CSA Type SHD-BGC, SHD-R and SHD-SP Shielded Mining Cable
Canadian shielded portable mining power cable engineered to CSA C22.2 No. 96 from 2 kV to 35 kV in Type SHD-BGC (braided ground-check over pilot), Type SHD-R (anti-torsion reeling construction) and Type SHD-SP / SHD-GC-SP (semi-conductive polymeric phase screen). Built for open-pit electric rope shovels, draglines, mobile stackers and cold-climate potash or hard-rock mines down to -40 C.
Canadian open-pit oil-sands shovels, walking draglines, mobile crushers and underground hard-rock or potash mines specify CSA C22.2 No. 96 shielded portable power cables tailored to distinct ground-check and mechanical reeling duties. Whereas standard US ICEA Type SHD-GC uses an unshielded insulated ground-check core, the Canadian CSA C22.2 No. 96 family defines Type SHD-BGC, Type SHD-R and Type SHD-SP / Type SHD-GC-SP across 2 kV, 5 kV, 8 kV, 15 kV, 25 kV and 35 kV voltage ratings.
Type SHD-BGC incorporates a braided tinned-copper ground-check conductor (BGC) concentrically applied over an insulated pilot core so rock-crush impact immediately triggers the ground-fault monitor before phase-to-ground contact occurs. Type SHD-R adds an open-weave high-tenacity synthetic anti-torsion braid locked between dual thermoset CPE jackets for high-tension monospiral and level-wind cable reels on stacker-reclaimers and electric shovels.
Type SHD-SP and Type SHD-GC-SP replace metallic phase braid shields with a heavy-duty semi-conductive polymeric phase screen over the 90 C EPR insulation, eliminating broken metallic shield strands that can puncture insulation during severe flexing and simplifying field splicing. All variants are engineered for -40 C cold-bend/cold-impact performance and FT1/FT4 flame retardance.
Explore the mining and tunneling cable range for related configurations.
CSA Type SHD-BGC, SHD-R and SHD-SP Shielded Mining Cable Construction & Layer Breakdown
The representative horizontal sample illustrates the CSA C22.2 No. 96 Type SHD-BGC 5 kV construction, showing three flexible rope-lay tinned copper power cores with triple-extruded EPR dielectric and tinned-copper/textile composite phase shields, two uninsulated interstitial grounding conductors, one yellow EPR pilot core with a concentric braided tinned-copper ground-check shield (BGC) and a reinforced two-layer -40 C thermoset CPE jacket.

| Component | Material and construction |
|---|---|
| Power Conductors (3 x Rope-Lay Tinned Copper) | Annealed tinned copper rope-lay stranded conductors (6 AWG to 500 kcmil) engineered to CSA C22.2 No. 96 and ASTM B33 for high flex life. |
| Conductor Screen & 90 C EPR Insulation | Extruded semi-conducting thermoset conductor screen and ozone-/discharge-resistant 90 C EPR insulation sized to 2 kV, 5 kV, 8 kV, 15 kV, 25 kV or 35 kV wall schedules. |
| Phase Shielding (Metallic Braid or SP Polymeric) | Tinned-copper and nylon composite braid over semi-conducting insulation screen on SHD-BGC and SHD-R; heavy semi-conductive elastomeric screen on SHD-SP / SHD-GC-SP. |
| Symmetrical Grounding Conductors | Two flexible stranded tinned copper grounding conductors laid in two outer interstices in intimate contact with the phase screens. |
| Braided Ground-Check / Pilot Assembly (BGC / GC) | SHD-BGC uses a concentric tinned-copper braid shield over an insulated pilot core; SHD-R and SHD-GC-SP use a high-strength yellow EPR-insulated ground-check core. |
| Inner Bedding & Anti-Torsion Braid | Extruded black thermoset elastomeric inner jacket with open-weave synthetic reinforcing braid (heavy anti-torsion weave on Type SHD-R). |
| Arctic -40 C FT1/FT4 Outer Jacket | Extra-heavy-duty thermoset chlorinated polyethylene (CPE) or polychloroprene (PCP) outer jacket rated for -40 C cold impact, oil, UV and FT1/FT4 flame tests. |
CSA Type SHD-BGC, SHD-R and SHD-SP Designation Breakdown (CSA C22.2 No. 96)
- CSA C22.2 No. 96: Canadian Standards Association standard for portable power cables including arctic -40 °C cold-impact and FT1/FT4 flame compliance
- SHD: Shielded heavy-duty portable trailing cable with individual metallic phase shields over 90 °C EPR power conductors
- BGC (SHD-BGC): Braided Ground-Check — concentric tinned-copper braid shield applied directly over the insulated yellow ground-check pilot conductor (2 kV to 15 kV)
- R (SHD-R): Reeling service — anti-torsion synthetic reinforcing braid between dual CPE jackets plus flexible metallic braid phase shields for monospiral/cylindrical drums (5 kV to 35 kV)
- SP / GC-SP (SHD-SP): Semi-Conductive Polymeric phase screen — non-metallic flexible stress-control screen eliminating metallic braid strand fatigue on tight-bend equipment (5 kV to 15 kV)
CSA Type SHD-BGC, SHD-R and SHD-SP Trailing & Reeling Mining Applications
Select CSA Type SHD-BGC, Type SHD-R or Type SHD-SP / SHD-GC-SP according to provincial Canadian mine code requirements, reeling drum tension and field-splicing practices.

