NTSCGCWOEU 12/20 kV Floating PV Shore Connection Cable
NTSCGCWOEU is a 12/20 kV screened single-core cable for floating photovoltaic shore connections and medium-voltage routes in water.
- Class 5 finely stranded tinned copper
- EPR insulation with inner and outer semiconductive field control
- Water-resistant EPR inner sheath and concentric tinned-copper wire earth screen
- Seven listed conductor / concentric-earth configurations
- Separate fixed and flexible bend requirements
Send the conductor configuration, circuit duty, shore-route drawing, bonding arrangement and water conditions for a technical quotation.
NTSCGCWOEU Single-Core Cable for Floating PV Shore Connections
NTSCGCWOEU is a 12/20 kV single-core flexible medium-voltage cable for shore connections from floating photovoltaic installations. It combines a Class 5 tinned-copper conductor, semiconductive EPR field-control layers, special EPR insulation, a water-resistant EPR inner sheath, a concentric tinned-copper wire screen and a special rubber outer sheath.
Plan the shoreline as a connected set of mechanical and electrical interfaces. The cable leaves a floating structure, passes through a supported water route and reaches fixed equipment on land. Independent strain relief, abrasion protection and controlled bend space keep mooring loads and concentrated movement away from the electrical connection.
The seven listed configurations identify the conductor and concentric-earth arrangement together. Compare the minimum and maximum finished diameters with the gland range, and use the cable mass when planning landing supports. Coordinate the wire-screen termination and bonding scheme with the complete single-core phase layout and fault-duty assessment.
For electrical selection, use the resistance, capacitance and current-reference conditions alongside the route length and installation drawing. Fixed and flexible sections have different bend requirements. The conductor-temperature limit applies to the electrical conductor; immersion depth and the permitted water temperature are confirmed for the project.
For NTSCGCWOEU material selection, review plain and tinned copper conductors; for NTSCGCWOEU applications, explore the industrial cable range.
Construction
The single-core assembly uses a concentric wire screen and a separate inner and outer sheath. Coordinate the wire-screen termination and bonding design with the complete phase circuit.

| Element | Construction |
|---|---|
| Conductor | Class 5 finely stranded tinned copper. |
| Inner field-control layer | Semiconductive EPR next to the conductor. |
| Insulation | EPR rubber, special compound > 3GI3. |
| Outer field-control layer | Semiconductive EPR over the insulation. |
| Inner sheath | Special water-resistant EPR rubber. |
| Metallic screen / earth | Concentric tinned-copper wire screen / earth conductor. |
| Outer sheath | Special rubber compound. |
| Geometry | Single-core round construction. |
Applications
Medium-voltage water routes and floating photovoltaic shore connections with mechanical exposure, supported transitions and controlled movement between floating and fixed equipment.

| Parameter | Value |
|---|---|
| Floating PV power export | Route medium-voltage power between the floating installation and shore-side equipment. |
| Shore transitions | Support both landings and coordinate abrasion protection, controlled bends and independent strain relief. |
| Water-level movement | Reserve service length within the specified bending and torsion limits; transfer mooring loads to the mechanical support system. |
| Phase routing and bonding | Coordinate the separate single-core phase routes, concentric-earth terminations and bonding design. |
| Thermal and current selection | Apply the listed current values only with their stated installation and ambient reference; assess the actual water route separately. |
| Entry fit | Match the selected diameter range, cable mass and termination envelope to the landing hardware and gland. |
| Water compatibility | Specify the actual water medium, immersion conditions and contaminant exposure. |
Specifications
Select the conductor and concentric-earth configuration together, then coordinate the diameter range, cable mass, electrical duty and shore-route interfaces.
