INDUSTRIAL CABLES TEBAOFLEX

H07ZZ-F Halogen-Free Rubber Cable 450/750 V

450/750 V flexible rubber cable with halogen-free insulation and sheath, Class 5 copper and a 90°C conductor rating. For indoor and temporary outdoor power connections.

Product information
Brand
TEBAOFLEX
Product overview

H07ZZ-F is a 450/750 V flexible rubber cable with halogen-free insulation and a low-smoke outer sheath. It combines Class 5 copper conductors with a 90°C maximum conductor temperature for indoor power connections and temporary outdoor use.

The insulation and sheath system is selected for applications where smoke emission and corrosive combustion gases affect the cable specification. These material requirements are distinct from circuit-integrity or fire-survival requirements. H07ZZ-F provides a defined flexible power-cable construction that can be compared with conventional rubber cable when specifying a building or temporary installation.

The range includes single-core, multicore and control configurations. The specifications tab lists model-specific conductor arrangements, diameter ranges, minimum bend radii and tensile loads. Fixed and moving installation conditions are shown separately so the route can be checked against the actual cable size. G configurations contain a green/yellow protective conductor.

Specify the number of working cores, protective earthing arrangement, conductor area and installed length when requesting a quotation. The operating environment, movement and connection details help determine the appropriate configuration. TEBAOFLEX provides a product-specific quotation based on these requirements, with related cable choices available for different voltage, sheath or mechanical conditions.

Explore the industrial cable range for related configurations.

When comparing H07ZZ-F 450/750 V low-smoke zero-halogen rubber cable against standard harmonized elastomeric cords, evaluate these options: H05RN-F / H05RR-F Cable 300/500 V (300/500 V light- to medium-duty rubber cord for general workshop appliances); H07RN-F Cable 450/750 V Heavy-Duty Rubber Flexible Cable (450/750 V polychloroprene-sheathed cable for oil-exposed outdoor and industrial duty). Select LSZH compounds where low smoke and zero halogen gas emission are mandatory.

Construction

Construction

H07ZZ-F uses flexible copper conductors and halogen-free rubber compounds. The illustration shows a representative four-core configuration.

H07ZZ-F four-core cross-section with brown, black, grey and green-yellow cores
Representative cable construction.
H07ZZ-F Halogen-Free Rubber Cable 450/750 V construction
ComponentMaterial and construction
ConductorBare copper, flexible Class 5 to IEC 60228.
InsulationEI8 rubber compound to EN 50363-5.
Core identificationUp to five cores: colours to HD 308 / DIN VDE 0293-308. Six cores and above: EN 50525-1.
Outer sheathBlack cross-linked halogen-free elastomer compound EM8 to EN 50363-6.
Applications

Applications

H07ZZ-F supports flexible power connections where low-smoke and halogen-free materials are part of the project specification.

Black flexible power cables connecting temporary distribution equipment in an indoor exhibition hall
Application illustration.
  • Indoor electrical equipment and temporary power distribution.
  • Public venues and installations requiring low-smoke cable materials.
  • Temporary outdoor use within the specified temperature and installation conditions.
  • Size the cable for its circuit load, protective arrangement and route.

For fire-safe elastomeric insulation comparisons and higher-voltage halogen-free power distribution, consult these technical resources: Rubber Cable vs PVC Cable: Temperature, Flexing, Oil and Where Each Belongs (engineering trade-offs between cross-linked rubber and thermoplastic PVC insulation systems); NSHXAFÖ 1.8/3kV Halogen-Free Rubber Cable (1.8/3 kV single-core halogen-free rubber cable for short-circuit-proof switchgear and rail traction). Verify operating voltage and flame-test compliance before installation.

