Get a Quote
Submersible Pump Cables TEBAOFLEX

TMP-NTSWOEU 1.8/3-3.6/6kV Submersible Pump Cable

TMP-NTSWOEU 1.8/3 kV and 3.6/6 kV submersible pump cable to DIN VDE 0250 Parts 812 and 813, for submersible pumps and equipment operating in industrial water.

  • Conductor: class 5 fine stranded tinned copper to DIN VDE 0295.
  • Insulation: heat-resistant EPR compound.
  • Inner sheath: butyl rubber GM1b, particularly low water absorption and vapour permeability.
  • Outer sheath: red chlorinated rubber 5GM3, oil-resistant and flame retardant.
  • Range: 3 × 25 mm² to 3 × 95 mm², both voltages.

Send pump rating, immersion depth, water temperature and entry-fitting details for RFQ review.

Product information
Brand
TEBAOFLEX
Product overview

TMP-NTSWOEU Medium-Voltage Submersible Pump Cable

TMP-NTSWOEU is a medium-voltage submersible cable to DIN VDE 0250 Parts 812 and 813, used to connect submersible pumps and other electrical operating equipment working in industrial water. TEBAOFLEX manufactures it in two rated voltages, 1.8/3 kV and 3.6/6 kV, each with its own dimension and weight table. The two voltages are not interchangeable: the same nominal cross-section has a different outer diameter in each, so the voltage must be fixed before a gland, entry fitting or reel is selected.

The construction is organised around water ingress control. Class 5 fine stranded tinned copper conductors to DIN VDE 0295 carry the load, heat-resistant EPR compound insulates them, and a butyl rubber inner sheath of type GM1b provides particularly low water absorption and low water vapour permeability. The red outer sheath of chlorinated rubber compound 5GM3 is oil-resistant and flame retardant.

  • Rated voltage: 1.8/3 kV and 3.6/6 kV, listed separately.
  • Cross-sections: 3 × 25 mm² to 3 × 95 mm² in both voltages.
  • Bending radius: 6 × D fixed, 10 × D mobile.
  • Duty: continuous submerged operation in industrial water.

Three-core versions without a separate earth core exist, but they are only applicable where the ascending pipe serves as the earth conductor; that arrangement follows the pump installation design. For low-voltage 0.6/1 kV pump and industrial-water duty use the (N)SSHÖU heavy-duty rubber cable, and for general pump sets see the submersible pump motor cable overview.

Construction

TMP-NTSWOEU Cable Construction

The layer sequence below is the manufacturing construction for the medium-voltage TMP-NTSWOEU build. The low-voltage TMP-NSSHÖU variant uses a yellow 5GM5 outer sheath and a different table; it is not covered on this page.

TMP-NTSWOEU cable cross-section showing tinned copper conductors, EPR insulation, butyl GM1b inner sheath and red outer sheath
Flat cross-section of the TMP-NTSWOEU medium-voltage submersible pump cable.
TMP-NTSWOEU medium-voltage submersible cable construction
LayerConstructionSelection relevance
ConductorFine stranded tinned copper wires, class 5 to DIN VDE 0295Flexibility for handling and installation down a rising main; tinning supports wet service.
InsulationHeat-resistant EPR compound, colour coded in 1 kV cablesInsulation system for the 1.8/3 kV and 3.6/6 kV builds.
Inner sheathButyl rubber compound GM1b with particularly low water absorption and low water vapour permeabilityThe layer that makes this a submersible construction rather than a general trailing cable.
Outer sheathChlorinated rubber compound 5GM3, red, oil-resistant and flame retardantDistinguishes the medium-voltage TMP-NTSWOEU from the yellow 5GM5 low-voltage build.
Earth arrangementThree-core versions without earth cores are supplied where the ascending pipe serves as the earth conductorApplies where the rising main serves as the earth path.

Special constructions

Armoured high-voltage builds for offshore drilling rigs and for extreme submersion depths up to 1000 m are special designs made to order. They are not the standard TMP-NTSWOEU construction shown above and are quoted separately against the project drawing.

Applications

TMP-NTSWOEU Applications

TMP-NTSWOEU connects electrical operating equipment in industrial water, most commonly submersible pump motors fed at medium voltage. The cable runs submerged for the whole service period, so the selection question is not only current rating but immersion conditions, entry sealing and the earth arrangement.

Medium-voltage submersible pump set with the supply cable strapped to the rising main
TMP-NTSWOEU supplying a medium-voltage submersible pump on a rising main.
  • Medium-voltage submersible pump motors in mine dewatering and industrial water systems.
  • Permanently submerged equipment feeds where the butyl GM1b inner sheath is required for low water absorption.
  • Installations where the ascending pipe is used as the earth conductor and a three-core build without earth cores is specified.
  • Rising-main installations with cable straps or clamps at the fixed bending radius of 6 × D.

Application boundaries

The 1000 m submersion depth belongs to the armoured made-to-order offshore construction and not to the standard build. State the immersion depth, water temperature and pump entry fitting with the enquiry so the correct build and termination sealing are supplied.

