MYJV, MYJV22, MYJV32, MYJV42 & MYJV-GXT (0.6/1–8.7/10 kV) XLPE Armoured & Fibre-Composite Mine Power Cable
Fixed XLPE-insulated, PVC-sheathed coal-mine power cable in six voltage classes from 0.6/1 kV to 8.7/10 kV: MYJV unarmoured, MYJV22 double steel-tape armoured, MYJV32 fine steel-wire armoured for inclined shafts and MYJV42 thick steel-wire armoured for vertical shafts, plus MYJV-GXT and MYJV22-GXT with integrated optical fibres for substation telemetry.
Fixed power distribution in Chinese-standard underground coal mines, from shaft-bottom substations to panel transformers, pump chambers and conveyor drive houses, is built on the MYJV family of XLPE-insulated, PVC-sheathed mine power cables. One designation covers six voltage classes, 0.6/1 kV, 1.8/3 kV, 3.6/6 kV, 6/6 kV, 6/10 kV and 8.7/10 kV, and the armour suffix tells the installer where the cable may go: MYJV is unarmoured, MYJV22 has double steel-tape armour, MYJV32 has fine galvanized round steel-wire armour and MYJV42 has thick galvanized round steel-wire armour.
Steel tape armour gives crush protection in horizontal roadways and inclined drifts but carries no tensile load. Fine wire armour is used where the cable must resist pull along inclined shafts, and thick wire armour is the choice for vertical shafts where the armour carries the suspended weight. Cross-sections are quoted from 3×10 mm2 up to 3×400 mm2, but the available core and size combinations and the reference diameters are confirmed for each voltage and armour code at order stage; the dimensions of one suffix are never assumed for another.
For substations that need protection signalling and data on the same route, MYJV-GXT and MYJV22-GXT add telecommunication optical fibres in protective tubes laid in the core interstices, at 3.6/6, 6/10 and 8.7/10 kV from 3×25 to 3×300 mm2. Fibre count and type, for example G.652D single-mode or OM2 / OM3 multimode, are configured to the project telemetry plan.
Explore the mining and tunneling cable range for related configurations.
MYJV, MYJV22 and MYJV-GXT XLPE Mine Power Cable Construction & Armour Options
The representative horizontal sample shows an MYJV22-GXT 8.7/10 kV 3x95 mm2 cable: three compacted copper conductors with triple-extruded XLPE insulation and copper tape screens, optical fibre tubes in the interstices, a PVC inner sheath, double galvanized steel tape armour and a flame-retardant PVC outer sheath.

| Component | Material and construction |
|---|---|
| Copper Conductors | Annealed copper Class 1 or Class 2 conductors to GB/T 3956 (IEC 60228), round compacted or sector-shaped by size. |
| XLPE Insulation (90 C) | Cross-linked polyethylene insulation rated 90 C continuous; semi-conductive conductor and insulation screens on 3.6/6 kV and higher voltage classes. |
| Metallic Screen (Medium Voltage) | Copper tape screen over each insulated core on 3.6/6 kV to 8.7/10 kV cables to carry earth-fault current and control the electric field. |
| Optical Fibre Unit (GXT Versions) | Telecommunication fibres in protective loose or stainless steel tubes laid in the interstices; fibre count and type configured per project. |
| Fillers and PVC Inner Sheath | Non-hygroscopic fillers and an extruded PVC inner sheath forming a round bed for the armour. |
| Armour by Suffix | 22: double galvanized steel tape; 32: fine galvanized round steel wire; 42: thick galvanized round steel wire; MYJV and MYJV-GXT are unarmoured. |
| Flame-Retardant PVC Outer Sheath | Black or coloured flame-retardant PVC outer sheath designed to the MT/T 386 (KA/T 386) flame test. |
MYJV Type Designation Breakdown
- M: coal-mine cable (Chinese MT/KA designation system)
- YJ: cross-linked polyethylene (XLPE) insulation
- V: PVC sheath
- 22: double steel tape armour with PVC outer sheath
- 32 / 42: fine (32) or thick (42) round steel wire armour with PVC outer sheath
- -GXT: integrated optical fibre unit for telemetry
MYJV, MYJV22, MYJV32 and MYJV42 Coal-Mine Applications & Route Scope
Select the armour code by route and tensile duty, and the GXT version where fibres must travel with the power circuit.

- Shaft-bottom and panel substations, main pump chambers and conveyor drive houses fed at 0.6/1 kV to 8.7/10 kV (MYJV, MYJV22).
- Horizontal roadways and inclined drifts where cables on brackets need crush protection (MYJV22) or must resist longitudinal pull (MYJV32).
- Vertical shaft feeders where the armour must carry the suspended cable weight (MYJV42), with suspension method and safety factor fixed on the order drawing.
- Digital substations and optical differential protection links that need fibre telemetry alongside 3.6/6 kV to 8.7/10 kV power (MYJV-GXT, MYJV22-GXT).
