TMP-NTSWOEU 1.8/3-3.6/6kV Submersible Pump Cable
TMP-NTSWOEU 1.8/3 kV and 3.6/6 kV submersible pump cable to DIN VDE 0250 Parts 812 and 813, for submersible pumps and equipment operating in industrial water.
- Conductor: class 5 fine stranded tinned copper to DIN VDE 0295.
- Insulation: heat-resistant EPR compound.
- Inner sheath: butyl rubber GM1b, particularly low water absorption and vapour permeability.
- Outer sheath: red chlorinated rubber 5GM3, oil-resistant and flame retardant.
- Range: 3 × 25 mm² to 3 × 95 mm², both voltages.
Send pump rating, immersion depth, water temperature and entry-fitting details for RFQ review.
TMP-NTSWOEU Medium-Voltage Submersible Pump Cable
TMP-NTSWOEU is a medium-voltage submersible cable to DIN VDE 0250 Parts 812 and 813, used to connect submersible pumps and other electrical operating equipment working in industrial water. TEBAOFLEX manufactures it in two rated voltages, 1.8/3 kV and 3.6/6 kV, each with its own dimension and weight table. The two voltages are not interchangeable: the same nominal cross-section has a different outer diameter in each, so the voltage must be fixed before a gland, entry fitting or reel is selected.
The construction is organised around water ingress control. Class 5 fine stranded tinned copper conductors to DIN VDE 0295 carry the load, heat-resistant EPR compound insulates them, and a butyl rubber inner sheath of type GM1b provides particularly low water absorption and low water vapour permeability. The red outer sheath of chlorinated rubber compound 5GM3 is oil-resistant and flame retardant.
- Rated voltage: 1.8/3 kV and 3.6/6 kV, listed separately.
- Cross-sections: 3 × 25 mm² to 3 × 95 mm² in both voltages.
- Bending radius: 6 × D fixed, 10 × D mobile.
- Duty: continuous submerged operation in industrial water.
Three-core versions without a separate earth core exist, but they are only applicable where the ascending pipe serves as the earth conductor; that arrangement follows the pump installation design. For low-voltage 0.6/1 kV pump and industrial-water duty use the (N)SSHÖU heavy-duty rubber cable, and for general pump sets see the submersible pump motor cable overview.
TMP-NTSWOEU Cable Construction
The layer sequence below is the manufacturing construction for the medium-voltage TMP-NTSWOEU build. The low-voltage TMP-NSSHÖU variant uses a yellow 5GM5 outer sheath and a different table; it is not covered on this page.

| Layer | Construction | Selection relevance |
|---|---|---|
| Conductor | Fine stranded tinned copper wires, class 5 to DIN VDE 0295 | Flexibility for handling and installation down a rising main; tinning supports wet service. |
| Insulation | Heat-resistant EPR compound, colour coded in 1 kV cables | Insulation system for the 1.8/3 kV and 3.6/6 kV builds. |
| Inner sheath | Butyl rubber compound GM1b with particularly low water absorption and low water vapour permeability | The layer that makes this a submersible construction rather than a general trailing cable. |
| Outer sheath | Chlorinated rubber compound 5GM3, red, oil-resistant and flame retardant | Distinguishes the medium-voltage TMP-NTSWOEU from the yellow 5GM5 low-voltage build. |
| Earth arrangement | Three-core versions without earth cores are supplied where the ascending pipe serves as the earth conductor | Applies where the rising main serves as the earth path. |
Special constructions
Armoured high-voltage builds for offshore drilling rigs and for extreme submersion depths up to 1000 m are special designs made to order. They are not the standard TMP-NTSWOEU construction shown above and are quoted separately against the project drawing.
TMP-NTSWOEU Applications
TMP-NTSWOEU connects electrical operating equipment in industrial water, most commonly submersible pump motors fed at medium voltage. The cable runs submerged for the whole service period, so the selection question is not only current rating but immersion conditions, entry sealing and the earth arrangement.

- Medium-voltage submersible pump motors in mine dewatering and industrial water systems.
- Permanently submerged equipment feeds where the butyl GM1b inner sheath is required for low water absorption.
- Installations where the ascending pipe is used as the earth conductor and a three-core build without earth cores is specified.
- Rising-main installations with cable straps or clamps at the fixed bending radius of 6 × D.
Application boundaries
The 1000 m submersion depth belongs to the armoured made-to-order offshore construction and not to the standard build. State the immersion depth, water temperature and pump entry fitting with the enquiry so the correct build and termination sealing are supplied.
Related submersible and pump references
Compare NTSCGERLWOEU 3.6/6 kV submersible cable for steel-braided permanently submerged duty, (N)SSHÖU for 0.6/1 kV industrial water duty, and NTSWOEU 0.6/1 kV E-loader cable, which shares part of the designation but is a dry-duty loader cable, not a pump cable.
Reference note: enquiries arriving marked TENAX-TMP or TMP-NTSWÖU are handled on this page; TEBAOFLEX manufactures to the designation and construction shown, and is not affiliated with the trademark holder.
