YHKGYFoyn 3.6/6 kV Individually Screened Steel-Wire-Armoured Underground Mine Power Cable
YHKGYFoyn is a 3.6/6 kV PVC-insulated, PVC-sheathed mine power cable for fixed installation, in which the H marks an individual screen of conductive tape and copper tape on each of the three compacted Class 2 copper cores, with a single layer of galvanized steel wire armour and a red flame-retardant PVC sheath tested to IEC 60332-3-24, from 3×25 to 3×240 mm².
Fixed 6 kV distribution in underground mines, from shaft-bottom substations to section transformers and pump chambers, needs armoured cable that stays in place for years and resists crushing and fire. YHKGYFoyn is a 3.6/6 kV PVC-insulated mine power cable for this duty. Its three circular compacted Class 2 copper conductors to BS EN 60228 are insulated with PVC compound type DIV14, and the H in the designation marks an individual screen of conductive non-metallic tape and copper tape over each core.
The screened cores are laid up with a central copper wire or filler, filled with rubber compound and covered with a PVC inner sheath type DMV6. A single layer of galvanized steel wires with a steel tape gives mechanical protection, and a red flame-retardant PVC sheath type DMV31 meets the bunched-cable flame test of IEC 60332-3-24. The reference schedule lists 18 designations from 3x25RMC/16 to 3x240RMC/30 mm² with outer diameters of 46.5 mm to 80.6 mm, net weights of 4632 to 16867 kg/km and maximum conductor resistances of 0.727 to 0.0754 Ω/km at 20 °C.
Individual core screens give each phase its own earthed screen, which confines the electric field at 6 kV and lets earth-fault protection act on a single core. Collective-screen YKGYFoyn and the other Polish and Czech fixed constructions are covered on our fixed mining power cable page.
Explore the mining and tunneling cable range for related configurations.
YHKGYFoyn 3.6/6 kV Cable Construction & Layer Structure
The representative horizontal sample shows YHKGYFoyn 3.6/6 kV 3x95RMC/16: three compacted copper conductors with natural PVC insulation and individual conductive tape and copper tape screens, rubber filling, a PVC inner sheath, galvanized steel wire armour with steel tape and a red flame-retardant PVC outer sheath.

| Component | Material and construction |
|---|---|
| Copper Conductors | Annealed copper, circular compacted stranded Class 2 to BS EN 60228, 25 mm² to 240 mm². |
| PVC Insulation | PVC compound type DIV14 to PN-HD 620 S1:2002, natural colour. |
| Individual Core Screen | Conductive non-metallic tape and copper tape over each insulated core. |
| Lay-Up and Inner Sheath | Three cores with a central copper wire or filler, rubber compound filling and a PVC inner sheath type DMV6. |
| Steel Wire Armour | Single layer of galvanized steel wires applied spirally over the inner sheath, with steel tape. |
| Flame-Retardant PVC Sheath | Red PVC compound type DMV31 to HD 620 S1:2002, flame retardant to IEC 60332-3-24. |
YHKGYFoyn Type Designation Breakdown
- Y (first): PVC insulation
- H: individual screen on each core (conductive tape and copper tape)
- K: power cable
- G: mining (górniczy) duty
- Fo: armour of round galvanized steel wires
- yn: flame-retardant PVC outer sheath
YHKGYFoyn 3.6/6 kV Underground Mine Applications & Duty Scope
Specify YHKGYFoyn for fixed 3.6/6 kV mine distribution where individually screened cores and steel wire armour are required.

- Shaft-bottom and section substations fed at 3.6/6 kV on fixed underground routes.
- Main pump chambers, conveyor drive houses and ventilation stations requiring armoured 6 kV supply.
- Roadway and drift distribution on brackets or trays where bunched cables must meet IEC 60332-3-24.
- Polish and Central European mine projects that specify YHKGYFoyn by designation.
YHKGYFoyn vs YKGYFoyn, MYJV and VBbShvng(A)-LS Selection Boundary
| Model | Insulation | Screen | Armour | Best fit |
|---|---|---|---|---|
| YHKGYFoyn (this page) | PVC, 70 °C | Individual copper tape on each core | Galvanized steel wire | Fixed 3.6/6 kV Polish-designation mine feeders |
| YKGYFoyn (Fixed Mining Power Cable page) | PVC | Collective screen | Steel wire | Fixed feeders where a collective screen is specified |
| MYJV family | XLPE, 90 °C | Copper tape (medium voltage) | None, steel tape or steel wire | Chinese MT/KA-system fixed distribution |
| VBbShvng(A)-LS | PVC, 70 °C | None | Steel tape | GOST 31996 low-voltage fixed routes |
Individual-screen and collective-screen versions differ in termination and earthing practice and are not interchangeable without checking the switchgear and gland arrangement.