- Electric rope shovels, hydraulic face shovels and walking draglines in Canadian oil sands, open-pit coal, iron-ore and copper mines operating from 5 kV to 35 kV (Type SHD-BGC).
- Motorized cable-reel shovels, mobile hopper cars, bucket-wheel reclaimers and shiploaders requiring torsion-free drum reeling under CSA C22.2 No. 96 (Type SHD-R).
- High-flexibility trailing feeders and mobile substations where semi-conductive polymeric phase screens eliminate metallic braid fatigue and speed up field vulcanized splices (Type SHD-SP / SHD-GC-SP).
- Sub-zero Arctic and boreal open-pit or underground mining distributions requiring -40 C cold-bend and FT1/FT4 flame compliance.
CSA Type SHD-BGC, SHD-R and SHD-SP vs SHD-GC & SHD-CGC Selection Matrix
| Cable Type | Standard & Voltage Class | Pilot / Phase Screen Architecture | Primary Mining Duty |
|---|---|---|---|
| CSA Type SHD-BGC | CSA C22.2 No. 96 (2 kV to 15 kV) | Tinned copper braid phase shields + concentric braided copper screen over yellow GC pilot | Canadian electric shovels, draglines and mobile substations requiring braided pilot fault detection and -40 °C cold impact |
| CSA Type SHD-R | CSA C22.2 No. 96 (5 kV to 35 kV) | Flexible metallic braid phase shields + anti-torsion synthetic braid between dual CPE jackets | Vertical/horizontal reeling drums on continuous miners, electric LHDs and mobile stacker-reclaimers |
| CSA Type SHD-SP / SHD-GC-SP | CSA C22.2 No. 96 (5 kV to 15 kV) | Flexible semi-conductive polymeric phase screen (no metallic phase braid strand breakage) | Tight-bend underground potash miners, shuttle cars and high-flex trailing loops |
| ICEA Type SHD-GC | ICEA S-75-381 / NEMA WC 58 (2 kV to 25 kV) | Copper tape + braid phase shield with unshielded insulated PP/EPR ground-check pilot | General North American open-pit and underground MV trailing feeders without CSA braided-pilot mandate |
Specify CSA Type SHD-BGC when Canadian provincial mine codes require a concentrically screened ground-check pilot, SHD-R for tensioned cable reels, or SHD-SP where tight flexing causes metallic braid fatigue.
Related selection resources
- Mining and tunneling cable engineering solutions
- What does Type SHD mean in mining cables? Construction and shield guide
- CSA Type G-BGC and SHC-GC 2000V Portable Mining Cable
- 5kV to 15kV Mining VFD, VFD-GC and VFD-BGC Drive Cable
- Type MPF and MPF-GC 5kV to 35kV Armoured Mine Shaft Feeder Cable
CSA Type SHD-BGC, SHD-R and SHD-SP Shielded Mining Cable Engineering FAQ
What is the difference between CSA Type SHD-BGC, SHD-R and SHD-SP?