MYJV Family vs Fixed Mining Power Cable, XAT/EVA FO and Borehole Cable Selection Boundary
| Product | Insulation / sheath | Voltage | Armour | Fibre | Best fit |
|---|---|---|---|---|---|
| MYJV family (this page) | XLPE / flame-retardant PVC | 0.6/1 to 8.7/10 kV | None, steel tape, fine or thick steel wire | GXT versions | Chinese MT/KA-system fixed mine distribution |
| Fixed Mining Power Cable — PVC / HEPR, SWA / STA Options | PVC or HEPR / PVC | Per Polish and Czech designations | SWA or STA options | No | Projects specifying European fixed mining designations |
| XAT/EVA FO 35 kV Armoured Mining Cable | XLPE / EVA | Up to 35 kV | Armoured | Yes | 35 kV armoured power and fibre feeders |
| Mine Borehole and Shaft Self-Supporting Armoured Drop Cable | XLPE or EPR | 0.6/1 to 8.7/15 kV | SWA / DWA self-supporting | No | Free-hanging borehole and shaft drops |
Low-smoke halogen-free (WDZ) MYJV versions are a separate enquiry and are not covered by the PVC-sheathed designations on this page.
Related selection resources
- Mining and tunneling cable engineering solutions
- Armoured and static mining cable engineering guide for fixed distribution routes
- Fixed Mining Power Cable — PVC / HEPR, SWA / STA Options
- XAT/EVA FO 35 kV Armoured Mining Cable
- Mine Borehole and Shaft Self-Supporting Armoured Drop Cable
MYJV and MYJV-GXT Frequently Asked Questions
Which MYJV armour code should be used in a vertical shaft?
MYJV42, with thick galvanized round steel-wire armour that carries the suspended cable weight. MYJV and MYJV22 cannot carry vertical self-weight, and MYJV32 is intended for inclined shafts. The suspension method and safety factor are fixed on the order drawing.
Are all 0.6/1 to 8.7/10 kV and 3x10 to 3x400 mm2 combinations available in every armour code?
No. The size range is an enquiry range. Available core and cross-section combinations and reference diameters are confirmed for each voltage class and armour code on the quotation drawing.
What fibres can MYJV-GXT carry?
Telecommunication fibres in protective loose or stainless steel tubes in the core interstices. Fibre count and type, for example G.652D single-mode or OM2 / OM3 multimode, are configured to the project telemetry and protection requirements.
What are the MOQ and lead time?
The minimum order quantity is 50 m and the manufacturing lead time is 7 to 45 working days, depending on construction and quantity.
MYJV Family Armour Matrix, MYJV-GXT Sizes & Technical Specifications
MYJV and MYJV-GXT Key Specifications
- Voltage: 0.6/1 to 8.7/10 kV (GXT 3.6/6 to 8.7/10 kV)
- Insulation: XLPE, 90 °C, flame-retardant PVC sheath
- Armour: None, steel tape (22), fine (32) or thick (42) steel wire
- Fibre option: MYJV-GXT / MYJV22-GXT, 3x25 to 3x300 mm²
- Supply: MOQ 50 m; 7 to 45 working days
| Parameter | Value |
|---|---|
| Design standard reference | MYJV family designed to MT/T 818.11-2009 / MT/T 818.13-2009 (now KA/T 818.11 / KA/T 818.13); GXT versions to an enterprise standard; flame test to MT/T 386 (KA/T 386) |
| Rated voltages | 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10 and 8.7/10 kV (GXT versions 3.6/6, 6/10 and 8.7/10 kV) |
| Armour codes | MYJV unarmoured; MYJV22 double steel tape; MYJV32 fine steel wire; MYJV42 thick steel wire |
| Conductor temperature | 90 C continuous; 250 C short-circuit for max 5 s |
| Optical fibre options (GXT) | Fibre count and type, for example G.652D single-mode or OM2 / OM3 multimode, configured to the project telemetry plan |
| Commercial supply terms | Minimum order quantity 50 m; manufacturing lead time 7 to 45 working days; size, armour and fibre configuration confirmed on the quotation drawing |
| Selection boundary vs Fixed Mining Power Cable and XAT/EVA FO | Choose the MYJV family for Chinese MT/KA-system fixed mine distribution; choose the PVC / HEPR fixed mining power cable for Polish and Czech designations, and the XAT/EVA FO cable for 35 kV armoured fibre-composite duty. |
MYJV, MYJV22, MYJV32 and MYJV42 Armour and Route Matrix
| Model | Armour | Outer Sheath | Typical Route | Tensile Duty | Voltage Classes | Core x Cross-Section |
|---|---|---|---|---|---|---|
| MYJV | None (unarmoured) | Flame-retardant PVC | Cable trays, brackets and hangers in protected roadways and substations | No — not for tensile or crush duty | 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10 kV | Enquiry range 3x10 to 3x400 mm²; combination confirmed per voltage at order |