Related selection resources
- Mining and tunneling cable engineering solutions
- Armoured and static mining cable engineering guide for fixed distribution routes
- Fixed Mining Power Cable — PVC / HEPR, SWA / STA Options
- MYJV, MYJV22, MYJV32, MYJV42 and MYJV-GXT XLPE Mine Power Cable
- VBbShvng(A)-LS GOST 31996 Steel-Tape Armoured Underground Mine Power Cable
YHKGYFoyn 3.6/6 kV Frequently Asked Questions
What does the H in YHKGYFoyn mean?
It marks an individual screen: each core has its own conductive non-metallic tape and copper tape, instead of one collective screen over all three cores.
What does 3x95RMC/16 mean?
Three round multi-wire compacted 95 mm² copper conductors; the figure after the slash is part of the reference designation, and the screen or earth arrangement it refers to is confirmed on the quotation drawing.
Can YHKGYFoyn hang in a vertical shaft?
It is designed for fixed installation. Vertical shaft suspension depends on armour sizing and the support method, which are confirmed on the order drawing; the maximum pulling stress with a cable grip is 50 N/mm² of copper.
What are the MOQ and lead time?
The minimum order quantity is 50 m and the manufacturing lead time is 7 to 45 working days, depending on size and quantity.
YHKGYFoyn Dimensions, Weight, Resistance & Technical Specifications
YHKGYFoyn Key Specifications
- Voltage: 3.6/6 kV
- Screen: Conductive tape and copper tape on each core
- Armour: Single layer galvanized steel wire with steel tape
- Sizes: 3x25 to 3x240 mm², 18 reference designations
- Supply: MOQ 50 m; 7 to 45 working days
| Parameter | Value |
|---|---|
| Construction references | BS EN 60228 conductors; PN-HD 620 S1:2002 compounds; flame test IEC 60332-3-24 |
| Rated voltage | 3.6/6 kV; test voltage 11 kV AC for 5 min |
| Screening | Individual conductive tape and copper tape screen on each core |
| Conductor temperature | 70 °C maximum; 150 °C short-circuit |
| Minimum bending radius | 12 x overall diameter |
| Commercial supply terms | Minimum order quantity 50 m; manufacturing lead time 7 to 45 working days; final values confirmed on the quotation drawing |
| Selection boundary vs YKGYFoyn and MYJV family | Choose YHKGYFoyn for individually screened PVC 3.6/6 kV armoured cable; choose collective-screen YKGYFoyn on the fixed mining power cable page, the MYJV family for Chinese XLPE designations and VBbShvng(A)-LS for GOST 31996. |
YHKGYFoyn 3.6/6 kV Reference Schedule
| Designation (n x mm²) | Conductor | Approx. Overall Diameter (mm) | Approx. Net Weight (kg/km) | Max. Conductor Resistance at 20 °C (Ω/km) | Next step |
|---|---|---|---|---|---|
| YHKGYFoyn 3x25RMC/16 | 3 x 25 mm² | 46.5 | 4632 | 0.727 | Request this size |
| YHKGYFoyn 3x25RMC/25 | 3 x 25 mm² | 46.5 | 4633 | 0.727 | Request this size |
| YHKGYFoyn 3x35RMC/16 | 3 x 35 mm² | 49.8 | 5633 | 0.524 | Request this size |
| YHKGYFoyn 3x35RMC/25 | 3 x 35 mm² | 49.8 | 5634 | 0.524 | Request this size |
| YHKGYFoyn 3x50RMC/16 | 3 x 50 mm² | 53.8 | 6539 | 0.387 | Request this size |
| YHKGYFoyn 3x50RMC/25 | 3 x 50 mm² | 53.8 | 6540 | 0.387 | Request this size |
| YHKGYFoyn 3x70RMC/16 | 3 x 70 mm² | 56.7 | 7518 | 0.268 | Request this size |
| YHKGYFoyn 3x70RMC/25 | 3 x 70 mm² | 56.7 | 7519 | 0.268 | Request this size |
| YHKGYFoyn 3x95RMC/16 | 3 x 95 mm² | 61.3 | 8981 | 0.193 | Request this size |
| YHKGYFoyn 3x95RMC/30 | 3 x 95 mm² | 61.3 | 8982 | 0.193 | Request this size |
| YHKGYFoyn 3x120RMC/16 | 3 x 120 mm² | 65.5 | 10305 | 0.153 | Request this size |
| YHKGYFoyn 3x120RMC/30 | 3 x 120 mm² | 65.5 | 10307 | 0.153 | Request this size |
| YHKGYFoyn 3x150RMC/25 | 3 x 150 mm² | 69.0 | 11629 | 0.124 | Request this size |
