Get a Quote
MINING & TUNNELING CABLES TEBAOFLEX

Type 61B 0.64/1.1 kV Flexible Screened Mining Cable

Type 61B mining cable is a 0.64/1.1 kV flexible screened cable for non-reeling mining and industrial equipment.

  • 35–150 mm² power-conductor range in the supplied tables
  • Three tinned-copper braided screened power cores
  • Three unscreened pilot cores, one in each interstice
  • Triple-extruded EPR RD3 insulation with strippable semiconductive screens
  • Polychloroprene RS6 inner and black outer sheath with open nylon braid
  • −25 °C to +90 °C source-listed temperature window

Send the cable size, route, equipment and termination details for a project-specific review.

Product information
Brand
TEBAOFLEX
Product overview

Type 61B mining cable for non-reeling mobile equipment

Type 61B mining cable is a 0.64/1.1 kV flexible screened cable for electrically driven machines and movable electrical apparatus in hazardous areas. The supplied SANS datasheet describes non-reeling mining and industrial use, so this page is aimed at buyers specifying a robust mobile connection where the cable is handled along a mine or plant route rather than selected from a generic low-voltage list.

The cable combines three screened power cores with one pilot core in each interstice. Class 5 tinned annealed copper, triple-extruded EPR insulation, semi-conductive core screens, a polychloroprene inner sheath, open nylon braid and a black RS6 outer sheath define the source construction. Search-led buyer language also places this family alongside underground mobile machinery and roadheader-type equipment; the final application decision must still follow the non-reeling description, route conditions and equipment schedule in the supplied sheet.

Choose the conductor area from the 35–150 mm² range shown in Specifications, then confirm the machine voltage, cable length, termination layout and required pilot function. The dimensional and electrical tables retain the source values, including diameter, mass, DC resistance, reactance, screen performance and short-circuit figures. For the wider Mining & Tunneling Cables range, compare the related Type 240, Type 245 and Type 409 paths before requesting a quotation.

Construction

Type 61B screened power-core construction

Type 61B is built as three screened power cores with one unscreened pilot in each interstice. A semi-conductive rubber filler supports the right-hand lay, followed by polychloroprene covering, an open nylon reinforcing braid and the black RS6 sheath identified in the datasheet.

Type 61B cable cross-section showing three screened power cores, pilot cores and outer braid
Supplied Type 61B cross-section showing the screened power-core and interstitial-pilot arrangement.
Construction identified in the supplied datasheet
ParameterSource-listed value
ConductorClass 5 flexible stranded tinned annealed copper with semi-conducting rubber screen
InsulationTriple-extruded EPR thermosetting compound type RD 3 with strippable semi-conducting core screen
Cable coreThree tinned copper braided screened power cores and three unscreened pilot cores, one in each interstice
Lay / fillerCores laid up in right-hand lay around a semi-conductive rubber filler
Inner sheathPolychloroprene thermosetting compound type RS 6
ReinforcementOpen nylon braid, minimum 16 nylon strings
Outer sheathPolychloroprene thermosetting compound type RS 6, black

The cross-section is a construction aid; the supplied PDF remains the controlling document for conductor areas, screen fill, pilot sizes, dimensions, mass and electrical data.

Applications

Type 61B application fit

The source application is specific about electrically driven machines, movable apparatus in hazardous areas and non-reeling service. That makes the cable-selection conversation primarily about equipment mobility, route handling and screen/pilot continuity rather than a nominal voltage alone.

  • Non-reeling mining and industrial applications named in the supplied datasheet
  • Movable electrical apparatus and electrically driven machines in hazardous areas
  • Underground mobile-equipment procurement contexts, including roadheader-type searches where the project calls for the Type 61B construction
  • Routes requiring flexible screened power cores, pilot cores and an open reinforcing braid
  • Before ordering, verify the machine cable schedule, cable length, entry protection, termination and handling method

The supplied sheet does not state a reeling rating, travel speed or universal minimum bend radius. Do not transfer those values from another mining-cable type; include the actual route and handling duty in the RFQ.

Specifications

Type 61B 0.64/1.1 kV Flexible Screened Mining Cable technical data

The dimensional, electrical and service values below are transcribed from the supplied PDF for Type 61B mining cable. Tables remain separated by the construction or service section used in the source, so the applicable row can be matched to the equipment schedule without inventing a merged product range.

Use the source-listed conductor area, core dimensions, overall diameter, mass and electrical values together. Where the PDF gives a bending, tension, current or short-circuit value, it remains in the table; where it does not, no universal project rating is added.

TYPE 61B PHYSICAL PROPERTIES

TYPE 61B PHYSICAL PROPERTIES
Power size mm2Power wire dia. mmPower cond. dia. mmScreen wire dia. mmScreen fill %Screen cross-sec. mm2Pilot size mm2Pilot wire dia. mmPilot cond. dia. mmLay ratio xPCDCable dia. mmMass kg/mBend radius mmTension kN
350.418.50.31802760.313.212413.13001.6
500.4110.30.31803260.313.21242.53.63402.3
700.5111.90.318037160.415.212484.83903.2
950.5113.50.318043160.415.21252.35.74304.3
1200.5115.50.318047160.415.212587.14605.4
1500.5117.30.318052160.415.21263.58.55006.8

ELECTRICAL CHARACTERISTICS

ELECTRICAL CHARACTERISTICS
Power size mm2DC res. 20 deg C oh/kmDC res. 90 deg C oh/kmReact. oh/kmImped. 90 deg CLaid out straight ASym. S/C kA 1sEarth fault kA 1s
350.5760.7340.0900.7401604.32.1
500.4010.5110.0900.5192006.13.1
700.2830.3600.0880.3712458.53.5
950.2140.2730.0860.28729511.64.1
1200.1670.2130.0860.23034514.64.1
1500.1350.1710.0850.19139018.34.1

Parameter

Parameter
Voltage rating0.64/1.1 kV
Ambient rating basisCurrent rating at 30 deg C ambient
Short circuit ratingValues shown are kA for 1 second
Installation useNon-reeling operation for movable electrical apparatus

3 technical tables were transcribed from the supplied datasheet. Confirm the final selection against the original PDF and project cable schedule.

Standards

Type 61B standard and service limits

The product sheet identifies the applicable SANS references and service window below. Performance wording is retained as a source-listed characteristic and is not expanded into a separate certification claim.

Source-listed standard and service limits
ParameterSource-listed value
StandardsSANS 1520-1; SANS 1411-1; SANS 1411-3
Rated voltage0.64/1.1 kV
Temperature rating−25 °C to +90 °C
Sheath colourBlack
PerformanceExcellent flexibility; water resistant; flame retardant; UV, sunlight, ozone and oil resistant
Installation useNon-reeling operation for movable electrical apparatus
Ambient rating basisCurrent rating at 30 °C ambient
Short-circuit ratingValues shown in the PDF are kA for 1 second

For an RFQ, identify the required SANS documentation, conductor size, pilot arrangement, operating environment and whether the installation is non-reeling as described by the source.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    Optional: attach a cable specification, drawing, data sheet or product image (PDF, DOC, DOCX, XLS, XLSX, CSV, JPG or PNG; maximum 10 MB).

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.