| Parameter | Value |
|---|---|
| Rated voltage U₀/U | 12/20 kV |
| Core count | 1 |
| Conductor | Class 5 finely stranded tinned copper |
| Insulation | EPR special compound > 3GI3 |
| Sheath system | Water-resistant EPR inner sheath; special rubber outer sheath |
| Metallic screen / earth | Concentric tinned-copper wire screen / earth conductor |
| Highest system voltage Uₘ | 24 kV |
| Test voltage | 29 kV |
| Maximum conductor temperature | 90 °C |
| Short-circuit conductor temperature | 250 °C |
| Ambient temperature, fixed installation | −40 to +80 °C |
| Ambient temperature, flexible installation | −25 to +60 °C |
| Minimum bend radius, fixed | 6 × cable diameter D |
| Minimum bend radius, flexible | 10 × cable diameter D |
| Permanent conductor tensile stress | 15 N/mm² |
| Torsional limit | ±25 °/m |
| Water-service design reference | AD8 |
| Water-service conditions | Immersion depth and permitted water temperature are confirmed for the project. |
| Model and basic configuration | Conductor diameter (mm) | Minimum cable diameter (mm) | Maximum cable diameter (mm) | Cable mass (kg/km) |
|---|---|---|---|---|
| NTSCGCWOEU 1X70/16KON | 10.8 | 33 | 36 | 2050 |
| NTSCGCWOEU 1X95/16KON | 12.6 | 35.2 | 38.2 | 2380 |
| NTSCGCWOEU 1x120/16KON | 14.2 | 36.8 | 39.8 | 2690 |
| NTSCGCWOEU 1x150/25KON | 15.8 | 40.6 | 43.6 | 3320 |
| NTSCGCWOEU 1X185/25KON | 17.4 | 41.6 | 44.6 | 3630 |
| NTSCGCWOEU 1X240/25KON | 20.4 | 44.5 | 47.5 | 4250 |
| NTSCGCWOEU 1X300/25KON | 22.9 | 47 | 50 | 4890 |
| Model and basic configuration | Maximum tensile force (N) | Nominal capacitance (nF/km) | Conductor resistance at 20 °C (Ω/km) | Reference current (A) |
|---|---|---|---|---|
| NTSCGCWOEU 1X70/16KON | 1050 | 240 | 0.277 | 360 |
| NTSCGCWOEU 1X95/16KON | 1425 | 270 | 0.21 | 434 |
| NTSCGCWOEU 1x120/16KON | 1800 | 290 | 0.164 | 505 |
| NTSCGCWOEU 1x150/25KON | 2250 | 320 | 0.132 | 582 |
| NTSCGCWOEU 1X185/25KON | 2775 | 340 | 0.108 | 664 |
| NTSCGCWOEU 1X240/25KON | 3600 | 390 | 0.0817 | 780 |
| NTSCGCWOEU 1X300/25KON | 4500 | 430 | 0.0641 | 897 |
Reference current: one cable on a surface at 30 °C ambient temperature, according to DIN VDE 0298-4, Table 15. Assess the actual route, grouping and thermal conditions before selecting the operating current.
D is the selected cable diameter. Use the fixed or flexible bend factor for the corresponding route section and coordinate termination dimensions with the equipment drawing.
Standards
| Reference | Application |
|---|---|
| DIN VDE 0250-813 | Construction reference for the selected medium-voltage cable family. |
| DIN VDE 0298-3 | Bending and installation guidance. |
| DIN VDE 0298-4, Table 15 | Current-reference conditions: one cable on a surface at 30 °C ambient temperature. |
| DIN EN 60811-404 / IEC 60811-404 | Oil-resistance reference. |
| DIN EN 50525-2-21 | Water-service material reference. |
| DIN EN 60332-1-2 / IEC 60332-1-2 | Single-cable flame-performance reference. |
| AD8 | Water-service design reference. |
Consult the official DIN VDE 0250-813 standard entry for its scope and edition.
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
NTMCGCWÖU Single-Core MV Cable 3.6/6kV to 18/30kV
A related cable option for a different application or duty profile.
View productNTSCGEWOU / (N)TSCGEWÖU+FO Medium Voltage Crane Reeling Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.