Related submersible and pump references

Compare NTSCGERLWOEU 3.6/6 kV submersible cable for steel-braided permanently submerged duty, (N)SSHÖU for 0.6/1 kV industrial water duty, and NTSWOEU 0.6/1 kV E-loader cable, which shares part of the designation but is a dry-duty loader cable, not a pump cable.

Reference note: enquiries arriving marked TENAX-TMP or TMP-NTSWÖU are handled on this page; TEBAOFLEX manufactures to the designation and construction shown, and is not affiliated with the trademark holder.

Reference designation cross-reference

This submersible pump cable is catalogued under its own reference name, and it is the medium-voltage half of a two-part family.

Reference designation cross-reference
Reference designationTEBAOFLEX designation and buildRated voltageWhat the reference name marks
TENAX-TMP / TMP-NTSWOEUTMP-NTSWOEU submersible pump cable1.8/3 and 3.6/6 kVRed 5GM3 sheath; the medium-voltage TMP build
TENAX-TMP / TMP-NSSHOEU(N)SSHÖU submersible reference build0.6/1 kVYellow 5GM5 sheath; the low-voltage TMP build, quoted on its own page

For the counterpart construction see (N)SSHÖU heavy-duty rubber cable.

For the full list of reference designations and the TEBAOFLEX build each one maps to, see the mining cable designation cross-reference.

Trademark note: TENAX®, TROMMELFLEX®, FELTOFLEX® and SCHRÄM® are trademarks of their respective owners, and TEBAOFLEX is neither affiliated with those companies nor reselling their cable. What we supply is the equivalent construction: we manufacture to the same VDE type designation and published construction, and every designation listed here can be quoted and supplied as a TEBAOFLEX build. The names appear so that an enquiry written in those terms reaches the matching construction, which is made to the standards and construction confirmed for the order.

Specifications

TMP-NTSWOEU Specifications

TMP-NTSWOEU operating data
Rated voltage U₀/U1.8/3 kV and 3.6/6 kV
StandardDIN VDE 0250 Parts 812 and 813
Conductor classClass 5 to DIN VDE 0295
Cable-surface temperature, static-40 °C to +80 °C
Cable-surface temperature, flexing-25 °C to +80 °C
Minimum bending radius, fixed installation6 × D
Minimum bending radius, mobile application10 × D
Outer sheath colourRed
Diameter notationD = cable diameter

TMP-NTSWOEU 1.8/3 kV size table

Code and cross-sectionOuter diameter approx.Weight approx.Inductive resistance at 50 Hz
TMP-NTSWOEU 1.8/3 kV 3 × 25 mm²35 mm1840 kg/km0.098 Ω/km
TMP-NTSWOEU 1.8/3 kV 3 × 35 mm²39 mm2410 kg/km0.093 Ω/km
TMP-NTSWOEU 1.8/3 kV 3 × 50 mm²43 mm3040 kg/km0.089 Ω/km
TMP-NTSWOEU 1.8/3 kV 3 × 70 mm²48 mm3920 kg/km0.085 Ω/km
TMP-NTSWOEU 1.8/3 kV 3 × 95 mm²53 mm4950 kg/km0.084 Ω/km

TMP-NTSWOEU 3.6/6 kV size table

Code and cross-sectionOuter diameter approx.Weight approx.Inductive resistance at 50 Hz
TMP-NTSWOEU 3.6/6 kV 3 × 25 mm²45 mm2690 kg/km0.105 Ω/km
TMP-NTSWOEU 3.6/6 kV 3 × 35 mm²47 mm3180 kg/km0.100 Ω/km
TMP-NTSWOEU 3.6/6 kV 3 × 50 mm²51 mm3860 kg/km0.095 Ω/km
TMP-NTSWOEU 3.6/6 kV 3 × 70 mm²56 mm4870 kg/km0.090 Ω/km
TMP-NTSWOEU 3.6/6 kV 3 × 95 mm²60 mm5870 kg/km0.087 Ω/km

All listed cross-sections in both voltages are available to order. Dimensions and weights are nominal values.

Standards

TMP-NTSWOEU Standards, Approvals and Order Documentation

Standards applied to TMP-NTSWOEU
ReferenceScopeOrder confirmation
DIN VDE 0250 Part 812Rubber-insulated flexible cablesState the required edition with the full cable designation.
DIN VDE 0250 Part 813Rubber-insulated flexible cables, medium-voltage seriesState the required voltage with the order.
DIN VDE 0295Conductor class 5 strandingConductor class is fixed at class 5.

Approvals

Certification held for this construction
ApprovalStatus
Manufacturing conformity, DIN VDE 0250 Parts 812/813Held
Routine and type test package for the medium-voltage buildHeld

Order package

The enquiry should state the rated voltage, cross-section and core count, pump rating and motor entry fitting, immersion depth and continuous immersion time, water temperature and chemistry, whether the ascending pipe is used as the earth conductor, drum lengths, termination sealing requirement and any project inspection or documentation scope.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.