Submersible Pump Cables TEBAOFLEX

TGFLSH / TGFLSH2G 450/750 V Flat Hot Water Pump Cable

TGFLSH / TGFLSH2G are 450/750 V flat halogen-free hot-water pump cables with Class 5 tinned copper and SIR insulation.

  • TGFLSH: EVA outer sheath
  • TGFLSH2G: SIR outer sheath
  • Separate conductor-temperature and flexible-use limits
  • Flat entry and bending-plane coordination

Send the full designation, core count, conductor section, cable height and width, installed length and pump-entry drawing for a technical quotation.

Product information
Brand
TEBAOFLEX
Product overview

TGFLSH and TGFLSH2G Flat Hot-Water Pump Connections

TGFLSH and TGFLSH2G are 450/750 V flat, halogen-free cables for hot-water submersible pumps and immersed electrical equipment under medium mechanical stress. Both use Class 5 tinned copper conductors with SIR silicone rubber insulation. TGFLSH has an EVA outer sheath; TGFLSH2G has an SIR outer sheath.

Select the sheath version before coordinating the pump entry. The two constructions have different conductor-temperature and flexible-use ambient limits, so the full designation matters when replacing a lead. Match the selected variant to the motor circuit, installation conditions and sealing materials.

A flat cable needs both height and width to fit the entry. Check the slot, sealing sleeve, clamp orientation and available bending plane together. Reserve separate fixed and flexible bend space, and support the cable independently from the pump lifting system. The flat arrangement is a geometry choice; the protective-conductor requirement follows the equipment drawing.

For industrial or well installations, include the actual water composition and treatment chemicals with the enquiry. Coordinate wet-to-dry transitions and termination space before choosing the installed length. Immersion depth and the permitted water-temperature limit are confirmed for the specified project. Use these cables in non-hazardous locations.

For TGFLSH or TGFLSH2G selection, explore the submersible pump cable range; for TGFLSH and TGFLSH2G entry planning, read the minimum bending radius guide.

Construction

Construction

The flat family uses parallel insulated conductors. Select the complete sheath version and the required protective-conductor arrangement.

TGFLSH flat three-core cross-section with tinned copper, SIR insulation and EVA sheath
Representative TGFLSH flat arrangement: three parallel SIR-insulated conductors and an EVA outer sheath.
TGFLSH2G flat three-core cross-section with tinned copper and SIR insulation and sheath
Representative TGFLSH2G flat arrangement: three parallel SIR-insulated conductors and an SIR outer sheath.
TGFLSH and TGFLSH2G construction comparison
ElementTGFLSHTGFLSH2G
ConductorClass 5 flexible tinned copperClass 5 flexible tinned copper
Core insulationSIR silicone rubberSIR silicone rubber
Outer sheathEVA rubber compoundSIR silicone rubber
Core identificationDIN EN 50525-1; G configurations include a green/yellow protective conductor.DIN EN 50525-1; G configurations include a green/yellow protective conductor.
ArrangementParallel insulated cores in a flat cable.Parallel insulated cores in a flat cable.
Metallic screenUnscreenedUnscreened
Applications

Applications

Power connections to hot-water pumps and immersed electrical equipment in industrial, agricultural, indoor and outdoor supported installations under medium mechanical stress.

Flat hot-water pump cable on a supported industrial pump route
Application illustration: supported flat-cable routing to a hot-water pump with separate lifting equipment.
Flat hot-water pump cable selection
Selection pointRequirement
Sheath selectionChoose TGFLSH with EVA or TGFLSH2G with SIR and use that variant’s conductor and ambient limits.
Entry geometrySpecify finished height and width, slot profile and seal compression for the selected flat construction.
Bending and supportPlan the flat-cable bending plane and support the cable independently from pump lifting equipment.
Water chemistryState the actual hot-water composition and treatment chemicals for material selection.
Water service conditionsConfirm immersion depth and the permitted water-temperature limit with the project enquiry.
Location restrictionNot for explosion-hazardous areas.
Specifications

Specifications

Select the sheath variant first, then coordinate the electrical conditions, conductor temperature and installed flat-cable geometry.

TGFLSH / TGFLSH2G common technical profile
ParameterValue or condition
Rated voltage U₀/U450/750 V
ConductorClass 5 flexible tinned copper
Core insulationSIR silicone rubber
Sheath optionsTGFLSH: EVA; TGFLSH2G: SIR
ShapeFlat, 3–4 cores
Metallic screenUnscreened
TGFLSH 450/750 V — EVA-sheathed profile
ParameterValue or condition
ModelTGFLSH 450/750 V
Outer sheathEVA
Maximum conductor temperature130 °C
Short-circuit conductor temperature / duration350 °C / maximum 5 s
Minimum ambient temperature, fixed−50 °C
Minimum ambient temperature, flexible−25 °C
Maximum AC operating voltage0.476/0.825 kV
Maximum DC operating voltage0.619/1.238 kV
AC test voltage — main cores2.5 kV / 15 minutes
Maximum conductor tensile stress15 N/mm²
Minimum bend radius, fixed3 × Dmax
Minimum bend radius, flexible4 × Dmax
Family range3–4 cores; cross-sections up to 240 mm². Select core count and cross-section together.
TGFLSH2G 450/750 V — SIR-sheathed profile
ParameterValue or condition
ModelTGFLSH2G 450/750 V
Outer sheathSIR
Maximum conductor temperature150 °C
Short-circuit conductor temperature / duration350 °C / maximum 5 s
Minimum ambient temperature, fixed−50 °C
Minimum ambient temperature, flexible−50 °C
Maximum AC operating voltage0.476/0.825 kV
Maximum DC operating voltage0.619/1.238 kV
AC test voltage — main cores2.5 kV / 15 minutes
Maximum conductor tensile stress15 N/mm²
Minimum bend radius, fixed3 × Dmax
Minimum bend radius, flexible4 × Dmax
Family range3–4 cores; cross-sections up to 240 mm². Select core count and cross-section together.
Protected fixed applications and installation conditions
ParameterValue or condition
Protected fixed AC application allowanceUp to 1000 V in protected fixed conduits, equipment, well installations or motor rotor circuits.
Protected fixed DC application allowanceUp to 750 V to earth under the same protected fixed conditions.
Motor-system AC test condition3 kV for maximum 3 minutes; distinct from the main-core cable test.
Flat-cable bending referenceApply Dmax to the selected cable drawing; coordinate finished height, width and the bending plane with the pump entry.
Location restrictionNot for explosion-hazardous areas.
Standards

Standards

TGFLSH and TGFLSH2G construction and test references
ReferenceApplication
EN 50525-2-21Construction reference: based on EN 50525-2-21.
DIN EN 60228Class 5 conductor reference.
DIN EN 50525-1Core identification reference.
DIN EN 50525-2-21Water-resistance reference.
DIN EN 50565-2General cable-use and installation guidance.
Main-core AC cable test2.5 kV for 15 minutes.
Motor-system AC test3 kV for maximum 3 minutes in the stated motor-test application.

For conductor classes, see the IEC 60228 standard scope.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.