LIHH FE180 & LIHCH FE180 Silicone/LSZH Fire Alarm Control Cable (300 V, IEC 60331)
LIHH FE180 unscreened and LIHCH FE180 screened fire alarm and security control cables (300 V, 1,500 V AC test) pair stranded tinned copper conductors (2×0.50 mm² to 25×0.75 mm², 19×1.50 mm² and 10×2.50 mm²) with ceramifying FE180 silicone rubber core insulation and a low-smoke zero-halogen orange LSZH-HFFR outer sheath per IEC 60331-11/21, VDE 0472-814 and IEC 60332-3-24.
LIHH FE180 and screened LIHCH FE180 fire alarm, voice-evacuation and building-security control cables keep life-safety signalling, smoke-damper commands and emergency PA loops operational during a building or tunnel fire, covering 2×0.50 mm² through 25×0.75 mm², 19×1.50 mm² and 10×2.50 mm² (5.00 mm to 14.85 mm nominal OD, 300 V operating voltage, 1,500 V AC test).
Unlike PVC control cables that release dense toxic HCl smoke or mica-taped solid installation wires that crack during tight conduit pulls, LIHH FE180 insulates stranded tinned copper conductors directly with flexible ceramifying silicone rubber (`>= 200 MOhm*km`, `120 nF/km` mutual capacitance) beneath an abrasion-resistant safety-orange LSZH-HFFR thermoplastic polyolefin sheath (`-30 °C` to `+90 °C`, `7.5x OD` fixed bend radius). When exposed to fire, the silicone core vitrifies into a solid SiO2 dielectric sleeve (`VDE 0472-814 FE180` / `IEC 60331-11/21`), while LIHCH FE180 adds a foil-and-braid electromagnetic shield against VFD lift/HVAC interference.
Specify LIHH FE180 for unscreened fire-zone solenoids, beacon/sounder circuits and multi-core damper status looms, or LIHCH FE180 for RS-485 addressable detector loops and 100 V voice-evacuation audio; if ambient service temperature permanently exceeds +90 °C up to +200 °C, choose our all-silicone SIMH FE180 PH120 cable instead (MOQ 50 m, standard 305 m / 500 m reels, 7 to 45 working days).
Explore the high-temperature wire and cable range for related configurations.
LIHH FE180 & LIHCH FE180 Fire Alarm Cable Construction
TEBAOFLEX builds LIHH FE180 and LIHCH FE180 cables to combine fast, low-friction conduit pulling (`7.5x OD` bend radius) with bunched-tray flame retardance (`IEC 60332-3-24`) and ceramifying core survival.

| Component | Material and construction |
|---|---|
| 1. Stranded Tinned Copper Conductors (IEC 60228) | Flexible stranded annealed tinned copper wires in 0.50, 0.75, 1.00, 1.50 and 2.50 mm² (max loop resistance 39.0, 26.0, 19.5, 13.3 and 7.98 Ohm/km at 20 °C). |
| 2. Ceramifying Silicone Rubber Core Insulation (FE180) | Halogen-free fire-resistant silicone rubber compound maintaining >= 200 MOhm*km insulation resistance at 20 °C and vitrifying into an insulating silica crust during fire. |
| 3. Core Identification & Short-Pitch Cabling | Up to 5 cores colour-coded (blue, brown, black, grey, green-yellow); 6 to 25 cores black with sequential white numerals cabled under a halogen-free separator tape. |
| 4. Optional EMC Screen (LIHCH FE180 Variant) | 100% glass/polyester + aluminium/PET tape with tinned copper drain wire and >= 80% tinned copper wire braid isolating fire-panel data and 100 V audio from power transients. |
| 5. Flame-Retardant Orange LSZH-HFFR Outer Sheath | Low-smoke zero-halogen thermoplastic HFFR compound (EN 50290-2) in safety orange (red on request), rated -30 °C to +90 °C and passing IEC 60332-3-24 Cat C bunched flame spread. |
LIHH FE180 & LIHCH FE180 Designation Code Breakdown
- LI: Stranded flexible tinned copper control conductor per IEC 60228 (0.50 to 2.50 mm²)
- H (first H): Halogen-free ceramifying silicone rubber core insulation providing fire-circuit insulation integrity
- C (in LIHCH): Overall electromagnetic screen (Al/PET tape + tinned copper drain wire and tinned copper braid)
- H (outer H): Halogen-free low-smoke flame-retardant thermoplastic outer sheath (LSZH-HFFR, orange)
- FE180: 180-minute insulation integrity under >= 750 °C flame exposure per VDE 0472-814 / IEC 60331-11/21
LIHH FE180 Tunnel, Metro, Hospital & PA/VA Applications
Deploy LIHH FE180 and LIHCH FE180 across high-occupancy public infrastructure, underground transit tunnels and industrial fire-detection networks.

