Port & Festoon Cables TEBAOFLEX

600V 2PNCT Flexible Rubber Cable (JIS C 3327)

600V 2PNCT cable (also designated CUR-2PNCT, 2PNCT-B, 2PNCT-SB / 2PNCT-BS, 2PNCT-F or 600V 2TC Light) is a JIS C 3327 Class 2 flexible rubber cabtyre cable built with stranded copper conductors, 80°C EP/EPR rubber insulation and a heavy-duty chloroprene rubber (CR) outer sheath for port cranes, festoon trolleys, hoists and mobile industrial equipment.

  • Rated voltage: AC 600 V; 1 to 30 cores, 0.75 mm² to 250 mm² (JIS C 3327 reference range); routine voltage test 3,000 V AC for 1 minute
  • Construction: flexible stranded annealed or tinned copper conductor, 80°C EP/EPR rubber insulation, black chloroprene rubber sheath; yarn-reinforced (2PNCT-B), braid-shielded (2PNCT-SB / 2PNCT-BS), flat (2PNCT-F) and polyurethane (-H-U) crane builds available
  • Outer diameter and ampacity (30°C ambient): 1C 38–150 mm² (15.5–27 mm OD, 209–493 A); 3C 2–60 mm² (11.0–38 mm OD, 23–188 A); 4C 2–50 mm² (12.5–39 mm OD, 21–149 A) — view 2PNCT size, OD and ampacity chart
  • Reference standard: JIS C 3327 (600V Class 2 EP rubber insulated chloroprene cabtyre cable); JCS 0168-1 ampacity basis
  • Supply: MOQ 50 m, cut to length, typical lead time 7–45 working days

For an RFQ, send the designation (2PNCT, CUR-2PNCT, 2PNCT-B, 2PNCT-SB or 2PNCT-F), core count and conductor size (mm² or sq), length per drum, movement duty and required test documentation.

Product information
SKU
600V 2PNCT Cable
Brand
TEBAOFLEX
Product overview

600V 2PNCT Cable (JIS C 3327): Designation, Sub-Types and Selection

600V 2PNCT cable (also written JIS C 3327 2PNCT, CUR-2PNCT, 2PNCT-B, 2PNCT-SB, 2PNCT-F or 600V 2TC Light) is a Japanese-standard Class 2 flexible rubber cabtyre cable for port cranes, festoon systems, hoists and mobile industrial machinery. In the designation 2PNCT, 2 denotes Class 2 mechanical duty, PN denotes ethylene-propylene (EP/EPR) rubber insulation, and CT denotes a chloroprene rubber (CR) cabtyre sheath rated for 600 V AC and 80°C conductor temperature.

Select this family when the circuit needs a 600 V flexible cable with a rubber-insulated, chloroprene-sheathed construction. Core count, conductor cross-section, identification, overall diameter and movement duty must be matched to the equipment drawing rather than inferred from the model name alone.

  • Best fit: mobile machinery, festoons, lifts, hoists and guided trolley connections.
  • Confirm before ordering: core count, conductor size, bend radius, travel path, temperature and test documentation.
  • Use another design when: the route requires vertical reeling, torsion, continuous immersion or a project-specific flame or approval scheme.

See the four technical tabs for the reference construction and selection limits. The Port and Festoon Cable category and RE(V)-2PNCT-RF vertical reeling cable help compare movement duties.

In the JIS C 3327 designation 2PNCT, the leading 2 marks the class 2 cabtyre construction. Sizes are often written with sq for the conductor area in mm² and c for the number of cores, so 2PNCT 2sq-3c means a three-core 2PNCT cable with 2 mm² conductors. Coordinated 2PNCT festoon cable packages for port cranes can include cables designated 2PNCT-B for power, control and multicore signal circuits and 2PNCT-BS for paired PG circuits; the voltage rating, screening and construction of each cable are confirmed against the complete cable schedule.

