SEOOW Cable 600 V TPE Portable Power Cord

600 V portable cord with Class K copper conductors, TPE insulation and an oil-resistant TPE jacket. Size schedule covers 18–10 AWG with two- to six-conductor configurations.

Product information
Brand
TEBAOFLEX
Product overview

SEOOW cable is a 600 V flexible portable power cord with thermoplastic elastomer insulation and an overall TPE jacket. It supplies portable tools, small motors, appliances and industrial equipment where the cable must combine flexible handling with resistance to oil, moisture and abrasion.

The conductor construction uses Class K stranded bare copper. The size schedule covers 18–10 AWG, including two-, three-, four- and five-conductor arrangements, plus a six-conductor 12 AWG configuration. Conductor colours identify the circuit functions, with a green grounding conductor in the configurations of three or more conductors shown.

The selected construction has a temperature range of -50°C to +105°C. TPE insulation and sheathing distinguish SEOOW from thermoset-rubber SOOW portable cable. Compare the materials and operating conditions together when choosing between the two families, especially where the route includes repeated handling, oil exposure or outdoor use.

Use the nominal diameter and weight table to check connection space and cable handling, and use the stated current-rating conditions when sizing the circuit. Severe quarry or mining duty calls for a dedicated heavy-duty cable selection. Send the AWG size, conductor count, cable length, jacket colour and equipment conditions for a TEBAOFLEX quotation tailored to the connection.

Explore the industrial cable range for related configurations.

When comparing 600 V SEOOW thermoplastic elastomer (TPE) portable cord with thermoset rubber North American cords, evaluate these options: SOOW Cable 600V for Heavy-Duty Portable Power (600 V EPDM-insulated, CPE-jacketed thermoset cord for high-heat and heavy abrasion); SJOOW Cable 300V Portable Power Cable (300 V junior-service EPDM/CPE rubber cord for lighter portable hand tools and appliances). Match voltage rating, cold-temperature flexibility, and jacket material to your operating duty.

Construction

Construction

SEOOW uses TPE for both core insulation and the outer jacket. The illustration shows a representative three-conductor cord.

SEOOW cross-section with black, white and green TPE-insulated conductors
Representative cable construction.
SEOOW Cable 600 V TPE Portable Power Cord construction
ComponentMaterial and construction
ConductorClass K stranded soft-drawn bare copper to ASTM B174.
InsulationColour-coded thermoplastic elastomer (TPE).
Core colours2C: black/white. 3C: black/white/green. 4C: black/white/red/green. 5C: black/white/red/orange/green. 6C: black/white/red/orange/blue/green.
Outer jacketOil-, water-, moisture- and abrasion-resistant TPE; black, white or yellow.
Applications

Applications

SEOOW portable cord is used for flexible equipment leads and temporary power connections within its electrical and environmental ratings.

TPE portable power cord supplying a small industrial compressor in a maintenance workshop
Application illustration.
  • Portable tools, appliances and small motors.
  • Industrial equipment and temporary indoor or outdoor power.
  • Oil- and moisture-exposed equipment leads.
  • For severe quarry or mining service, select a cable designed for that mechanical environment.

For portable cord letter nomenclature and European harmonized equivalents to 600 V SEOOW cordage, review these references: SOOW vs SJOOW vs SEOOW: What the Cord Letters Mean and Which to Specify (side-by-side breakdown of voltage class, TPE vs EPDM/CPE compounds, and temperature ratings); H05RN-F / H05RR-F Cable 300/500 V (300/500 V European harmonized rubber cable for export machinery and light portable equipment). Check AWG vs metric cross-section and plug compatibility before specifying.

Specifications

Specifications

SEOOW Cable 600 V TPE Portable Power Cord technical data
ParameterValue
Rated voltage600 V
Temperature range-50°C to +105°C
Conductor size schedule18–10 AWG
Conductor arrangements2, 3, 4 or 5 conductors; 6-conductor option at 12 AWG.
Insulation and jacketTPE
Standard jacket coloursBlack, white or yellow
SEOOW 600 V dimensions and reference current ratings
Model and configurationStranding (No./AWG)Nominal insulation thickness (mm)Nominal jacket thickness (mm)Nominal OD (mm)Approx. weight (lb/1000 ft)Reference current (A)
SEOOW 2C × 18 AWG16/300.761.528.695410
SEOOW 3C × 18 AWG16/300.761.529.196410
SEOOW 4C × 18 AWG16/300.761.529.83797
SEOOW 5C × 18 AWG16/300.762.0311.731087
SEOOW 2C × 16 AWG26/300.761.529.326213
SEOOW 3C × 16 AWG26/300.761.529.837713
SEOOW 4C × 16 AWG26/300.761.5210.549110
SEOOW 5C × 16 AWG26/300.762.0312.501288
SEOOW 2C × 14 AWG41/301.142.0312.6211418
SEOOW 3C × 14 AWG41/301.142.0313.2614018
SEOOW 4C × 14 AWG41/301.142.0314.3516615
SEOOW 5C × 14 AWG41/301.142.4116.3121412
SEOOW 2C × 12 AWG65/301.142.4114.4815325
SEOOW 3C × 12 AWG65/301.142.4115.0418525
SEOOW 4C × 12 AWG65/301.142.4116.3122720
SEOOW 5C × 12 AWG65/301.142.4117.9628016
SEOOW 6C × 12 AWG65/301.142.4118.9233514
SEOOW 2C × 10 AWG104/301.142.4115.6719630
SEOOW 3C × 10 AWG104/301.142.4116.5624530
SEOOW 4C × 10 AWG104/301.142.4117.8330125
SEOOW 5C × 10 AWG104/301.142.4119.3535820

Reference currents apply at 30°C ambient according to NEC Table 400.5(A) and CEC Table 12. A grounding conductor, or a conductor carrying only the unbalanced current of other conductors, is not counted as a current-carrying conductor.

Dimensions, thicknesses and weights are nominal. Weight is stated in lb/1000 ft. Specify AWG, conductor count, jacket colour and cable length for the required configuration.

Standards

Standards

SEOOW Cable 600 V TPE Portable Power Cord standards and test references
Standard or specificationApplication
UL 62Flexible-cord construction reference.
CSA C22.2 No. 49Flexible cords and cables reference.
ASTM B174Class K copper conductor stranding.
ICEA S-58-679, Method 1, Table 1Conductor colour-code reference.
Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.