- Underground metro stations, road/rail tunnels, airport terminals and railway concourses requiring IEC 61034 high light-transmittance low-smoke escape visibility.
- Hospitals, high-rise hotels, shopping centres and data centres wiring addressable smoke/heat detector loops, manual call points and alarm sounders.
- 100 V line public-address / voice-evacuation (PA/VA) speaker risers, firefighter intercom telephones and stairwell pressurization fan controls (LIHCH FE180).
- Smoke-extraction damper actuators, fire-curtain release panels, sprinkler flow-switch monitoring and BMS emergency interlock multi-core trunks.
LIHH FE180 vs LIHCH FE180 vs SIMH FE180 PH120 vs LiHH
| Cable Designation | Core / Jacket Material | EMC Shielding & Temp | When to Specify |
|---|---|---|---|
| LIHH FE180 (this page) | Ceramifying silicone + orange LSZH-HFFR | Unscreened, -30 to +90 °C | Fire-alarm sounders, beacons, smoke dampers & solenoid release circuits |
| LIHCH FE180 (this page) | Ceramifying silicone + foil/Cu braid + LSZH | Foil + tinned Cu braid, -30 to +90 °C | Addressable fire detector loops, RS-485 & 100 V voice-evacuation PA/VA |
| SIMH FE180 PH120 | Ceramifying EI2 silicone + orange EM9 silicone | Unscreened (screen opt.), -60 to +200 °C | Steelworks, kilns & boiler zones where ambient exceeds +90 °C |
| Standard LiHH / LiHCH (Non-FE180) | Thermoplastic LSZH core + LSZH sheath | Halogen-free flame retardant only | General halogen-free data/control circuits NOT required to run during fire |
Always choose FE180 silicone-core LIHH/LIHCH over standard LiHH when fire codes mandate continued alarm/evacuation operation during a fire.
LIHH FE180 & LIHCH FE180 Fire Alarm Cable RFQ Checklist
- Shielding variant: unscreened LIHH FE180 or EMC foil-and-braid screened LIHCH FE180 (or twisted-pair JE-H(St)H FE180 equivalent).
- Core count x conductor cross-section (for example 2x1.50 mm², 4x1.50 mm², 12x1.50 mm² or 2x2.50 mm² for long 100 V PA/VA runs).
- Outer LSZH-HFFR jacket colour: standard safety orange, fire-alarm red, or project-coded colour.
- Target fire/smoke test package (IEC 60331-11/21 FE180, IEC 60332-3-24 Cat C, IEC 61034, IEC 60754-1/2).
- Put-up reel length (305 m or 500 m standard reels; MOQ 50 m) and delivery schedule (7 to 45 working days).
Related selection resources
- Fire-resistant silicone and high-temperature cable catalog
- Screened industrial control and instrumentation cable range
- Case study: Shielded 2x2.5 mm² voice-evacuation fire safety cable supply
- SiHFC 180 °C Copper-Braided Screened All-Silicone Control Cable
- Engineering guide: Copper braid shielding vs spiral/foil screens for EMC
- Comparison of silicone vs LSZH vs fluoropolymer temperature ratings
LIHH FE180 & LIHCH FE180 Frequently Asked Questions
What is the difference between LIHH FE180 and LIHCH FE180 fire alarm cables?