Procurement note: match the cable entry, drum or festoon hardware, termination kit and final outside diameter to the order drawing.

When pairing 600 V 2PNCT mobile power feeders with multi-core instrumentation or tensile-reinforced reeling cables on the same crane, compare these JIS rubber cables: K-PNCT / K-PNCT-SB Flexible Instrumentation Cable (unshielded K-PNCT and copper-braid-screened K-PNCT-SB flexible rubber cables for encoder, limit-switch, and control signals); PNCT Reeling Cable 600 V–1 kV — Round, Flat and Reinforced Types (round, flat, and center-reinforced PNCT reeling cables for continuous drum winding and festoon travel). Match chloroprene sheath oil/weather resistance and bend radius across power and control runs.

Construction

Construction

The 2TC Light (2PNCT) reference build uses flexible copper conductors and rubber compounds selected for mobile low-voltage service.

LayerReference construction
ConductorAnnealed copper or tinned annealed copper, flexible stranded construction
InsulationEP / EPR rubber around each core
Core assemblyFlexible multi-core lay-up with colour or tracer identification according to the ordered build
Outer sheathChloroprene rubber (CR) sheath

Final fillers, sheath thickness, stranding, diameter and mass depend on core count and conductor size. The order drawing controls.

2PNCT Series Variants: CUR-2PNCT, 2PNCT-B, 2PNCT-SB / 2PNCT-BS, 2PNCT-F and 2PNCT-H-U

Project cable schedules add prefixes or suffixes to 600V 2PNCT to specify reinforcement, shielding or profile for specific crane movements:

600V 2PNCT family designations and TEBAOFLEX factory build options
DesignationStructural featureTypical duty and documented TEBAOFLEX builds
600V 2PNCT / CUR-2PNCTRound Class 2 EP/EPR-insulated, chloroprene-sheathed flexible cable (JIS C 3327 reference structure)Festoon trolleys, lift systems and mobile equipment power or control (1C to 30C, 0.75 to 250 mm²)
600V 2PNCT-BAnti-twist synthetic-yarn reinforcing braid between inner and outer chloroprene sheathHorizontal reeling drums, heavy mobile machinery and crane feeder routes (documented build: 600V 2PNCT-B 3×60 mm²)
600V 2PNCT-SB / 2PNCT-BSTinned copper braid shield over the core assembly (-SB) or over individual twisted pairs (-BS)VFD motor leads, encoder/PG feedback and EMI-sensitive crane instrumentation (documented build: 2PNCT-BS 6P×2.0 mm²)
600V 2PNCT-F / H-2PNCTParallel flat core arrangement in a chloroprene outer sheath for tight mono-plane bendingOverhead crane festoon loops and hoist trolleys where stack height is restricted (documented build: flat 2PNCT 3×38 mm²)
600V 2PNCT-H / 2PNCT-H-UHigh-flexibility multi-core crane build with chloroprene (-H) or polyurethane (-H-U) outer sheathHigh-cycle port crane festoon and multi-core control looms requiring extra abrasion resistance (documented build: 30×3.5 mm²)
Applications

Applications

Use the 600V 2TC Light / 2PNCT family for guided or occasional-movement power and control routes where the selected construction matches the mechanical duty.

  • Crane and festoon trolley systems
  • Lift, hoist and handling equipment connections
  • Portable industrial machinery and mobile tools
  • Factory equipment requiring a flexible 600 V rubber cable

For vertical winding, compare the RE(V)-2PNCT-RF vertical reeling cable. For a fixed product family view, use the Port and Festoon Cable category. Confirm bend radius, travel speed, torsion, temperature and support method before release.

When a crane or container-crane festoon needs a screened round cable for flexible power or control connections, the NGRDGöu-O screened round festoon cable is rated 0.6/1 kV and has a black polychloroprene outer sheath.

600V 2PNCT Cable FAQ

What is 600V 2PNCT cable under JIS C 3327?

