S07RC4N8-F 450/750 V Screened Submersible Pump Cable
S07RC4N8-F is a 450/750 V screened rubber cable for submersible wastewater pumps and frequency-converter-controlled motors. It combines EPR-insulated conductors, an overall tinned-copper braid and a black CPE outer sheath.
- 450/750 V
- EPR insulation, EPDM inner sheath, tinned-copper braid and black CPE outer sheath
- Class 5 copper; tinned up to 6 mm², plain above 6 mm²
- 90 °C maximum conductor temperature
Send the configuration, motor or controller drawing, installed length and entry dimensions for a technical quotation.
S07RC4N8-F for Pump Connections
S07RC4N8-F is a 450/750 V screened rubber cable for submersible wastewater pumps and frequency-converter-controlled motors. It combines EPR-insulated conductors, an overall tinned-copper braid and a black CPE outer sheath.
The four-core G configurations include a protective conductor as well as the phase conductors. The braid provides the EMC screening function and is not a substitute for the PE connection. Effective screen contact at both cable ends should be planned with the drive, motor and cable-entry system. Keep the braid termination accessible and mechanically protected during installation.
The size table covers 4G1.5 through 4G120, with separate minimum and maximum finished diameters and approximate masses. Use the whole diameter range when choosing a gland or sealing sleeve. A screened cable has a different outside diameter and termination build from an unscreened lead of the same conductor section.
Give the drive output, motor current, installed length and routing with the enquiry. These inputs help coordinate conductor sizing, screen termination and the available bending space. Provide independent cable supports and include the wastewater composition when selecting the sheath and accessories. Immersion depth and water-temperature limits are confirmed for the specified installation.
- Keep the braid and protective conductor as separate connection functions.
- Select the seal from the finished OD limits of the exact 4G configuration.
- Allow space for screen preparation, strain relief and the specified bend.
Selection resources: submersible pump cable range · VFD cable guide.
Construction
EPR insulation, EPDM inner sheath, tinned-copper braid and black CPE outer sheath. The representative image follows the selected configuration; other sizes retain their stated core arrangement.

| Layer | Construction |
|---|---|
| Conductor | Flexible copper, Class 5; tinned through 6 mm² and plain above 6 mm². |
| Insulation | EPR rubber; four-core power identification to DIN VDE 0293-308. |
| Inner sheath | EPDM rubber where applicable to the selected construction. |
| Separator | Thin separating film in the illustrated construction. |
| Overall screen | Tinned-copper wire braid between inner and outer sheath. |
| Outer sheath | Black CPE rubber. |
Applications
S07RC4N8-F is a 450/750 V screened rubber cable for submersible wastewater pumps and frequency-converter-controlled motors. It combines EPR-insulated conductors, an overall tinned-copper braid and a black CPE outer sheath.

| Selection point | What to coordinate |
|---|---|
| EMC connection | Provide effective braid contact at both cable ends and a separate PE connection. |
| Entry dimensions | Match the exact 4G size and its OD limits to the gland or sealing sleeve. |
| Drive duty | State drive output, motor-cable length, current and routing for the connection design. |
| Bending space | Allow the required radius beyond the prepared screen termination and strain relief. |
Confirm immersion depth and the maximum permitted water temperature with the enquiry. Support the cable independently; use a separate mechanical system to lift the pump.
Specifications
Keep the exact configuration and its installation conditions together when selecting the cable entry and route.
| Parameter | Value |
|---|---|
| Rated voltage U₀/U | 450/750 V |
| Conductor | Class 5 copper; tinned up to 6 mm², plain above 6 mm² |
| Insulation and sheath | EPR insulation, EPDM inner sheath, tinned-copper braid and black CPE outer sheath |
| Temperature condition | 90 °C maximum conductor temperature |
| Maximum operating voltage AC | 476/825 V |
| Maximum operating voltage DC | 619/1238 V |
| Maximum short-circuit conductor temperature | 250 °C |
| Minimum ambient temperature | −40 °C fixed; −25 °C flexible |
| Maximum tensile stress on conductor | 15 N/mm² |
| Minimum bending radius | 4 × maximum OD, fixed; 6 × maximum OD, flexible |
S07RC4N8-F Configurations
| Configuration | Minimum OD (mm) | Maximum OD (mm) | Approximate mass (kg/km) |
|---|---|---|---|
| S07RC4N8-F 4G1.5 | 12.8 | 14.4 | 266 |
| S07RC4N8-F 4G2.5 | 15.2 | 17.2 | 388 |
| S07RC4N8-F 4G4 | 17 | 19 | 516 |
| S07RC4N8-F 4G6 | 18.9 | 20.9 | 630 |
| S07RC4N8-F 4G10 | 23.1 | 25.1 | 972 |
| S07RC4N8-F 4G16 | 26.6 | 29.6 | 1447 |
| S07RC4N8-F 4G25 | 31.8 | 34.8 | 2015 |
| S07RC4N8-F 4G35 | 35.3 | 38.3 | 2539 |
| S07RC4N8-F 4G50 | 40.5 | 43.5 | 3458 |
| S07RC4N8-F 4G70 | 45.2 | 48.2 | 4586 |
| S07RC4N8-F 4G95 | 50 | 54 | 5350 |
| S07RC4N8-F 4G120 | 57 | 60.5 | 6780 |
Standards
The following references identify the conductor, material and test requirements relevant to this construction.
| Reference | Application |
|---|---|
| EN 50525-2-21 | Design and water-resistance reference |
| IEC 60228 | Class 5 conductor reference |
| EN 60332-1-2 | Single-cable flame-test reference |
| EN 60811-404 | Oil-resistance test reference |
| AC voltage test | 2.5 kV AC for 15 minutes |
For conductor classes, see the IEC 60228 standard scope.
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
S07RN8H2-F 450/750 V Flat Wastewater Pump Cable
A related cable option for a different application or duty profile.
View productS1BC4N8-F 0.6/1 kV Screened Wastewater Pump Cable
A related cable option for a different application or duty profile.
View productS1BN8-F 0.6/1 kV Wastewater Pump Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.