Both cables use stranded tinned copper conductors, ceramifying FE180 silicone core insulation and an orange LSZH-HFFR outer sheath, but LIHCH FE180 adds an aluminium/polyester tape plus tinned copper wire braid shield to protect addressable fire-panel loops and 100 V voice-evacuation audio against electromagnetic interference.
Why does LIHH FE180 combine silicone core insulation with an LSZH-HFFR outer sheath instead of all-silicone?
In subways, tunnels, hospitals and high-rise risers (-30 °C to +90 °C ambient), a tough thermoplastic LSZH-HFFR outer jacket pulls through long conduits with much higher cut/abrasion resistance and passes IEC 60332-3-24 bunched flame tests economically, while the inner silicone cores vitrify into SiO2 to maintain 180-minute FE180 circuit insulation if fire burns away the outer jacket.
Can LIHH FE180 or LIHCH FE180 be used for 100 V voice-evacuation speaker lines?
Yes. 2x1.50 mm² (13.3 Ohm/km max loop resistance) and 2x2.50 mm² (7.98 Ohm/km max loop resistance) LIHH FE180 and screened LIHCH FE180 are standard choices for low-voltage-drop 100 V PA/VA emergency voice-evacuation circuits.
Can LIHH FE180 operate in a +180 °C industrial furnace room?
No. Although the inner silicone cores survive fire, the outer LSZH-HFFR polyolefin sheath is rated for -30 °C to +90 °C continuous ambient; for continuous +90 °C to +200 °C hot industrial zones, specify our all-silicone SIMH FE180 PH120 cable.
What reel lengths and minimum order quantities apply to LIHH FE180 and LIHCH FE180?
Standard contractor put-up is 305 m or 500 m per reel for uninterrupted riser and tunnel pulls, with a 50 m minimum order quantity on custom multi-core sizes and 7 to 45 working days production lead time.
LIHH FE180 & LIHCH FE180 Dimensional & Electrical Schedule
LIHH FE180 Key Voltage, Loop Resistance, Fire & Reel Summary
- Silicone FE180 + LSZH-HFFR: Ceramifying silicone core insulation maintains 180-minute flame insulation integrity (FE180 / E90 system reference) inside a tough orange LSZH-HFFR jacket
- Unscreened LIHH & screened LIHCH: Available unscreened (LIHH FE180) or with Al/PET tape + tinned copper drain/braid EMC screen (LIHCH FE180) for addressable loops and PA/VA audio
- Full 0.50 to 2.50 mm² matrix: 2 to 25 cores across 0.50, 0.75, 1.00, 1.50 and 2.50 mm² (5.00 mm to 14.85 mm OD; >= 200 MOhm*km insulation resistance; 120 nF/km mutual capacitance)
- Subway & hospital smoke safety: Passes IEC 60332-3-24 bunched vertical flame spread, IEC 61034 low smoke density and IEC 60754-1/2 zero halogen acid gas evolution
- Project reels & 305 m drums: MOQ 50 m (standard 305 m / 500 m installation reels) manufactured in 7 to 45 working days
| Parameter | Value |
|---|---|
| Rated voltage | 300 V operating voltage with 1500 V AC 50 Hz dielectric test voltage |
| Fire survival and flame tests | FE180 insulation integrity (VDE 0472-814 / IEC 60331-11/21 E90 system reference) plus IEC 60332-3-24 Cat C bunched vertical flame retardance |
| Conductor and core matrix | Stranded tinned copper across 0.50, 0.75, 1.00, 1.50 and 2.50 mm2 from 2 cores up to 25 cores (unscreened LIHH FE180 and screened LIHCH FE180) |
