CHKCU Kiosk Substation Cable 6/10-12.7/22-20/35kV

CHKCU single-core kiosk substation cable to DS 076-2004, in 6/10 kV, 12.7/22 kV and 20/35 kV ratings for compact kiosk substations.

  • Conductor: stranded tinned copper, class 5.
  • Screening: semiconducting layers either side of the rubber insulation.
  • Concentric conductor: integrated earth and screen return.
  • Sheath: black chloroprene.
  • Bending radius: 5 × D, or 10 × D below −20 °C.

Send system voltage, cross-section, kiosk type and termination details for RFQ review.

Product information
Brand
TEBAOFLEX
Product overview

CHKCU Compact Kiosk Substation Cable

The CHKCU family is a single-core screened rubber cable to DS 076-2004, built for the short, tightly routed connections inside compact kiosk substations. Three rated voltages share the construction: 10-CHKCU at 6/10 kV, 22-CHKCU at 12.7/22 kV and 35-CHKCU at 20/35 kV, tested at 17 kV, 29 kV and 50 kV respectively.

The reason these are specified by name rather than as a generic switchgear cable is the combination of 12.7/22 kV system matching with the bending space inside a kiosk enclosure. The permissible bending radius is five times the cable diameter, and ten times below −20 °C, which is what governs whether a run will physically land on its terminal inside the housing.

  • Rated voltages: 6/10 kV, 12.7/22 kV and 20/35 kV.
  • Construction: single-core, screened, with concentric conductor and chloroprene sheath.
  • Bending radius: minimum 5 × D; 10 × D below −20 °C.
  • Temperature: −35 °C laying, handling and storage; +90 °C conductor.

The cables suit fixed and flexible installation in networks at these voltages, and are particularly suited to compact kiosk substations. For the German-standard single-core range from 3.6/6 kV to 18/30 kV see NTMCGCWÖU single-core cable, and for 26/45 kV switchgear connection see NTMCWOEU switchgear cable.

Construction

CHKCU Cable Construction

Seven-layer single-core screened construction, common to all three voltage ratings. The insulation wall changes with the rating; the layer sequence does not.

CHKCU cross-section showing the tinned copper conductor, semiconducting layers, concentric conductor and chloroprene sheath
Flat cross-section of the CHKCU single-core kiosk substation cable.
CHKCU cable construction
No.LayerConstruction
1ConductorStranded tinned copper, class 5
2Conductor screenSemiconducting layer
3InsulationRubber insulation, natural colour
4Insulation screenSemiconducting layer
5Concentric conductorConcentric conductor over the insulation screen
6TapeTape of suitable material
7SheathChloroprene sheath, black

Family members

CHKCU voltage variants
DesignationRated voltage U₀/UTest voltageAvailability
10-CHKCU6/10 kV17 kVAvailable to order; minimum order quantity applies.
22-CHKCU12.7/22 kV29 kVAvailable to order from the standard size table below.
35-CHKCU20/35 kV50 kVAvailable to order; minimum order quantity applies.
Applications

CHKCU Applications

CHKCU cables are for fixed and flexible installation in networks rated 10, 22 and 35 kV, and are especially suited to compact kiosk substations where a medium-voltage single core has to be routed and terminated in a confined enclosure.

Compact kiosk substation interior with single-core medium-voltage cables routed to a ring main unit
CHKCU single cores routed and terminated inside a compact kiosk substation.
  • Compact kiosk and packaged substations at 10, 22 and 35 kV.
  • Connections between ring main units, transformers and switchgear inside the housing.
  • Runs where the 5 × D bending radius determines the routing inside the enclosure.
  • Installations in cold conditions where the 10 × D limit below −20 °C applies.

Application boundaries

The bending radius is a minimum: 5 × D is the smallest radius the cable may be bent to, and 10 × D applies below −20 °C. Inside a kiosk enclosure that limit, rather than the current rating, usually decides the routing.

Related single-core medium-voltage references

Compare NTMCGCWÖU for the 3.6/6 kV to 18/30 kV German-standard single-core range and NTMCWOEU switchgear cable for 26/45 kV equipment connection.

Reference note: enquiries arriving marked 10-CHKCu, 22CHKCu or 35-CHKCu are handled on this page; spacing and capitalisation variants refer to the same family.

Specifications

CHKCU Specifications

CHKCU operating data
Rated voltage U₀/U6/10 kV (10-CHKCU), 12.7/22 kV (22-CHKCU), 20/35 kV (35-CHKCU)
Test voltage17 kV / 29 kV / 50 kV respectively
Manufacturing standardDS 076-2004
Maximum short-circuit temperature+250 °C
Conductor operating temperature+90 °C
Minimum bending radius5 × D; 10 × D below -20 °C
Minimum laying temperature-35 °C
Minimum handling temperature-35 °C
Minimum storage temperature-35 °C
Insulation colourNatural
Sheath colourBlack
Standard packingWooden or metal drums

22-CHKCU 12.7/22 kV size and electrical table

Code and cross-sectionOuter diameterWeightBending radiusConductor resistanceShort-circuit current 1 sCurrent capacity in airCopper content
22-CHKCU 1 × 35/16 mm²31 mm1450 kg/km155 mm0.565 Ω/km5.037 kA218 A560 kg/km
22-CHKCU 1 × 70/16 mm²35 mm2025 kg/km175 mm0.277 Ω/km10.070 kA336 A943 kg/km

The notation 1 × 35/16 means a 35 mm² conductor with a 16 mm² concentric conductor. The tabulated bending radius is the 5 × D value for each diameter. The 10-CHKCU 6/10 kV and 35-CHKCU 20/35 kV builds are available to order with a minimum order quantity. Their insulation wall differs from the 12.7/22 kV table above, so their dimensions are quoted per build.

Standards

CHKCU Standards, Approvals and Order Documentation

Standards applied
ReferenceScopeOrder confirmation
DS 076-2004Manufacturing specification for the CHKCU familyState the designation, voltage and cross-section in full.

Approvals

Certification held for this construction
ApprovalStatus
Manufacturing conformity, DS 076-2004Held
Medium-voltage routine electrical test packageHeld
Partial discharge testHeld

Order package

State the system voltage and which family member is required, conductor and concentric conductor cross-sections, the kiosk or switchgear type and its entry arrangement, termination type, required lengths, and the partial discharge and documentation scope. Minimum order quantities apply to the 10-CHKCU and 35-CHKCU builds.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.