Reference designation cross-reference
This submersible pump cable is catalogued under its own reference name, and it is the medium-voltage half of a two-part family.
| Reference designation | TEBAOFLEX designation and build | Rated voltage | What the reference name marks |
|---|---|---|---|
| TENAX-TMP / TMP-NTSWOEU | TMP-NTSWOEU submersible pump cable | 1.8/3 and 3.6/6 kV | Red 5GM3 sheath; the medium-voltage TMP build |
| TENAX-TMP / TMP-NSSHOEU | (N)SSHÖU submersible reference build | 0.6/1 kV | Yellow 5GM5 sheath; the low-voltage TMP build, quoted on its own page |
For the counterpart construction see (N)SSHÖU heavy-duty rubber cable.
For the full list of reference designations and the TEBAOFLEX build each one maps to, see the mining cable designation cross-reference.
Trademark note: TENAX®, TROMMELFLEX®, FELTOFLEX® and SCHRÄM® are trademarks of their respective owners, and TEBAOFLEX is neither affiliated with those companies nor reselling their cable. What we supply is the equivalent construction: we manufacture to the same VDE type designation and published construction, and every designation listed here can be quoted and supplied as a TEBAOFLEX build. The names appear so that an enquiry written in those terms reaches the matching construction, which is made to the standards and construction confirmed for the order.
TMP-NTSWOEU Specifications
| Rated voltage U₀/U | 1.8/3 kV and 3.6/6 kV |
|---|---|
| Standard | DIN VDE 0250 Parts 812 and 813 |
| Conductor class | Class 5 to DIN VDE 0295 |
| Cable-surface temperature, static | -40 °C to +80 °C |
| Cable-surface temperature, flexing | -25 °C to +80 °C |
| Minimum bending radius, fixed installation | 6 × D |
| Minimum bending radius, mobile application | 10 × D |
| Outer sheath colour | Red |
| Diameter notation | D = cable diameter |
TMP-NTSWOEU 1.8/3 kV size table
| Code and cross-section | Outer diameter approx. | Weight approx. | Inductive resistance at 50 Hz |
|---|---|---|---|
| TMP-NTSWOEU 1.8/3 kV 3 × 25 mm² | 35 mm | 1840 kg/km | 0.098 Ω/km |
| TMP-NTSWOEU 1.8/3 kV 3 × 35 mm² | 39 mm | 2410 kg/km | 0.093 Ω/km |
| TMP-NTSWOEU 1.8/3 kV 3 × 50 mm² | 43 mm | 3040 kg/km | 0.089 Ω/km |
| TMP-NTSWOEU 1.8/3 kV 3 × 70 mm² | 48 mm | 3920 kg/km | 0.085 Ω/km |
| TMP-NTSWOEU 1.8/3 kV 3 × 95 mm² | 53 mm | 4950 kg/km | 0.084 Ω/km |
TMP-NTSWOEU 3.6/6 kV size table
| Code and cross-section | Outer diameter approx. | Weight approx. | Inductive resistance at 50 Hz |
|---|---|---|---|
| TMP-NTSWOEU 3.6/6 kV 3 × 25 mm² | 45 mm | 2690 kg/km | 0.105 Ω/km |
| TMP-NTSWOEU 3.6/6 kV 3 × 35 mm² | 47 mm | 3180 kg/km | 0.100 Ω/km |
| TMP-NTSWOEU 3.6/6 kV 3 × 50 mm² | 51 mm | 3860 kg/km | 0.095 Ω/km |
| TMP-NTSWOEU 3.6/6 kV 3 × 70 mm² | 56 mm | 4870 kg/km | 0.090 Ω/km |
| TMP-NTSWOEU 3.6/6 kV 3 × 95 mm² | 60 mm | 5870 kg/km | 0.087 Ω/km |
All listed cross-sections in both voltages are available to order. Dimensions and weights are nominal values.
TMP-NTSWOEU Standards, Approvals and Order Documentation
| Reference | Scope | Order confirmation |
|---|---|---|
| DIN VDE 0250 Part 812 | Rubber-insulated flexible cables | State the required edition with the full cable designation. |
| DIN VDE 0250 Part 813 | Rubber-insulated flexible cables, medium-voltage series | State the required voltage with the order. |
| DIN VDE 0295 | Conductor class 5 stranding | Conductor class is fixed at class 5. |
Approvals
| Approval | Status |
|---|---|
| Manufacturing conformity, DIN VDE 0250 Parts 812/813 | Held |
| Routine and type test package for the medium-voltage build | Held |
Order package
The enquiry should state the rated voltage, cross-section and core count, pump rating and motor entry fitting, immersion depth and continuous immersion time, water temperature and chemistry, whether the ascending pipe is used as the earth conductor, drum lengths, termination sealing requirement and any project inspection or documentation scope.
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
NTSCGERLWOEU 3.6/6 kV Flexible Submersible Cable
A related cable option for a different application or duty profile.
View productSubmersible Pump Motor Cable 450/750V 0.6/1kV with Control Cores
A related cable option for a different application or duty profile.
View product(N)SSHÖU O/J, 3E and 3E + ST 0.6/1kV Heavy Duty Rubber Flexible Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.