600V 2PNCT cable is a Japanese-standard (JIS C 3327) Class 2 flexible rubber cabtyre cable rated at 600 V AC and 80°C conductor temperature. It uses flexible stranded copper conductors, ethylene-propylene (EP/EPR) rubber insulation and a heavy-duty chloroprene rubber (CR) outer sheath for festoon systems, cranes, hoists and mobile industrial equipment.

What are the outer diameter and ampacity of 600V 2PNCT cable by size?

600V 2PNCT cable nominal outer diameter and 30°C free-air ampacity under JIS C 3327 range from 10.5 mm and 27 A for 2×2 mm², 11.0 mm and 23 A for 3×2 mm² (2PNCT 2sq-3c), 13.0 mm and 33 A for 3×3.5 mm², 20 mm and 76 A for 3×14 mm², 31 mm and 142 A for 3×38 mm², to 38 mm and 188 A for 3×60 mm². Single-core power sizes run from 15.5 mm and 209 A at 1×38 mm² up to 27 mm and 493 A at 1×150 mm², while multi-core control builds such as 12×2 mm² (20 mm OD, 13 A) and 30×3.5 mm² (34 mm OD, 14 A) are rated using JCS 0168-1 multi-core reduction factors.

What is the difference between 2PNCT, CUR-2PNCT, 2PNCT-B, 2PNCT-SB and 2PNCT-F?

Standard 600V 2PNCT and CUR-2PNCT share the JIS C 3327 round Class 2 construction for festoon and lift loops. 2PNCT-B adds an anti-twist synthetic reinforcing braid between the inner and outer chloroprene sheaths for reeling drums (such as 3×60 mm²). 2PNCT-SB and 2PNCT-BS add tinned copper braid shielding overall or over twisted pairs (such as 6P×2.0 mm²) for VFD and encoder signals. 2PNCT-F (or H-2PNCT) arranges the cores flat for tight festoon bending, and 2PNCT-H-U uses a polyurethane outer sheath for heavy abrasion.

What does 2PNCT 2sq-3c or 3×38 mm² mean on a cable schedule?

In Japanese cable notation, sq stands for nominal conductor cross-sectional area in square millimetres (mm²) and c stands for the number of cores. Therefore, 2PNCT 2sq-3c (or 2PNCT 3×2 mm²) designates a three-core 600V 2PNCT cable with 2.0 mm² conductors (37/0.26 mm stranding, 11.0 mm nominal OD and 23 A reference ampacity at 30°C), while 2PNCT 3×38 mm² designates three 38 mm² power cores (7/34/0.45 mm stranding, 31 mm round nominal OD and 142 A reference ampacity).

How is 600V 2PNCT cable tested and supplied by TEBAOFLEX?

Every TEBAOFLEX 600V 2PNCT production length undergoes a 3,000 V AC voltage test for 1 minute, 20°C conductor DC resistance measurement and insulation resistance testing before dispatch. Minimum order quantity is 50 m for both standard and custom constructions, supplied cut to drum length with a typical lead time of 7–45 working days depending on size and build.

Every standard size, outer diameter and current rating is in the 600V 2PNCT size, OD and ampacity chart.

Specifications

Specifications

Rated voltageAC 600 V
Reference test voltage3,000 V / 1 minute
Reference temperature80 deg C in the current product data
Core options1, 2, 3, 4, 5, 6, 7, 8, 10, 12 or 16 cores
Conductor-size scope0.75 to 250 mm2 depending on core count and build
Insulation / sheathEP / EPR rubber / chloroprene rubber
Order checksCurrent capacity, voltage drop, outside diameter, mass, bend radius and movement limits

Use the exact quoted construction for ampacity and dimensional calculations. The term 2TC Light is retained as a market designation and does not replace the order-specific drawing.