All three are manufactured to CSA C22.2 No. 96 with 90 °C EPR insulation and -40 °C cold-impact CPE jackets. Type SHD-BGC (2 kV to 15 kV) features a concentric tinned-copper braid shield over the yellow ground-check pilot conductor for fail-safe pilot fault detection. Type SHD-R (5 kV to 35 kV) adds an anti-torsion synthetic reinforcing braid between dual CPE jackets for motorized reeling drums. Type SHD-SP / SHD-GC-SP (5 kV to 15 kV) replaces the metallic phase braid with a flexible semi-conductive polymeric phase screen to eliminate wire-strand fatigue in tight-radius underground flexing.
Why do Canadian mines specify a braided ground-check (BGC) pilot conductor?
In CSA Type SHD-BGC cables, the concentric copper braid over the insulated 8 AWG or 6 AWG pilot core is tied to ground. If rock crushing or mechanical pinch penetrates the pilot insulation before reaching a phase shield, the pilot conductor immediately contacts its concentric ground braid and trips the ground-check monitor relay at the feeder breaker.
Are CSA Type SHD-BGC and SHD-R cables tested for -40 °C arctic operation?
Yes. Every CSA C22.2 No. 96 Type SHD-BGC, SHD-R and SHD-SP cable is compounded and tested for -40 °C cold-bend and -40 °C cold-impact endurance alongside FT1 / FT4 and MSHA flame-retardant performance for year-round Canadian open-pit and underground operations.
What are the minimum order quantity (MOQ) and manufacturing lead time for CSA Type SHD-BGC, SHD-R and SHD-SP?
TEBAOFLEX supplies CSA C22.2 No. 96 Type SHD-BGC, SHD-R and SHD-SP cables from a 50 m minimum order quantity (MOQ) with a manufacturing lead time of 7 to 45 working days, complete with factory AC hi-pot and partial-discharge test reports.
CSA Type SHD-BGC, SHD-R and SHD-SP Technical Specifications & Size Schedule (2 kV to 35 kV)
CSA Type SHD-BGC, SHD-R and SHD-SP Key Electrical, Cold-Impact & Mechanical Ratings
- Standard & Models: CSA C22.2 No. 96 Type SHD-BGC (2–15 kV), Type SHD-R reeling (5–35 kV) and Type SHD-SP / SHD-GC-SP (5–15 kV)
- Phase & Pilot Screening: 90 °C EPR insulation with tinned copper braid (SHD-BGC/SHD-R), semi-conductive screen (SHD-SP) or braided pilot (BGC)
- Conductor Range: 3 Class I/K flexible tinned copper phase cores (6 AWG to 500 kcmil; 4 AWG to 2/0 AWG tabulated) + 2 grounds + 1 pilot
- Arctic & Flame Rating: -40 °C cold-impact / cold-bend tested per CSA C22.2 No. 96 with FT1 / FT4 and MSHA flame-retardant dual CPE jacket
- Commercial Terms: MOQ 50 m; manufacturing lead time 7 to 45 working days with factory partial-discharge and AC hi-pot test reports
| Parameter | Value |
|---|---|
| Design standard reference | Engineered to CSA C22.2 No. 96, ICEA S-75-381 / NEMA WC 58 and CSA FT1 / FT4 flame test schedules |
| Rated voltage classes | 2000 V (2 kV), 5000 V (5 kV), 8000 V (8 kV), 15000 V (15 kV), 25000 V (25 kV) and 35000 V (35 kV) |
| SHD-BGC vs SHD-R vs SHD-SP | SHD-BGC: braided ground-check over pilot; SHD-R: anti-torsion reeling jacket; SHD-SP: semi-conductive polymeric phase screen |
| Operating temperature range | -40 C cold-bend/impact to +90 C continuous conductor temperature (250 C short-circuit rating) |
| Minimum dynamic bend radius | 6 x O.D. for 2 kV to 5 kV trailing; 8 x O.D. for 8 kV to 35 kV trailing; 10 x O.D. for dynamic drum reeling (SHD-R) |
| Commercial supply terms | Minimum order quantity 50 m; manufacturing lead time 7 to 45 working days with factory HV and partial-discharge test reports |
