Single-Conductor Type W 2000 V Mining Power Cable

Single-conductor Type W 2000 V cable with stranded bare copper, EPDM insulation and polyester reinforcement for portable power. Reference sizes: 8 AWG–500 kcmil. MOQ: 50 m; lead time: 7–45 working days.

Product information
SKU
TEB-MIN-P1-M001
Brand
TEBAOFLEX
Product overview

TEBAOFLEX single-conductor Type W 2000 V cable provides an individual power lead for portable electrical systems around mines, processing plants and temporary work areas. Its single-core format lets the circuit designer select each power conductor separately and match the lead to the connection arrangement. This page covers the 2 kV Type W construction in sizes from 8 AWG to 500 kcmil, with dimensions for comparing cable entries, connectors and handling space.

A stranded bare copper conductor carries the current beneath EPDM insulation. An open polyester braid sits between the insulation and the black outer jacket, adding mechanical reinforcement without a metallic screen or armour. The construction supports portable power use, while the required conductor size still depends on load, circuit length, installation conditions and the temperature rating of the connected equipment. The listed conductor limits are 90°C in dry service and 75°C in wet service.

Specify the protective earth arrangement separately: this cable contains one insulated power conductor and no integrated ground-check core. Compare multiconductor Type W configurations when several power cores must share a jacket, or Type G-GC cable with grounding and ground-check conductors for circuits requiring that integrated arrangement. For cable reels or routes with repeated movement, include the reel geometry and duty cycle with the enquiry so the application can be assessed. TEBAOFLEX supplies quoted lengths from a 50 m minimum order, with a lead time of 7–45 working days. Send the conductor size, required length and termination details to receive a construction-specific quotation.

Explore the mining and tunneling cable range for related configurations.

Construction

Construction

A reinforced single-core construction combines stranded copper, EPDM insulation and a black outer jacket. The polyester braid is a non-metallic reinforcing layer. The main image is a representative construction illustration.

Single-Conductor Type W 2000 V Mining Power Cable construction
ComponentMaterial and construction
ConductorOne fully annealed, stranded bare copper conductor; 8 AWG–500 kcmil reference sizes.
InsulationEPDM insulation; nominal thickness varies with conductor size as listed below.
ReinforcementOpen polyester braid between the insulation and outer jacket.
Outer jacketBlack heavy-duty jacket.
Circuit arrangementSingle insulated power conductor; protective earth and ground-check circuits are specified separately.
Applications

Applications

For portable power connections where a separate single-core lead is appropriate to the equipment and circuit design.

  • Portable power distribution for mine maintenance and temporary work areas.
  • Individual power leads between portable equipment and its supply connection.
  • Temporary power connections in mineral processing and industrial plant areas.
  • Outdoor portable power routes with terminations selected for the exposure conditions.

For route and construction selection, see the Type W, G-GC and SHD-GC selection guide.

Specifications

Specifications

Single-Conductor Type W 2000 V Mining Power Cable technical data
ParameterValue
Cable designationType W, single conductor
Rated voltage2000 V
Conductor sizes8 AWG–500 kcmil; listed sizes only
Maximum conductor temperature90°C dry; 75°C wet
Core insulationEPDM
Mechanical reinforcementOpen polyester braid
Outer jacket colourBlack
Metallic armour or screenNone
Minimum order quantity50 m
Lead time7–45 working days
Type W 2000 V single-conductor reference dimensions
Cable configurationCopper strandsNominal insulation (mm)Nominal cable OD (mm)Approx. net weight (lb/1000 ft)
Type W 1 × 8 AWG1331.7812.32150
Type W 1 × 6 AWG2591.7814.35214
Type W 1 × 4 AWG2591.7815.37277
Type W 1 × 2 AWG2591.7817.27387
Type W 1 × 1 AWG2592.2919.43485
Type W 1 × 1/0 AWG2592.2920.57563
Type W 1 × 2/0 AWG2592.2922.48679
Type W 1 × 3/0 AWG2592.2923.62809
Type W 1 × 4/0 AWG2592.2924.89973
Type W 1 × 250 kcmil6272.6726.541155
Type W 1 × 350 kcmil8552.6729.081492
Type W 1 × 500 kcmil12352.6733.272048

Dimensions and weights are reference values for the listed construction. The quotation and agreed production drawing define the supplied cable.

Choose connector and gland dimensions from the finished cable diameter and the conductor size; these are separate measurements.

Determine permissible current from the complete circuit, installation arrangement, ambient conditions and terminal temperature limits.

Single-core cables require a separately designed protective earth arrangement. Include any ground-monitoring requirement in the enquiry.

For repeated movement or reel use, provide the bend radius, reel dimensions, travel and operating duty before selecting the cable.

Specify order length, conductor size, termination arrangement and delivery destination when requesting a quotation.

Standards

Standards

Single-Conductor Type W 2000 V Mining Power Cable standards and test references
Standard or specificationApplication
ICEA S-75-381 / NEMA WC 58Design reference for portable and power-feeder cables used in mines and similar applications.

Official standards and approval references

The current NEMA/ICEA publication is ANSI/NEMA WC 23058/ICEA S-75-381-2025; NEMA WC 58 is the historical designation used in the construction reference above.

Certifications and document support

Review our company certificates and document scopes when identifying the documentation required for the quoted construction.

For an order specifying MSHA identification, provide the required cable type, rated voltage and conductor size so the approval record and marking scope can be checked for that construction. Standards and regulatory references explain the procurement requirements; the applicable certificate or acceptance record identifies the approved product scope.

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    * Required fields. Please include the key cable or application details for review.