| YHKGYFoyn 3x150RMC/30 | 3 x 150 mm² | 69.0 | 11631 | 0.124 | Request this size |
| YHKGYFoyn 3x185RMC/25 | 3 x 185 mm² | 73.6 | 14014 | 0.0991 | Request this size |
| YHKGYFoyn 3x185RMC/30 | 3 x 185 mm² | 73.6 | 14017 | 0.0991 | Request this size |
| YHKGYFoyn 3x240RMC/25 | 3 x 240 mm² | 80.6 | 16863 | 0.0754 | Request this size |
| YHKGYFoyn 3x240RMC/30 | 3 x 240 mm² | 80.6 | 16867 | 0.0754 | Request this size |
YHKGYFoyn Construction and Rating Parameters
| Parameter | Value |
|---|---|
| Rated voltage U0/U | 3.6/6 kV |
| Conductors | Annealed copper, circular compacted stranded Class 2 to BS EN 60228 |
| Insulation | PVC compound type DIV14 to PN-HD 620 S1:2002, natural colour |
| Individual screen | Conductive non-metallic tape and copper tape over each core |
| Core and filling | Three cores laid up with a central copper wire or central filler; rubber compound filling |
| Inner sheath | PVC compound type DMV6 to PN-HD 620 S1:2002 |
| Armour | Single layer of galvanized steel wires applied spirally over the inner sheath, with steel tape |
| Outer sheath | Flame-retardant PVC compound type DMV31 to HD 620 S1:2002, red |
| Temperatures | Maximum conductor 70 °C; short-circuit 150 °C; lowest ambient for fixed installation -30 °C; lowest installation temperature -5 °C |
| Minimum bending radius | 12 x overall diameter |
| Test voltage | 11 kV AC, 5 min, 50 Hz |
| Flame test | IEC 60332-3-24 |
| Max. tensile stress with cable grip | 50 N/mm² of copper conductor |
RMC denotes a round multi-wire compacted conductor; the figure after the slash (16, 25 or 30) is part of the reference designation, and the resulting screen or earth arrangement is confirmed on the quotation drawing.
Polish designations and the ZN / WT works standards are cited as construction references; TEBAOFLEX builds to the referenced construction and does not claim a Polish mining admission or third-party approval for it, so state the approval documents your mine requires when requesting a quotation.
ASCII part references for BOM and ERP entry: YHKGYFoyn 3x25RMC/16, YHKGYFoyn 3x25RMC/25, YHKGYFoyn 3x35RMC/16, YHKGYFoyn 3x35RMC/25, YHKGYFoyn 3x50RMC/16, YHKGYFoyn 3x50RMC/25, YHKGYFoyn 3x70RMC/16, YHKGYFoyn 3x70RMC/25, YHKGYFoyn 3x95RMC/16, YHKGYFoyn 3x95RMC/30, YHKGYFoyn 3x120RMC/16, YHKGYFoyn 3x120RMC/30, YHKGYFoyn 3x150RMC/25, YHKGYFoyn 3x150RMC/30, YHKGYFoyn 3x185RMC/25, YHKGYFoyn 3x185RMC/30, YHKGYFoyn 3x240RMC/25, YHKGYFoyn 3x240RMC/30.
YHKGYFoyn Standards & Test References (PN-HD 620 S1, IEC 60332-3-24)
| Standard or specification | Application |
|---|---|
| BS EN 60228 / IEC 60228 | Conductors of insulated cables: Class 2 compacted copper conductors and maximum DC resistance. |
| PN-HD 620 S1:2002 | Distribution cables with extruded insulation: PVC compound types DIV14, DMV6 and DMV31. |
| IEC 60332-3-24 | Flame spread test of vertically mounted bunched cables, category C. |
| IEC 60502-2 | Power cables with extruded insulation for rated voltages from 6 kV, the general reference for 3.6/6 kV screened cable. |
Certifications and document support
TEBAOFLEX company certificates and quality system documentation
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
Fixed Mining Power Cable — PVC / HEPR, SWA / STA Options
A related cable option for a different application or duty profile.
View productMYJV, MYJV22, MYJV32, MYJV42 & MYJV-GXT (0.6/1–8.7/10 kV) XLPE Armoured & Fibre-Composite Mine Power Cable
A related cable option for a different application or duty profile.
View productVBbShvng(A)-LS GOST 31996 Steel-Tape Armoured Underground Mine Power Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.