| Electrical parameters at 20 C | At least 200 MOhm*km insulation resistance and 120 nF/km nominal mutual capacitance (loop resistance 39.0 to 7.98 Ohm/km) |
| Temperature, bend and supply | -30 C to +90 C fixed service, 7.5x OD minimum bend radius, MOQ 50 m (standard 305 m / 500 m reels) in 7 to 45 working days |
| Low-smoke zero-halogen safety | Orange LSZH-HFFR outer sheath tested to IEC 60754-1/2 zero halogen acid gas and IEC 61034 low smoke density |
| Optional jacket colours | Standard safety orange; fire-alarm red, white or grey LSZH-HFFR outer sheaths produced on project reel runs |
LIHH FE180 & LIHCH FE180 Fire Alarm Control Cable Dimensional Schedule (0.50 to 2.50 mm²)
| Model & Core Size (mm²) | Construction Type | Overall OD (mm) | Max Loop Res. (Ω/km) | Copper Index (kg/km) | Nominal Weight (kg/km) | Next step |
|---|---|---|---|---|---|---|
| LIHH FE180 2x0.50 mm² | Unscreened Silicone/LSZH | 5.00 | 39.0 | 8 | 30 | Request this size |
| LIHH FE180 4x0.50 mm² | Unscreened Silicone/LSZH | 5.95 | 39.0 | 17 | 49 | Request this size |
| LIHH FE180 7x0.50 mm² | Unscreened Silicone/LSZH | 7.15 | 39.0 | 29 | 77 | Request this size |
| LIHH FE180 12x0.50 mm² | Unscreened Silicone/LSZH | 9.10 | 39.0 | 50 | 121 | Request this size |
| LIHH FE180 24x0.50 mm² | Unscreened Silicone/LSZH | 12.65 | 39.0 | 101 | 230 | Request this size |
| LIHH FE180 2x0.75 mm² | Unscreened Silicone/LSZH | 5.70 | 26.0 | 13 | 40 | Request this size |
| LIHH FE180 3x0.75 mm² | Unscreened Silicone/LSZH | 6.00 | 26.0 | 19 | 51 | Request this size |
| LIHH FE180 4x0.75 mm² | Unscreened Silicone/LSZH | 6.75 | 26.0 | 25 | 66 | Request this size |
| LIHH FE180 7x0.75 mm² | Unscreened Silicone/LSZH | 7.90 | 26.0 | 44 | 100 | Request this size |
| LIHH FE180 12x0.75 mm² | Unscreened Silicone/LSZH | 10.55 | 26.0 | 76 | 168 | Request this size |
| LIHH FE180 19x0.75 mm² | Unscreened Silicone/LSZH | 12.20 | 26.0 | 120 | 246 | Request this size |
| LIHH FE180 25x0.75 mm² | Unscreened Silicone/LSZH | 14.55 | 26.0 | 158 | 328 | Request this size |
| LIHH FE180 2x1.00 mm² | Unscreened Silicone/LSZH | 5.90 | 19.5 | 17 | 45 | Request this size |
| LIHH FE180 3x1.00 mm² | Unscreened Silicone/LSZH | 6.25 | 19.5 | 25 | 58 | Request this size |
| LIHH FE180 4x1.00 mm² | Unscreened Silicone/LSZH | 6.95 | 19.5 | 34 | 75 | Request this size |
| LIHH FE180 7x1.00 mm² | Unscreened Silicone/LSZH | 8.20 | 19.5 | 59 | 116 | Request this size |
| LIHH FE180 12x1.00 mm² | Unscreened Silicone/LSZH | 10.95 | 19.5 | 101 | 196 | Request this size |
| LIHH FE180 20x1.00 mm² | Unscreened Silicone/LSZH | 13.35 | 19.5 | 168 | 305 | Request this size |
| LIHH FE180 2x1.50 mm² | Unscreened Silicone/LSZH | 6.80 | 13.3 | 25 | 61 | Request this size |
| LIHH FE180 3x1.50 mm² | Unscreened Silicone/LSZH | 7.20 | 13.3 | 37 | 80 | Request this size |
| LIHH FE180 4x1.50 mm² | Unscreened Silicone/LSZH | 7.80 | 13.3 | 49 | 99 | Request this size |
| LIHH FE180 7x1.50 mm² | Unscreened Silicone/LSZH | 9.25 | 13.3 | 86 | 156 | Request this size |
| LIHH FE180 12x1.50 mm² | Unscreened Silicone/LSZH | 12.45 | 13.3 | 147 | 264 | Request this size |
