JTW-LD-997 Resettable Analogue Linear Heat Detection Cable

JTW-LD-997 resettable analogue linear heat detection cable senses temperature changes along a protected route using a heat-sensitive polymer system. This 200 m-zone construction uses a factory-selected 70–130 °C alarm profile, with recovery limited to 120 °C peak exposure and a matching sensing interface.

Product information
Brand
TEBAOFLEX
Product overview

JTW-LD-997 resettable analogue linear heat detection cable provides a continuous heat-sensing element for cable routes, conveyors and equipment areas where access to individual point detectors is difficult. Its temperature-sensitive insulation changes electrical resistance as heat exposure changes, allowing the matched sensing interface to identify an alarm condition along the protected cable.

This page covers the 200 m-zone construction with a factory-selected alarm profile between 70 °C and 130 °C and an 85 °C default profile. Recovery is limited to a maximum cable exposure of 120 °C. Select the alarm threshold and expected peak exposure together when repeatable operation is required; the selected alarm temperature and recovery limit are separate design conditions.

The cable is installed with a matched sensing interface and end-of-line supervision. The supply length can be 200 m or 600 m, while each protected zone in this construction remains limited to 200 m. Roll length therefore serves procurement and cutting plans, whereas zone length controls the detector layout. The selected protective covering must also suit the route, fixing method and ambient conditions.

For a quotation, send the detector designation, required alarm profile, normal ambient temperature, protected-route drawing, zone lengths, covering option and quantity. Include the intended sensing interface and fire-alarm system documentation so that cable, supervision arrangement and commissioning requirements can be reviewed as one detection circuit.

Explore the industrial cable range for related configurations.

Construction

Construction

The representative PVC-covered cable contains two twisted steel sensing conductors with heat-sensitive polymer insulation, protective tape and an outer covering. The illustration shows the sensing cable only; interface electronics and end-of-line devices are separate system components.

Representative JTW-LD-997 analogue heat detection cable section showing two steel sensing conductors with heat-sensitive polymer insulation, protective tape and red PVC outer covering
Representative cable construction.
JTW-LD-997 Resettable Analogue Linear Heat Detection Cable construction
ComponentMaterial and construction
Sensing conductorsTwo twisted steel conductors forming the continuous electrical sensing element.
Heat-sensitive polymerInsulation whose resistance changes with temperature for analogue heat sensing. Maintain the specified sensing-interface relationship for the selected cable.
Protective wrapProtective tape around the insulated sensing-conductor assembly.
Outer coveringPVC, nylon or steel covering options are listed for the family; the representative product image shows the PVC-covered construction.
Circuit terminationA matched end-of-line device provides continuity supervision at the end of each sensing zone; leader-wire and interface connections follow the approved system layout.
Applications

Applications

Route the sensing cable along the hazard area with suitable fixings and a defined zone plan. Choose the alarm profile from normal ambient conditions, required response and the maximum exposure compatible with recovery.

Red linear heat detection cable securely clipped along an industrial cable tray with supported routing and clear separation from moving equipment
Application illustration.
  • Continuous heat monitoring along industrial cable trays and cable fields where point-detector access is restricted.
  • Heat-sensing routes adjacent to material conveyors and industrial equipment, with the cable supported clear of moving parts.
  • Local overheating and fire detection around plant and equipment when the matched detector system is specified for that location.
  • Distributed alarm sensing along protected routes; use an RTD instrumentation circuit when the requirement is a defined point-temperature measurement.
  • Keep each zone within the 200 m design limit for this construction and preserve the 15 mm minimum cable bend radius.
  • Specify the normal ambient temperature, alarm profile, maximum heat exposure, covering and system interface before ordering.
Specifications

Specifications

JTW-LD-997 Resettable Analogue Linear Heat Detection Cable technical data
ParameterValue
Cable typeResettable analogue linear heat-sensing cable.
ModelJTW-LD-997, 200 m-zone construction.
Alarm temperature range70 °C to 130 °C, factory-selected; default 85 °C.
Recovery exposure limit120 °C maximum.
Operating ambient range−25 °C to (selected alarm temperature − 20) °C.
Maximum sensing-zone length200 m.
Minimum bend radius1.5 cm (15 mm).
Standard supply lengths200 m or 600 m rolls.
Conductor materialSteel.
PVC-covered cable mass1.4 kg/100 m (0.94 lb/100 ft).
JTW-LD-997 resettable analogue cable ordering and zone limits
Cable designationAlarm profile (°C)Maximum zone (m)Supply roll options (m)Recovery limit (°C)Minimum bend (cm)
JTW-LD-997 analogue heat-sensing cable70–130, factory-selected; default 85200200 or 6001201.5
JTW-LD-997 cable construction and supply references
ParameterCable specification
Sensing elementTwo twisted steel conductors
InsulationTemperature-sensitive polymer
Assembly wrapProtective tape
Covering optionsPVC / nylon / steel
PVC construction mass1.4 kg/100 m (0.94 lb/100 ft)
Operating ambient−25 °C to (selected alarm temperature − 20) °C
Matched sensing-system interface references for the 200 m-zone cable
Interface parameterSystem reference
Operating supply20–26 VDC
Standby current25 mA
Alarm and fault current45 mA
Supervision arrangementMatched sensing interface and end-of-line device

The alarm profile is selected before shipment. Match normal ambient temperature to the operating limit of the selected profile.

Recovery depends on peak cable exposure remaining within 120 °C. The factory-selected alarm range and the recovery limit must both be considered in the detector design.

A 600 m supply roll is a procurement length; the protected zone for this construction is limited to 200 m.

The 20–26 VDC and 25/45 mA values belong to the matched sensing-system interface. Cable length, termination and electrical supervision are selected together.

Specify outside diameter, fixing details and the required protective covering on the project drawing. Keep the cable clear of sharp edges, local crushing and moving equipment.

Standards

Standards

JTW-LD-997 Resettable Analogue Linear Heat Detection Cable standards and test references
Standard or specificationApplication
EN 54-22Reference framework for specifying a resettable line-type heat detector comprising the sensing element and its sensor control unit.
Factory alarm-profile specificationIdentify the selected 70–130 °C profile, default 85 °C where applicable, and the associated normal ambient limit.
Zone and continuity-supervision specificationDocument the 200 m maximum zone, matching interface, end-of-line arrangement and commissioning checks.
Cable acceptance documentationRecord cable designation, covering, supplied length, alarm profile and recovery exposure limit in the order and detector-system documentation.

EN 54-22 scope for resettable line-type heat detectors

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.