| MYJV22 | Double galvanized steel tape (STA) | Flame-retardant PVC | Horizontal roadways and inclined drifts needing crush protection | No — tape armour carries no tensile load | 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10 kV | Enquiry range 3x10 to 3x400 mm²; combination confirmed per voltage at order |
| MYJV32 | Fine galvanized round steel wire (SWA) | Flame-retardant PVC | Inclined shafts and steep drifts | Yes — moderate longitudinal pull | 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10 kV | Enquiry range 3x10 to 3x400 mm²; combination confirmed per voltage at order |
| MYJV42 | Thick galvanized round steel wire (SWA) | Flame-retardant PVC | Vertical shafts where the armour carries the suspended weight | Yes — vertical self-weight tension | 0.6/1, 1.8/3, 3.6/6, 6/6, 6/10, 8.7/10 kV | Enquiry range 3x10 to 3x400 mm²; combination confirmed per voltage at order |
MYJV-GXT and MYJV22-GXT Fibre-Composite Size Range
| Model & Size (mm²) | Voltage Classes | Power Cores | Conductor (mm²) | Armour | Optical Unit | Next step |
|---|---|---|---|---|---|---|
| MYJV-GXT / MYJV22-GXT 3x25 | 3.6/6, 6/10, 8.7/10 kV | 3 | 25 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x35 | 3.6/6, 6/10, 8.7/10 kV | 3 | 35 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x50 | 3.6/6, 6/10, 8.7/10 kV | 3 | 50 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x70 | 3.6/6, 6/10, 8.7/10 kV | 3 | 70 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x95 | 3.6/6, 6/10, 8.7/10 kV | 3 | 95 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x120 | 3.6/6, 6/10, 8.7/10 kV | 3 | 120 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x150 | 3.6/6, 6/10, 8.7/10 kV | 3 | 150 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x185 | 3.6/6, 6/10, 8.7/10 kV | 3 | 185 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x240 | 3.6/6, 6/10, 8.7/10 kV | 3 | 240 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
| MYJV-GXT / MYJV22-GXT 3x300 | 3.6/6, 6/10, 8.7/10 kV | 3 | 300 | Unarmoured (GXT) or double steel tape (22-GXT) | Optical fibres in protective loose or stainless tubes in the interstices | Request this size |
Reference outer diameters and masses depend on voltage class, armour code and fibre configuration and are issued on the quotation drawing; one suffix or voltage is never assumed to share the dimensions of another.
Under China National Mine Safety Administration Announcement No. 2 of 2026, MT 818.1 became KA 818.1 and MT/T 818.2 to MT/T 818.14 and MT/T 386 became KA/T 818.2 to KA/T 818.14 and KA/T 386, keeping their years; project-specific certification and test scope is verified per order, and no MA safety-mark coverage is claimed on this page.
ASCII part references for BOM and ERP entry: MYJV-GXT and MYJV22-GXT 3x25, MYJV-GXT and MYJV22-GXT 3x35, MYJV-GXT and MYJV22-GXT 3x50, MYJV-GXT and MYJV22-GXT 3x70, MYJV-GXT and MYJV22-GXT 3x95, MYJV-GXT and MYJV22-GXT 3x120, MYJV-GXT and MYJV22-GXT 3x150, MYJV-GXT and MYJV22-GXT 3x185, MYJV-GXT and MYJV22-GXT 3x240, MYJV-GXT and MYJV22-GXT 3x300; MYJV, MYJV22, MYJV32 and MYJV42 are entered as model, voltage class and 3xS with S confirmed on the quotation drawing.
MYJV Standards & Test References (MT/T 818.11, KA/T 818.11, MT/T 386)
| Standard or specification | Application |
|---|---|
| MT/T 818.11-2009 / MT/T 818.13-2009 (KA/T 818.11 / KA/T 818.13) | Coal-mine cable parts referenced for MYJV-family fixed XLPE power cables; the applicable part and edition are confirmed per order. |
| MT/T 386-2011 (KA/T 386-2011) | Flame-retardant performance test methods and assessment rules for coal-mine cables. |
| GB/T 3956 / IEC 60228 | Conductors of insulated cables: conductor classes and maximum DC resistance. |
| ITU-T G.652 / IEC 60793-2-10 | Single-mode (G.652D) and multimode (OM2 / OM3) optical fibre characteristics for the GXT optical unit. |
Certifications and document support
TEBAOFLEX company certificates and quality system documentation
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
Fixed Mining Power Cable — PVC / HEPR, SWA / STA Options
A related cable option for a different application or duty profile.
View productMine Borehole & Shaft Self-Supporting Armoured Drop Cable (0.6/1–15 kV)
A related cable option for a different application or duty profile.
View productVBbShvng(A)-LS GOST 31996 Steel-Tape Armoured Underground Mine Power Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.