(N)TMCGC11Y Screened Single-Core MV Switchgear Cable

(N)TMCGC11Y screened single-core MV cable for short switchgear and transformer links: Class 5 tinned copper, EPR insulation, tinned-copper wire screen and red PUR sheath. Source rating family 3.6/6–18/30 kV; detailed 6/10 and 12/20 kV tables below.

Product information
Product overview

(N)TMCGC11Y is a screened single-core medium-voltage cable for short connections in switchgear or transformer rooms where terminal space and the route’s bend radius need close attention. The supplied construction uses a finely stranded Class 5 tinned-copper main conductor, EPR insulation between semiconductive stress-control layers, spirally applied tinned-copper protective wires and a red PUR outer sheath. Its source catalogue lists a 3.6/6 to 18/30 kV voltage family and gives complete size data specifically for 6/10 and 12/20 kV.

Start selection with the circuit voltage and conductor/protective-wire size, then check the available enclosure space against the listed outer-diameter band. The source distinguishes a fixed route from free movement: their bending radii and ambient limits differ. The quoted current table has its own free-air reference arrangement, so the circuit rating must be recalculated for the real installation. Confirm the screen and earthing arrangement, termination dimensions and project standard before ordering.

The similar-looking (N)TMCGCW11Y crane cable has a different published construction and movement application; choose by the exact designation and drawing. Browse the industrial cable range for adjacent power designs. See the Specifications tab for the source-backed size matrix.

Construction

Construction

The (N)TMCGC11Y construction combines a tinned-copper conductor, semiconductive field-control layers, EPR insulation and protective copper wires. The tinned-copper protective wires are a separate specified layer; confirm the required protective-conductor and screen termination design on the project drawing.

(N)TMCGC11Y layer construction
LayerSource construction
Main conductorFinely stranded Class 5 tinned copper, DIN EN/IEC 60228 reference
Inner stress-control layerExtruded semiconductive layer
InsulationEPR compound, DIN VDE 0207-20-based source description
Outer insulation screenSemiconductive insulation-shield layer
Protective conductorSpirally applied tinned-copper wires
Outer sheathRed PUR compound; source lists oil, ozone, UV and moisture resistance
(N)TMCGC11Y screened MV switchgear cable construction cross-section showing the conductor and layers
(N)TMCGC11Y Screened Single-Core MV Switchgear Cable construction illustration; verify the ordered build against its approved drawing.
Applications

Applications

Use the (N)TMCGC11Y construction as a candidate for short MV links between switchgear and transformers, especially where the connection route has constrained bending space. Check whether the installed route is fixed or experiences movement; the source gives different temperature and bend values for those duties.

  • Switchgear bay and transformer-house links after voltage, current and screen-bonding review.
  • Industrial indoor or outdoor routes where the specified red PUR sheath and environmental requirements match the actual duty.
  • Compare the (N)TMCGCW11Y cable where the application is a crane or other moving-equipment connection.

For a quote, specify U₀/U, main conductor/protective-wire section, length, movement duty, installation layout and termination arrangement.

(N)TMCGC11Y screened MV switchgear cable, single-core cable routed inside industrial medium-voltage switchgear
Illustrative application setting for (N)TMCGC11Y Screened Single-Core MV Switchgear Cable; final cable route and terminations depend on the equipment design.
Specifications

Specifications

(N)TMCGC11Y catalogue reference ratings cover 3.6/6–18/30 kV. The supplied size tables cover 6/10 and 12/20 kV only. Do not assume that a size in those two tables is available at every other voltage.

(N)TMCGC11Y source electrical rating matrix
U₀/U kVMax AC operating U₀/U kVMax DC operating U₀/U kVAC test kV
3.6/64.2/7.25.4/10.811
6/106.9/129/1817
8.7/1510.4/1813.5/2724
12/2013.9/2418/3629
14/2517.3/3022.5/4536
18/3020.8/3627/5443
(N)TMCGC11Y thermal and mechanical selection limits
ParameterSource value
Fixed ambient−40 to +90 °C
Flexible operation ambient−35 to +80 °C
Max conductor90 °C
Short circuit conductor250 °C
Tensile load15 N/mm² of conductor
Fixed bend≥6 × OD
Free-moving bend≥10 × OD

(N)TMCGC11Y 6/10 kV catalogue size reference

(N)TMCGC11Y 6/10 kV catalogue size and ampacity data
Model + sizeMax conductor Ω/kmNominal insulation OD mmCable OD mmApprox. kg/kmReference ampacity A
(N)TMCGC11Y 1 × 25/16 mm² 6/10 kV0.79514.521–23730135
(N)TMCGC11Y 1 × 35/16 mm² 6/10 kV0.56516.022–24860169
(N)TMCGC11Y 1 × 50/16 mm² 6/10 kV0.39317.024–261045207
(N)TMCGC11Y 1 × 70/16 mm² 6/10 kV0.27719.026–281290268
(N)TMCGC11Y 1 × 95/16 mm² 6/10 kV0.21020.527–291545328
(N)TMCGC11Y 1 × 120/16 mm² 6/10 kV0.16422.029–311820383
(N)TMCGC11Y 1 × 150/25 mm² 6/10 kV0.13224.031–332170444
(N)TMCGC11Y 1 × 185/25 mm² 6/10 kV0.10826.033–352515510
(N)TMCGC11Y 1 × 240/25 mm² 6/10 kV0.081728.036–383085607

(N)TMCGC11Y 12/20 kV catalogue size reference

(N)TMCGC11Y 12/20 kV catalogue size and ampacity data
Model + sizeMax conductor Ω/kmNominal insulation OD mmCable OD mmApprox. kg/kmReference ampacity A
(N)TMCGC11Y 1 × 25/16 mm² 12/20 kV0.79518.025–27925135
(N)TMCGC11Y 1 × 35/16 mm² 12/20 kV0.56519.026–281065169
(N)TMCGC11Y 1 × 50/16 mm² 12/20 kV0.39320.527–291250207
(N)TMCGC11Y 1 × 70/16 mm² 12/20 kV0.27722.029–311520268
(N)TMCGC11Y 1 × 95/16 mm² 12/20 kV0.21024.031–331790328
(N)TMCGC11Y 1 × 120/16 mm² 12/20 kV0.16425.533–352075383
(N)TMCGC11Y 1 × 150/25 mm² 12/20 kV0.13227.535–372455444
(N)TMCGC11Y 1 × 185/25 mm² 12/20 kV0.10829.537–392815510
(N)TMCGC11Y 1 × 240/25 mm² 12/20 kV0.081731.539–413350607

Reference current figures use conductor 90 °C, ambient 30 °C, free air, IEC 60364-5-52 installation method F, three loaded conductors in trefoil. Confirm derating, bonding and earth-fault duty for the actual circuit. Conductor resistance is shown in Ω/km at 20 °C.

Standards

Standards

Design references for (N)TMCGC11Y include DIN VDE 0250-813 and DIN EN/IEC 60228 for the Class 5 copper conductor, DIN VDE 0207-20 for the EPR compound, DIN VDE 0298-4 for derating, DIN EN/IEC 60811-404 for oil-resistance testing and DIN EN/IEC 60332-1-2 for single-cable flame behaviour. AC test voltages for each rated-voltage grade appear in Specifications.

Specify the applicable project edition, acceptance tests, terminal system and delivered documentation with the final construction drawing.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.