(N)TS-TGSH 3.6/6 kV Medium Voltage Hot Water Pump Cable
(N)TS-TGSH is a 3.6/6 kV halogen-free hot-water pump cable with SIR insulation, inner semiconductive field control and an EVA outer sheath.
- Class 5 finely stranded tinned copper
- 130 °C maximum conductor temperature
- 11 kV / 5 minutes main-core AC test
- Separate fixed and flexible bend requirements
Send the motor voltage, core configuration, installed length, pump-entry drawing and water conditions for a technical quotation.
(N)TS-TGSH for Medium-Voltage Hot-Water Pump Connections
(N)TS-TGSH is a 3.6/6 kV round, halogen-free cable for hot-water pump connections and immersed electrical equipment under medium mechanical stress. Its construction combines Class 5 tinned copper conductors, an inner semiconductive rubber field-control layer, SIR silicone rubber insulation and an EVA outer sheath. An EPDM inner sheath is used where included in the selected construction.
The medium-voltage connection needs coordinated electrical and mechanical preparation. Match the motor circuit and termination to the actual core arrangement, insulation system and inner field-control layer. Include the pump-entry drawing, available sealing length and termination space when specifying a replacement cable.
Plan the route around the selected finished diameter. Fixed supported sections and flexible sections have separate bend requirements, so allow adequate space at wellheads, glands and changes of direction. Provide independent cable supports and use the pump’s designated lifting equipment. Select the required protective conductor from the motor connection drawing.
The conductor-temperature limit applies to the current-carrying conductor. State the actual water composition, treatment chemicals, immersion conditions and installed length for the project assessment. Immersion depth and the permitted water-temperature limit are confirmed for the specified project. Use this construction in non-hazardous locations.
For (N)TS-TGSH selection, explore the submersible pump cable range; for (N)TS-TGSH insulation selection, read the high-temperature wire insulation guide.
Construction
Select the core count, protective-conductor arrangement and inner-sheath construction for the pump connection. The inner semiconductive rubber layer provides electrical field control.

| Element | Construction |
|---|---|
| Conductor | Class 5 finely stranded tinned copper. |
| Electrical field control | Inner layer of semiconductive rubber compound on the power conductors. |
| Core insulation | SIR silicone rubber. |
| Core identification | Numbering; G configurations include a green/yellow protective conductor. |
| Inner sheath | EPDM rubber where included in the selected construction. |
| Outer sheath | EVA rubber compound. |
| Metallic screen | Unscreened family construction. |
| Shape | Round. |
Applications
Medium-voltage power connections to hot-water pumps and immersed equipment in industrial, agricultural, indoor and outdoor supported installations under medium mechanical stress.

| Selection point | Requirement |
|---|---|
| Voltage and termination | Coordinate the 3.6/6 kV motor circuit, inner field-control layer and termination preparation with the equipment drawing. |
| Entry fit | Specify the finished diameter, seal range, strain relief and space for the termination. |
| Bending and support | Reserve 6 × maximum diameter for fixed routes and 10 × maximum diameter for flexible sections. Support the cable independently from the pump lifting system. |
| Conductor and water temperatures | Use the conductor-temperature limit for the electrical loading assessment; confirm the project’s water conditions separately. |
| Water chemistry | State water composition and treatment chemicals for material selection. |
| Location restriction | Not for explosion-hazardous areas. |
Specifications
| Parameter | Value |
|---|---|
| Rated voltage U₀/U | 3.6/6 kV |
| Conductor | Class 5 flexible tinned copper |
| Core insulation | SIR silicone rubber |
| Electrical field control | Inner semiconductive rubber layer |
| Outer sheath | EVA |
Keep the operating-voltage limits, main-core test and installation conditions together when selecting the medium-voltage pump connection.
| Parameter | Value or condition |
|---|---|
| Rated voltage U₀/U | 3.6/6 kV |
| Maximum AC operating voltage | 4.2/7.2 kV |
| Maximum DC operating voltage | 5.4/10.8 kV |
| AC test voltage — main cores | 11 kV / 5 minutes |
| Maximum conductor temperature | 130 °C |
| Short-circuit conductor temperature / duration | 350 °C / maximum 5 s |
| Minimum ambient temperature, fixed | −50 °C |
| Minimum ambient temperature, flexible | −25 °C |
| Maximum conductor tensile stress | 15 N/mm² |
| Minimum bend radius, fixed | 6 × maximum overall diameter |
| Minimum bend radius, flexible | 10 × maximum overall diameter |
| Family range | 1–4 cores; cross-sections up to 70 mm². Select core count and cross-section together. |
| Conductor | Class 5 flexible tinned copper |
| Core insulation | SIR silicone rubber |
| Electrical field control | Inner semiconductive rubber layer |
| Outer sheath | EVA |
| Metallic screen | Unscreened |
| Location restriction | Not for explosion-hazardous areas. |
Standards
| Reference | Application |
|---|---|
| EN 50525-2-21 | Construction reference: based on EN 50525-2-21. |
| DIN EN 60228 | Class 5 conductor reference. |
| DIN EN 50525-2-21 | Water-resistance reference. |
| DIN VDE 0298-3 | General cable-use and installation guidance. |
| Main-core AC cable test | 11 kV for 5 minutes. |
For conductor classes, see the IEC 60228 standard scope.
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
(N)TSW 3.6/6 kV Submersible Pump Cable for Potable-Water Systems
A related cable option for a different application or duty profile.
View productTMP-NTSWOEU 1.8/3-3.6/6kV Submersible Pump Cable
A related cable option for a different application or duty profile.
View productTGSH / TGSH2G Hot-Water Submersible Pump Cable 450/750 V
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.