class 2 Screened Mining Cable 1.1/1.1 kV technical data
The dimensional and electrical values below are transcribed from the supplied PDF for Type 441.1 Class 2 mining cable. The tables are retained by voltage, screen option or construction section as presented in the source. Source ordering codes are included where present in the extracted table; blank source cells are not assigned new values.
Use the relevant area, conductor dimensions, insulation or covering thickness, nominal diameter and mass together. The source does not create a universal current-capacity, bend-radius, pulling-load or travel-speed value for this product.
TYPE 441.1 - 1.1/1.1 kV CLASS 2 - POWER, EARTH AND PILOT CORES
| Cross section mm2 | Conductor strand no/mm | Conductor dia. mm | Insul. thick. mm | Insul. dia. mm | Earth strand no/mm | Earth section mm2 | Semi-cond. cover mm | Pilot strand no/mm | Pilot insul. mm |
|---|---|---|---|---|---|---|---|---|---|
| 6 | 84/0.30 | 3.4 | 1.5 | 6.5 | 30/0.30 | 2.2 | 0.8 | 24/0.20 | 0.8 |
| 10 | 77/0.40 | 4.6 | 1.5 | 7.7 | 48/0.30 | 3.4 | 0.8 | 24/0.20 | 0.8 |
| 16 | 126/0.40 | 5.7 | 1.6 | 9 | 75/0.30 | 5.3 | 1.0 | 24/0.20 | 0.8 |
| 25 | 209/0.40 | 7.2 | 1.6 | 10.5 | 75/0.30 | 5.3 | 1.0 | 24/0.20 | 0.8 |
| 35 | 285/0.40 | 8.5 | 1.6 | 11.8 | 75/0.30 | 5.3 | 1.0 | 24/0.20 | 0.8 |
| 50 | 380/0.40 | 10 | 1.7 | 13.5 | 114/0.30 | 8.1 | 1.0 | 40/0.20 | 0.8 |
| 70 | 203/0.67 | 12 | 1.8 | 16 | 36/0.67 | 12.7 | 1.0 | 40/0.20 | 0.8 |
| 95 | 259/0.67 | 13.2 | 2.0 | 17.6 | 45/0.67 | 15.9 | 1.0 | 40/0.20 | 0.8 |
| 120 | 336/0.67 | 15.3 | 2.1 | 20 | 57/0.67 | 20.1 | 1.0 | 40/0.20 | 0.8 |
| 150 | 427/0.67 | 17.1 | 2.3 | 22.2 | 77/0.67 | 27.2 | 1.2 | 40/0.20 | 0.8 |
| 185 | 518/0.67 | 19.2 | 2.5 | 24.7 | 91/0.67 | 32.1 | 1.2 | 40/0.20 | 0.8 |
| 240 | 672/0.67 | 21.8 | 2.8 | 27.9 | 112/0.67 | 39.5 | 1.2 | 40/0.20 | 0.8 |
| 300 | 854/0.67 | 24.4 | 3.0 | 30.9 | 144/0.67 | 50.8 | 1.4 | 40/0.20 | 0.8 |
TYPE 441.1 - SHEATH AND MASS
| Cross section mm2 | Sheath thick. mm | Overall dia. mm | Cable mass kg/km | Copper mass kg/km |
|---|---|---|---|---|
| 6 | 3.8 | 28.5 | 1100 | 244 |
| 10 | 3.8 | 31.1 | 1350 | 394 |
| 16 | 3.9 | 34.1 | 1750 | 621 |
| 25 | 4.2 | 37.9 | 2300 | 885 |
| 35 | 4.4 | 41.2 | 2750 | 1173 |
| 50 | 4.9 | 45.9 | 3500 | 1686 |
| 70 | 5.3 | 52.2 | 4800 | 2394 |
| 95 | 5.8 | 56.7 | 5800 | 3206 |
| 120 | 6.3 | 62.7 | 7250 | 4047 |
| 150 | 6.7 | 68.3 | 8800 | 5116 |
| 185 | 7.3 | 74.9 | 10500 | 6265 |
| 240 | 8.0 | 83.3 | 13300 | 8062 |
| 300 | 8.7 | 91.2 | 16300 | 10116 |
2 technical tables were transcribed from the supplied datasheet; confirm final selection against the original PDF and project cable schedule.
Type 441.1 Class 2 source references
This product is kept separate from the higher-voltage Type 441 Class 1 page because the source documents define different classes and voltage ranges.
| Параметр | Значение по исходным данным |
|---|---|
| Стандарт изделия | AS/NZS 2802 |
| Номинальное напряжение | 1,1/1,1 кВ |
| Испытательное напряжение | 4,2 кВ |
| Максимальная непрерывная рабочая температура | +90 °C |
| Minimum installation temperature | −25 °C |
| Основная структура | 3 phase + 3 interstitial earth + 1 central pilot |
Reference the exact Type 441.1 Class 2 designation in the RFQ and request the applicable inspection or test documentation with the cable schedule.
Варианты кабелей по теме
Сравните эти варианты кабелей по сочетанию услуг, типу перемещения, нагрузке, напряжению и требованиям к передаче.
Подземный угольный шахтный кабель типа 240, напряжение от 1,1 кВ до 11 кВ.
Аналогичный кабель предназначен для других областей применения или режимов работы.
Посмотреть товарГорнодобывающий кабель типа 241.1 1,1 кВ | Семейство типов 241
Аналогичный кабель предназначен для других областей применения или режимов работы.
Посмотреть товарБронированный экранированный силовой кабель для горнодобывающей промышленности TYPE260
Аналогичный кабель предназначен для других областей применения или режимов работы.
Посмотреть товарЗапросите рекомендации по выбору кабеля и коммерческое предложение.
Укажите необходимые услуги, длину кабеля, механические характеристики, условия эксплуатации, тип разъемов и количество. Наша команда рассмотрит заявку перед составлением коммерческого предложения.
- Укажите название продукта или артикул, а также необходимую длину кабеля и количество.
- При наличии приложите техническое задание, чертеж или спецификацию.