600V 2PNCT Cable Size, Outer Diameter and Ampacity Chart (JIS C 3327)

Select the core count and conductor cross-section below to compare the JIS C 3327 nominal outer diameter and 30°C free-air ampacity, jump to the full dimensional row or request a quotation for that size.

600V 2PNCT / CUR-2PNCT cable size, nominal outer diameter and ampacity reference values (JIS C 3327 basis, +30°C ambient in air, +80°C conductor)
Size identifierNominal OD mm (JIS C 3327 reference)Ampacity A, 30°C ambient in air (JIS C 3327 reference)Full dataNext step
2PNCT 1×38 mm²15.5209View rowRequest this size
2PNCT 1×60 mm²19.0281View rowRequest this size
2PNCT 1×100 mm²24393View rowRequest this size
2PNCT 1×150 mm²27493View rowRequest this size
2PNCT 2×2 mm²10.527View rowRequest this size
2PNCT 2×3.5 mm²12.539View rowRequest this size
2PNCT 3×2 mm²11.023View rowRequest this size
2PNCT 3×3.5 mm²13.033View rowRequest this size
2PNCT 3×5.5 mm²15.544View rowRequest this size
2PNCT 3×8 mm²17.054View rowRequest this size
2PNCT 3×14 mm²2076View rowRequest this size
2PNCT 3×22 mm²26103View rowRequest this size
2PNCT 3×38 mm²31142View rowRequest this size
2PNCT 3×60 mm²38188View rowRequest this size
2PNCT 4×2 mm²12.521View rowRequest this size
2PNCT 4×3.5 mm²14.030View rowRequest this size
2PNCT 4×5.5 mm²17.040View rowRequest this size
2PNCT 4×14 mm²2269View rowRequest this size
2PNCT 4×38 mm²34128View rowRequest this size
2PNCT 4×50 mm²39149View rowRequest this size
2PNCT 7×2 mm²15.516View rowRequest this size
2PNCT 12×2 mm²2013View rowRequest this size
2PNCT 30×3.5 mm²3414View rowRequest this size

JIS C 3327 600V 2PNCT Dimensions, Stranding, Resistance, Weight and Ampacity

600V 2PNCT / CUR-2PNCT nominal dimensions, conductor construction, mass, DC resistance at 20°C and ampacity at 30°C in free air (JIS C 3327 / JCS 0168-1 reference)
Size identifierConductor construction (No./mm)Insulation mmSheath mmNominal OD mm (JIS C 3327 reference)Min. bending radius mmApprox. mass kg/kmMax. DC resistance at 20°C (Ω/km)Ampacity A, 30°C ambient in air (JIS C 3327 reference)
2PNCT 1×38 mm²7/34/0.451.22.115.51005150.525209
2PNCT 1×60 mm²19/20/0.451.52.319.01207900.329281
2PNCT 1×100 mm²19/34/0.452.02.6241501,3100.193393
2PNCT 1×150 mm²27/34/0.452.02.7271701,7600.136493
2PNCT 2×2 mm²37/0.260.81.810.57015510.227
2PNCT 2×3.5 mm²45/0.320.81.912.5802205.5439
2PNCT 3×2 mm²37/0.260.81.811.07018010.223
2PNCT 3×3.5 mm²45/0.320.81.913.0802605.5433
2PNCT 3×5.5 mm²70/0.321.02.015.51003803.5644
2PNCT 3×8 mm²50/0.451.02.117.01104802.5254
2PNCT 3×14 mm²88/0.451.02.3201207351.4376
2PNCT 3×22 mm²7/20/0.451.22.7261601,1800.919103
2PNCT 3×38 mm²7/34/0.451.23.0311901,8100.541142
2PNCT 3×60 mm²19/20/0.451.53.4382302,7500.339188
2PNCT 4×2 mm²37/0.260.81.912.58022010.221
2PNCT 4×3.5 mm²45/0.320.82.014.0903205.5430
2PNCT 4×5.5 mm²70/0.321.02.117.01104653.5640
2PNCT 4×14 mm²88/0.451.02.4221409101.4369
2PNCT 4×38 mm²7/34/0.451.23.2342102,2900.541128
2PNCT 4×50 mm²19/16/0.451.53.5392402,9400.423149
2PNCT 7×2 mm²37/0.260.82.115.510036010.216
2PNCT 12×2 mm²37/0.260.82.32012056010.213
2PNCT 30×3.5 mm²45/0.320.83.1342101,9305.5414