Specifications

Specifications

H07ZZ-F Halogen-Free Rubber Cable 450/750 V technical data
ParameterValue
Rated voltage U₀/U450/750 V
AC test voltage2.5 kV
Maximum conductor temperature90°C
Maximum short-circuit conductor temperature250°C
Ambient temperature, fixed installation-25°C to +80°C
Ambient temperature, flexible use-5°C to +80°C
Maximum conductor tensile stress15 N/mm²
UV resistanceUV-resistant outer sheath.
Representative four-core identificationBrown, black, grey and green/yellow.
H07ZZ-F configurations and mechanical data
Model and configuration (mm²)OD min. (mm)OD max. (mm)Fixed bend radius min. (mm)Moving bend radius min. (mm)Max. tensile load (N)Reference current (A)
H07ZZ-F 1x1.55.87.1284322.524
H07ZZ-F 1x2.56.47.9324737.532
H07ZZ-F 1x47.3936546042
H07ZZ-F 1x689.839599054
H07ZZ-F 1x109.311.9487115073
H07ZZ-F 1x1610.613.4548024098
H07ZZ-F 1G1610.613.4548024098
H07ZZ-F 1x3513.717.972107525158
H07ZZ-F 1x5015.920.682124750198
H07ZZ-F 1x7018.123.3931401050245
H07ZZ-F 1x9520.6261041561425292
H07ZZ-F 1x12022.928.61141721800344
H07ZZ-F 1x1502531.41261882250391
H07ZZ-F 1x18527.634.41382062775448
H07ZZ-F 1x24030.638.31532303600528
H07ZZ-F 1x30033.541.91682514500608
H07ZZ-F 1x40037.446.81872816000726
H07ZZ-F 1x50041.3522083127500830
H07ZZ-F 2x17.71040603019
H07ZZ-F 2x1.58.51144664524
H07ZZ-F 2x2.510.213.152797532
H07ZZ-F 2x411.815.1609112042
H07ZZ-F 2x613.116.86710118054
H07ZZ-F 2x1017.722.69013630073
H07ZZ-F 2x1620.225.710315448098
H07ZZ-F 2x2524.330.7123184750129
H07ZZ-F 3G18.310.743644519
H07ZZ-F 3G1.59.211.9487167.524
H07ZZ-F 3G2.510.9145684112.532
H07ZZ-F 3G412.716.2659718042
H07ZZ-F 3G614.1187210827054
H07ZZ-F 3G1019.124.29714545073
H07ZZ-F 3G1621.827.611016672098
H07ZZ-F 3G2526.1331321981125129
H07ZZ-F 3G3529.337.11482231575158
H07ZZ-F 3G5034.142.91722572250198
H07ZZ-F 3G7038.448.31932903150245
H07ZZ-F 3G9543.3542163244275292
H07ZZ-F 3G12047.4602403605400344
H07ZZ-F 3G15052662643966750391
H07ZZ-F 3G18557722884328325448
H07ZZ-F 3G240658232849210800528
H07ZZ-F 4G19.211.948716019
H07ZZ-F 4G1.510.213.152799024
H07ZZ-F 4G2.512.115.5629315032
H07ZZ-F 4G41417.97210724042
H07ZZ-F 4G615.7208012036054
H07ZZ-F 4G1020.926.510615960073
H07ZZ-F 4G1623.830.112018196098
H07ZZ-F 4G2528.936.61462201500129
H07ZZ-F 4G3532.541.11642472100158
H07ZZ-F 4G5037.747.51902853000198
H07ZZ-F 4G7042.7542163244200245
H07ZZ-F 4G9548.4612443665700292
H07ZZ-F 4G12053662643967200344
H07ZZ-F 4G15058732924389000391
H07ZZ-F 4G185648032048011100448
H07ZZ-F 5G110.213.152797515
H07ZZ-F 5G1.511.214.45886112.518
H07ZZ-F 5G2.513.31768102187.526
H07ZZ-F 5G415.619.98011930034
H07ZZ-F 5G617.522.28913345044
H07ZZ-F 5G1022.929.111617575061
H07ZZ-F 5G1626.433.3133200120082
H07ZZ-F 5G253240.41622421875108
H07ZZ-F 6G1.513.417.26910313518
H07ZZ-F 7G1.514.718.775112157.518
H07ZZ-F 12G1.517.622.49013427018
H07ZZ-F 18G1.520.726.310515840518
H07ZZ-F 19G1.520.726.3105158427.518
H07ZZ-F 24G1.524.330.712318454018
H07ZZ-F 36G1.527.835.214121181018
H07ZZ-F 6G2.515.7208012022526
H07ZZ-F 7G2.517.121.887131262.526
H07ZZ-F 12G2.520.626.210515745026
H07ZZ-F 18G2.524.430.912418567526
H07ZZ-F 24G2.528.836.414621890026
H07ZZ-F 36G2.533.241.8167251135026
H07ZZ-F 6G418.223.29313936034
H07ZZ-F 7G420.125.510215342034
H07ZZ-F 12G424.430.912418572034
H07ZZ-F 18G428.836.4146218108034

Reference currents apply to continuous DC or 50–60 Hz AC service at 30°C ambient, on a surface, with two or three loaded cores; all cores loaded for multicore control cables. Apply the relevant VDE 0298 installation corrections.

Fixed and moving bend-radius values belong to the configuration on the same row. G indicates a green/yellow protective conductor.

Standards

Standards

H07ZZ-F Halogen-Free Rubber Cable 450/750 V standards and test references
Standard or specificationApplication
DIN EN 50525-3-21Cable construction reference.
IEC 60228Flexible conductor construction.
EN 50363-5Halogen-free compound requirements.
EN 61034-2Smoke-density test reference.
EN 60332-3-24Bunched-cable flame propagation test reference.
EN 60811-404Oil-resistance test reference.
EN 50363-6EM8 halogen-free sheath compound reference.
EN 60332-1-2Single-cable flame propagation test reference.
Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.