| LIHH FE180 19x1.50 mm² | Unscreened Silicone/LSZH | 14.85 | 13.3 | 233 | 406 | Request this size |
| LIHH FE180 2x2.50 mm² | Unscreened Silicone/LSZH | 7.90 | 7.98 | 41 | 86 | Request this size |
| LIHH FE180 3x2.50 mm² | Unscreened Silicone/LSZH | 8.35 | 7.98 | 61 | 114 | Request this size |
| LIHH FE180 4x2.50 mm² | Unscreened Silicone/LSZH | 9.15 | 7.98 | 82 | 146 | Request this size |
| LIHH FE180 10x2.50 mm² | Unscreened Silicone/LSZH | 14.65 | 7.98 | 205 | 355 | Request this size |
| LIHCH FE180 2x0.75 mm² | Foil + Cu Braid Screened | 6.30 | 26.0 | 24 | 56 | Request this size |
| LIHCH FE180 2x1.00 mm² | Foil + Cu Braid Screened | 6.50 | 19.5 | 29 | 64 | Request this size |
| LIHCH FE180 2x1.50 mm² | Foil + Cu Braid Screened | 7.40 | 13.3 | 40 | 82 | Request this size |
| LIHCH FE180 4x1.50 mm² | Foil + Cu Braid Screened | 8.45 | 13.3 | 68 | 126 | Request this size |
| LIHCH FE180 2x2.50 mm² | Foil + Cu Braid Screened | 8.55 | 7.98 | 59 | 112 | Request this size |
Intermediate core counts across the full 67-item series (including 3, 5, 6, 8, 10, 14, 16, 18 and 20 cores in 0.50, 0.75, 1.00, 1.50 and 2.50 mm², both unscreened LIHH FE180 and screened LIHCH FE180) are produced to order; final values are confirmed on the quotation drawing.
Note that DIN 4102-12 E30–E90 functional system survival depends on the tested combination of cable AND certified fire-rated bracket/tray support hardware installed on site.
Minimum order quantity is 50 m (with standard 305 m or 500 m contractor reels for fast site pulling) and a manufacturing lead time of 7 to 45 working days.
ASCII part references for BOM and ERP entry: TF-LIHH-FE180-2X0.75; TF-LIHH-FE180-2X1.0; TF-LIHH-FE180-2X1.5; TF-LIHH-FE180-4X1.5; TF-LIHH-FE180-7X1.5; TF-LIHH-FE180-12X1.5; TF-LIHH-FE180-2X2.5; TF-LIHH-FE180-4X2.5; TF-LIHCH-FE180-2X1.0; TF-LIHCH-FE180-2X1.5; TF-LIHCH-FE180-2X2.5.
LIHH FE180 IEC 60331, IEC 60332-3-24 & LSZH Standards
| Standard or specification | Application |
|---|---|
| IEC 60331-11 & IEC 60331-21 / VDE 0472-814 (FE180) | 180-minute fire insulation integrity on silicone-insulated control cores under >= 750 °C flame. |
| IEC 60332-3-24 (Category C Bunched Flame Test) | Vertical flame-propagation suppression on bunched cables mounted in building risers and tunnel trays. |
| IEC 60754-1, IEC 60754-2 & IEC 61034 | Zero halogen acid gas release, low gas conductivity/acidity and >= 60% light transmittance low-smoke density. |
| IEC 60228 & EN 50290-2 | Stranded tinned copper conductor resistance and LSZH-HFFR outer sheathing compound mechanical requirements. |
Certifications and document support
TEBAOFLEX ISO 9001 quality management and factory electrical test documentation
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
SiHFC & SiHF-C-Si EMC Screened Silicone Cable (300/500 V, 180 °C)
A related cable option for a different application or duty profile.
View productSiFCuSi 300/500 V Screened Silicone Cable
A related cable option for a different application or duty profile.
View productSiHF & SiHF-J Multi-Core Flexible Silicone Cable (300/500 V, 180 °C)
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.