MINING & TUNNELING CABLES TEBAOFLEX

AS/NZS 1972 Type 3 Mining Machine Cable, 1.1/1.1 kV

Type 3 1.1/1.1 kV machine cable connects control boxes, motors and resistor boxes on mining machinery. Four tinned-copper cores use R-S-150 insulation, an overall composite screen and a PVC covering. The complete cable operates up to 90°C; the 150°C allowance applies only to a short uncovered section beside a terminal. MOQ: 50 m; lead time: 7–45 working days.

Product information
SKU
TF-MIN-P1B3-M011
Brand
TEBAOFLEX
Product overview

Type 3 mining machine cable is a 1.1/1.1 kV screened cable for connections where heat concentrates at equipment terminals. It is used around control boxes, motors and resistor boxes on shuttle cars and other mobile haulage machinery. R-S-150 insulation addresses the hot connection area, while an overall tinned-copper and poly-yarn screen sits beneath the PVC outer covering.

The temperature boundary is central to selecting this cable. The complete covered cable has a maximum continuous operating temperature of 90°C. A short section immediately beside the connecting terminal may operate up to 150°C only where the outer covering has been removed. That local allowance does not make the whole cable a 150°C cable, and the termination arrangement still needs to suit the equipment enclosure and connection hardware.

The documented configuration is four 1.5 mm² cores, with flexible tinned conductors and red, black, blue and white core identification. Check the machine circuit, terminal temperature, cable entry and required screened connection before specifying a replacement. This machine-wiring construction has a different purpose from the reel-fed trailing cable supplying the vehicle. Its fixed-bend reference also does not establish a continuous reeling rating.

TEBAOFLEX supplies Type 3 cable from a 50 m minimum order with a lead time of 7–45 working days. Provide the existing marking, required length, terminal arrangement and equipment documentation when requesting a quotation.

Explore the mining and tunneling cable range for related configurations.

Construction

Construction

This Type 3 configuration keeps four equal-sized insulated cores in a round assembly, with one overall composite screen and a 5V90 PVC outer covering.

AS/NZS 1972 Type 3 Mining Machine Cable, 1.1/1.1 kV construction
ComponentMaterial and construction
ConductorsOxygen-free tinned annealed copper, flexible Class 5; reference stranding 30/0.25 mm.
Core insulationR-S-150 heat-resistant insulation.
Core identificationRed, black, blue and white.
AssemblyFour insulated cores, taped together beneath the overall braid.
Overall screenTinned annealed copper wire interwoven with high-tensile poly-yarn; minimum braid coverage 90%.
Outer covering5V90 PVC; the representative sample has a blue covering.
Applications

Applications

Type 3 serves internal or interconnecting machine wiring where local terminal heat and vibration influence cable selection.

  • Control-box connections on mobile underground haulage equipment.
  • Motor terminal connections where the short uncovered end section needs the documented higher temperature allowance.
  • Resistor-box connections on shuttle cars, with the covered route kept within the complete-cable temperature rating.
  • Confined equipment wiring routes requiring flexible tinned conductors and an overall screen.
  • Assess the gland, screen termination, enclosure and mechanical support as part of the machine connection. A cable designation alone does not establish an approved hazardous-area equipment assembly.
  • For a reel-fed or dragged vehicle supply, select a cable with a documented trailing or reeling duty instead of extrapolating the Type 3 fixed-bend value.

For route and construction selection, see mining and tunnelling cable selection.

For a PVC-insulated machine-wiring option, review Type 1 screened machine cable and match its temperature rating to the connection.

Where the equipment specifies EPR insulation and CPE covering, compare Type 2S and Type 2S.3 machine cables by voltage and construction rather than treating the Type numbers as interchangeable.

Specifications

Specifications

AS/NZS 1972 Type 3 Mining Machine Cable, 1.1/1.1 kV technical data
ParameterValue
Cable familyAS/NZS 1972 Type 3 machine cable
Rated voltage U₀/U1.1/1.1 kV
Core arrangement4×1.5 mm²
ConductorClass 5 tinned annealed copper
Insulation / coveringR-S-150 / 5V90 PVC
Complete-cable operating temperature−10°C to +90°C
Local terminal-section temperatureMaximum 150°C over a short section adjacent to the terminal only where the outer covering is removed
Maximum short-circuit temperature250°C for a maximum of 5 s
Minimum recommended bend radius — fixed6 × cable overall diameter
Maximum conductor DC resistance at 20°C13.7 Ω/km
Core-to-core capacitance at 1 kHz70 pF/m
Parallel-core inductance at 1 kHz0.64 μH/m
L/R ratio23.4 μH/Ω
Minimum order quantity50 m
Lead time7–45 working days
Type 3 machine cable — documented configuration and nominal reference data
Model and configurationStranding (number / wire diameter mm)Nominal OD (mm)Reference current (A)Approx. mass (kg/km)
Type 3 4×1.5 mm²30/0.2510.617118

The 17 A value follows the AS/NZS 3008.1.1:2009 Table 14, Column 12 basis stated with this configuration. It is a reference value, not an unconditional ampacity for every enclosure or route; confirm the applicable installation and thermal conditions.

The reference size table contains only 4×1.5 mm². Other requested constructions require their own dimensional and electrical specification.

Keep the 90°C complete-cable limit separate from the 150°C short uncovered terminal-section allowance. Confirm the exposed length and terminal arrangement against the equipment design.

The 10.6 mm diameter and 118 kg/km mass are nominal configuration references; confirm the ordered cable dimensions for gland and enclosure selection.

Standards

Standards

AS/NZS 1972 Type 3 Mining Machine Cable, 1.1/1.1 kV standards and test references
Standard or specificationApplication
AS/NZS 1972Construction reference for underground coal-mine cables other than reeling and trailing cables.
AS/NZS 1125; IEC 60228Conductor references.
AS/NZS 3808Insulating and sheathing material reference.
AS/NZS 60079.1 — Gas Group I; AS/NZS 60079.14Referenced in the Type 3 machine-connection specification for the equipment and installation context.
AS/NZS 1660.5.6; IEC 60332-1Single-cable flame-propagation test references.
AS/NZS 3008.1.1:2009, Table 14, Column 12Basis of the listed 17 A reference current.

Official standards and approval references

Select the applicable standard edition and equipment documentation with the purchase specification. The listed construction and test references describe different parts of cable selection.

Certifications and document support

Review our company certificates and document scopes when identifying the documentation required for the quoted construction.

Company certificates, construction standards and product-specific approvals serve different purposes. Include the destination mine, required approval documents and terminal arrangement in the enquiry so the document package matches the quoted Type 3 construction.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.