| Selection boundary vs Type G-BGC & US SHD-GC | Select CSA Type SHD-BGC/SHD-R/SHD-SP for 2 kV to 35 kV Canadian phase-shielded service; select CSA Type G-BGC for unshielded 2 kV duty. |
CSA C22.2 No. 96 Type SHD-BGC (2 kV to 15 kV) Braided Ground-Check Shielded Mining Cable Schedule
| Cable Designation & Core Layout | Voltage Rating | Power Core Size | Grounding Cores | Ground-Check (BGC) | Nominal EPR Wall (mm) | Nominal Overall O.D. (mm) | Approx. Net Mass (kg/km) | Ampacity at 40 °C Ambient (A) | Next step |
|---|---|---|---|---|---|---|---|---|---|
| SHD-BGC 2kV 3x4 AWG + 2x8 + 1x8 BGC | 2 kV | 4 AWG | 2x8 AWG | 8 AWG BGC | 2.8 | 38.4 | 2240 | 122 | Request this size |
| SHD-BGC 2kV 3x2 AWG + 2x6 + 1x8 BGC | 2 kV | 2 AWG | 2x6 AWG | 8 AWG BGC | 2.8 | 42.2 | 2890 | 159 | Request this size |
| SHD-BGC 5kV 3x2 AWG + 2x6 + 1x8 BGC | 5 kV | 2 AWG | 2x6 AWG | 8 AWG BGC | 3.8 | 49.3 | 3560 | 164 | Request this size |
| SHD-BGC 5kV 3x1/0 AWG + 2x4 + 1x8 BGC | 5 kV | 1/0 AWG | 2x4 AWG | 8 AWG BGC | 3.8 | 54.6 | 4680 | 211 | Request this size |
| SHD-BGC 5kV 3x2/0 AWG + 2x3 + 1x8 BGC | 5 kV | 2/0 AWG | 2x3 AWG | 8 AWG BGC | 3.8 | 58.2 | 5420 | 243 | Request this size |
| SHD-BGC 5kV 3x4/0 AWG + 2x1 + 1x8 BGC | 5 kV | 4/0 AWG | 2x1 AWG | 8 AWG BGC | 3.8 | 65.0 | 7290 | 321 | Request this size |
| SHD-BGC 8kV 3x1/0 AWG + 2x4 + 1x8 BGC | 8 kV | 1/0 AWG | 2x4 AWG | 8 AWG BGC | 4.4 | 58.4 | 5120 | 215 | Request this size |
| SHD-BGC 8kV 3x2/0 AWG + 2x3 + 1x8 BGC | 8 kV | 2/0 AWG | 2x3 AWG | 8 AWG BGC | 4.4 | 61.7 | 5890 | 248 | Request this size |
| SHD-BGC 15kV 3x1/0 AWG + 2x4 + 1x8 BGC | 15 kV | 1/0 AWG | 2x4 AWG | 8 AWG BGC | 5.3 | 65.5 | 6140 | 218 | Request this size |
| SHD-BGC 15kV 3x2/0 AWG + 2x3 + 1x8 BGC | 15 kV | 2/0 AWG | 2x3 AWG | 8 AWG BGC | 5.3 | 68.8 | 6950 | 251 | Request this size |
CSA C22.2 No. 96 Type SHD-R (Reeling) & SHD-GC-SP (Semi-Conductive Screen) 5 kV to 35 kV Schedule
| Cable Designation & Core Layout | Voltage Rating | Power Core Size | Phase Shield & Jacket Architecture | Nominal EPR Wall (mm) | Nominal Overall O.D. (mm) | Approx. Net Mass (kg/km) | Ampacity at 40 °C Ambient (A) | Next step |
|---|---|---|---|---|---|---|---|---|
| SHD-R 5kV 3x2 AWG + 2x6 + 1x8 GC | 5 kV | 2 AWG | Metallic Braid + Anti-Torsion | 3.8 | 50.8 | 3740 | 164 | Request this size |
| SHD-R 8kV 3x1/0 AWG + 2x4 + 1x8 GC | 8 kV | 1/0 AWG | Metallic Braid + Anti-Torsion | 4.4 | 59.8 | 5320 | 215 | Request this size |
| SHD-R 15kV 3x2/0 AWG + 2x3 + 1x8 GC | 15 kV | 2/0 AWG | Metallic Braid + Anti-Torsion | 5.3 | 70.4 | 7210 | 251 | Request this size |
| SHD-R 25kV 3x1/0 AWG + 2x4 + 1x8 GC | 25 kV | 1/0 AWG | Metallic Braid + Anti-Torsion | 7.5 | 78.2 | 8180 | 224 | Request this size |
| SHD-R 35kV 3x1/0 AWG + 2x4 + 1x8 GC | 35 kV | 1/0 AWG | Metallic Braid + Anti-Torsion | 9.8 | 89.6 | 10450 | 228 | Request this size |
| SHD-SP 5kV 3x2/0 AWG + 2x3 + 1x8 GC | 5 kV | 2/0 AWG | Semi-Conductive Polymeric Screen | 3.8 | 56.4 | 5120 | 243 | Request this size |
| SHD-GC-SP 8kV 3x2/0 AWG + 2x3 + 1x8 GC | 8 kV | 2/0 AWG | Semi-Conductive Polymeric Screen | 4.4 | 60.2 | 5580 | 248 | Request this size |
| SHD-GC-SP 15kV 3x2/0 AWG + 2x3 + 1x8 GC | 15 kV | 2/0 AWG | Semi-Conductive Polymeric Screen | 5.3 | 67.1 | 6610 | 251 | Request this size |
Ampacities are based on a single cable in free air at 40 C ambient and 90 C conductor temperature; apply reeling-drum layer derating factors for Type SHD-R.