Source Notes

  • The dimensional, resistance and mass values in the tables above are JIS C 3327 nominal reference data for 600V 2PNCT and 600V CUR-2PNCT round flexible cabtyre cables; they are code-and-standard reference values for initial sizing, not a TEBAOFLEX performance statement. Confirm the exact outer diameter, stranding and tolerance on the TEBAOFLEX order drawing before ordering.
  • The 30°C ampacity column lists reference values for a single cable installed in free air at +30°C ambient temperature and +80°C maximum conductor temperature (JIS C 3327 / JCS 0168-1 basis). For the 7-core, 12-core and 30-core control rows, the listed current applies the JCS 0168-1 multi-core factor (0.51 for 7C, 0.42 for 12C and 0.29 for 30C) to the single-core rating (32 A at 2 mm²; 47 A at 3.5 mm²).
  • When cables operate at higher ambient temperatures or wound on a reel, apply the appropriate derating factor: under JCS 0168-1, ambient correction at 80°C conductor temperature is 0.89 at 40°C and 0.77 at 50°C, and multi-layer drum reeling requires layer reduction factors (0.85 for 1 layer, 0.65 for 2 layers, 0.45 for 3 layers, 0.35 for 4 layers).

Supply and ordering

  • Minimum order quantity: 50 m, for standard and custom constructions.
  • Cut lengths: supplied cut to the ordered length; state the required length per drum in the RFQ.
  • Typical lead time: 7–45 working days depending on size, construction and order details; the written quotation governs.
  • Outer sheath material and colour: black chloroprene rubber (CR) is standard for 2PNCT, CUR-2PNCT, 2PNCT-B, 2PNCT-SB and 2PNCT-F; polyurethane (-H-U) is built to order for high-abrasion crane service.
  • Packing and marking: drum size, cable marking and the document package are confirmed at quotation.
Standards

Standards

  • JIS C 3327 reference for the 2PNCT low-voltage cabtyre cable family.
  • Japanese Electrical Appliance and Material Safety Act references may apply by construction and size; confirm the requested scope for the quotation.
  • Request the order-specific marking, routine test and inspection documents with the RFQ.

A standard reference is not a blanket certificate for every core count or size. State the destination market and required documentation before order confirmation.

These reference standards are named for the constructions on this page; the last row gives the third-party certification status. They are not certifications TEBAOFLEX holds for this product, and nothing on this page should be read as a PSE mark, a JIS mark, a UL Listing, a CSA certification or a mine-safety agency approval.

600V 2PNCT reference standards and factory test scope
Reference or checkHow it applies to TEBAOFLEX 600V 2PNCT orders
JIS C 3327Design and dimensional reference for 600V Class 2 EP rubber insulated chloroprene cabtyre cable (2PNCT / CUR-2PNCT) from 0.75 mm² to 250 mm².
JCS 0168-1Calculation basis for the 30°C free-air reference ampacities and multi-core / ambient / reeling correction factors shown on this page.
Factory routine testing3,000 V AC voltage withstand test for 1 minute, conductor DC resistance at 20°C and insulation resistance check at 20°C on each production drum.
PSE / JIS / UL / CSA statusNot claimed for this construction. Request the factory inspection report and project-specific test scope in the RFQ.
Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    MOQ 50 m · Engineering reply within 24 hours

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    Email or WhatsApp is enough. Please include the key cable or application details for review.