Specify exact CSA designation (SHD-BGC, SHD-R, SHD-SP or SHD-GC-SP), voltage class (2 kV to 35 kV) and outer sheath colour (black, yellow or orange) on tender inquiries.
ASCII part references for BOM and ERP entry: SHD-BGC 2kV 3x4 AWG + 2x8 + 1x8 BGC, SHD-BGC 2kV 3x2 AWG + 2x6 + 1x8 BGC, SHD-BGC 5kV 3x2 AWG + 2x6 + 1x8 BGC, SHD-BGC 5kV 3x1/0 AWG + 2x4 + 1x8 BGC, SHD-BGC 5kV 3x2/0 AWG + 2x3 + 1x8 BGC, SHD-BGC 5kV 3x4/0 AWG + 2x1 + 1x8 BGC, SHD-BGC 8kV 3x1/0 AWG + 2x4 + 1x8 BGC, SHD-BGC 8kV 3x2/0 AWG + 2x3 + 1x8 BGC, SHD-BGC 15kV 3x1/0 AWG + 2x4 + 1x8 BGC, SHD-BGC 15kV 3x2/0 AWG + 2x3 + 1x8 BGC, SHD-R 5kV 3x2 AWG + 2x6 + 1x8 GC, SHD-R 8kV 3x1/0 AWG + 2x4 + 1x8 GC, SHD-R 15kV 3x2/0 AWG + 2x3 + 1x8 GC, SHD-R 25kV 3x1/0 AWG + 2x4 + 1x8 GC, SHD-R 35kV 3x1/0 AWG + 2x4 + 1x8 GC, SHD-SP 5kV 3x2/0 AWG + 2x3 + 1x8 GC, SHD-GC-SP 8kV 3x2/0 AWG + 2x3 + 1x8 GC, SHD-GC-SP 15kV 3x2/0 AWG + 2x3 + 1x8 GC.
CSA Type SHD-BGC, SHD-R and SHD-SP Applicable Standards & Related Mining Cables
| Standard or specification | Application |
|---|---|
| CSA C22.2 No. 96 | Portable power cables — Canadian construction, voltage endurance, -40 C cold impact and FT1/FT4 flame test standard for SHD-BGC, SHD-R and SHD-SP. |
| ICEA S-75-381 / NEMA WC 58 | Portable and power feeder cables for use in mines and similar applications (dimensional and electrical cross-reference). |
| ASTM B33 & ASTM B172 | Tinned soft or annealed copper wire and rope-lay stranded copper conductors for portable power cables. |
| CSA C22.2 No. 0.3 | Test methods for electrical wires and cables including -40 C cold bend, cold impact and vertical flame tests. |
Certifications and document support
TEBAOFLEX company certificates and quality system documentation
NEMA — WC 58 / ICEA S-75-381 Portable and Feeder Mining Cable Standard
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
CSA Type G-BGC and SHC-GC 2000V Portable Mining Cable
A related cable option for a different application or duty profile.
View product5kV to 15kV Mining VFD, VFD-GC and VFD-BGC Drive Cable
A related cable option for a different application or duty profile.
View productSHD-GC Cable 2kV-25kV Mining Power Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.