CSA Type G-BGC and SHC-GC 2000V Portable Mining Cable
Heavy-duty 2000 V (2 kV) Canadian portable mining power cables engineered to CSA C22.2 No. 96 for underground potash, hard-rock and open-pit mobile equipment. Covers Type G-BGC (unshielded phase cores with balanced ground-check pilot pair to cancel induced voltage) and Type SHC-GC (common overall metallic braid shield over the cabled core assembly), finished with a -40 C rated reinforced thermoset CPE jacket.
Canadian underground potash mines, hard-rock operations and cold-climate open-pit quarries specify two specialized 2000 V portable power constructions under CSA C22.2 No. 96 that differ fundamentally from standard North American Type G-GC and Type SHD-GC cables: Type G-BGC (Balanced Ground-Check) and Type SHC-GC (Shielded Common with Ground-Check). Selecting the exact CSA designation ensures compatibility with mine ground-fault relays and phase-to-ground protection schemes.
In conventional asymmetric 2000 V Type G-GC cables, high phase currents flowing through long trailing lengths induce an unbalanced longitudinal electromotive force (EMF) into the single off-center ground-check conductor, causing nuisance relay trips or circulating stray currents. CSA Type G-BGC resolves this by replacing the single pilot with a geometrically balanced, low-induced-voltage pilot assembly in the third interstice opposite the two split grounding conductors, keeping induced voltage below Canadian mine relay thresholds.
Where provincial mining codes require metallic fault screening at 2000 V without the larger diameter and stiffness of individually shielded Type SHD-GC, CSA Type SHC-GC applies a flexible overall tinned copper braid shield (SHC = Shielded Common) around the complete cabled core assembly beneath the reinforced dual-layer thermoset Chlorinated Polyethylene (CPE) jacket. Both constructions pass CSA -40 C cold bend and cold impact tests and FT4 flame testing.
Explore the mining and tunneling cable range for related configurations.
CSA Type G-BGC and SHC-GC 2000V Construction
The horizontal sample illustrates the 2000 V CSA C22.2 No. 96 Type G-BGC and Type SHC-GC constructions, highlighting the three rope-lay tinned copper phase conductors with 90 C EPR insulation (Black, White, Red), two split tinned copper grounding conductors, the yellow balanced ground-check (BGC) pilot assembly or single GC pilot, overall tinned copper braid shield (on Type SHC-GC), reinforcing textile braid and -40 C black thermoset CPE jacket.

| Component | Material and construction |
|---|---|
| Phase Conductors (3 x Rope-Lay Tinned Copper) | 8 AWG through 500 kcmil annealed tinned copper rope-lay bunched stranding per CSA C22.2 No. 96 and ASTM B33/B172 for high flex life. |
| 90 C EPR Phase Insulation | Heavy-duty thermosetting Ethylene Propylene Rubber (EPR) rated 90 C continuous, color-coded Black, White and Red for phase identification. |
| Grounding Conductors (2 x Split Ground) | Two uninsulated (or green/yellow covered per order) flexible stranded tinned copper grounding conductors laid in two outer interstices with combined cross-section >= 50% of one phase conductor. |
| Ground-Check Pilot (G-BGC vs SHC-GC) | Type G-BGC incorporates a yellow EPR-insulated balanced ground-check (BGC) twisted pair or coaxial low-induced-voltage pilot; Type SHC-GC uses an 8 AWG yellow EPR-insulated ground-check conductor. |
| Overall Common Shield (Type SHC-GC Only) | Helically applied semi-conducting tape plus flexible tinned copper braid shield (minimum 85% coverage) enclosing the entire cabled core assembly in Type SHC-GC. |
| Reinforced Dual-Layer -40 C CPE Jacket | Inner and outer black heavy-duty thermoset Chlorinated Polyethylene (CPE) jacket vulcanized around an open-weave nylon reinforcing braid, rated to -40 C cold impact and CSA FT4 / MSHA flame resistance. |
CSA Type G-BGC and SHC-GC 2000V Code and Designation Breakdown
- CSA C22.2 No. 96: Canadian Standards Association specification governing 2000 V portable power cables for mining and industrial service
- Type G-BGC: Three EPR phase cores, two split grounding conductors and a geometrically balanced ground-check (BGC) pilot assembly to cancel induced EMF voltage
- Type SHC-GC: Three EPR phase cores, two split grounds and an 8 AWG ground-check pilot enclosed within a common overall tinned copper braid shield (SHC = Shielded Common)
- 2000 V (2 kV): Rated continuous phase-to-phase 60 Hz AC portable and trailing mining operating voltage across 8 AWG to 500 kcmil
- -40 °C Cold Impact: CSA C22.2 No. 0.3 Arctic cold bend and cold impact rating for Canadian surface pits and underground potash/hard-rock mines
- FT4 / MSHA CPE Jacket: Dual-layer reinforced thermoset Chlorinated Polyethylene (CPE) jacket complying with CSA FT1/FT4 and MSHA 30 CFR Part 7 flame resistance
CSA Type G-BGC and SHC-GC 2000V Applications
Specify CSA Type G-BGC or Type SHC-GC 2000 V cables for Canadian underground mines, Arctic surface pits and mobile mining machinery operating up to 2 kV.

- Long trailing feeder runs to underground potash borer miners, continuous miners, shuttle cars and mobile bridge conveyors using sensitive balanced ground-check (BGC) monitoring relays.
- 2000 V portable load centers, mine dewatering skid pumps, jumbo drills and portable crushers requiring CSA C22.2 No. 96 common metallic fault shielding (Type SHC-GC).
- Extreme cold-weather surface mining and Arctic exploration equipment down to -40 C ambient temperature without jacket cracking.
- Direct replacement for Canadian equipment schedules specifying Type G-BGC (unshielded balanced pilot) or Type SHC-GC (common shield), avoiding mismatch with standard Type G-GC or individually shielded Type SHD-BGC.
CSA Type G-BGC and SHC-GC 2000V Model Comparison and Selection Boundary
| CSA / ICEA Designation | Rated Voltage | Metallic Shielding | Ground-Check Pilot Architecture | Typical North American Mining Use |
|---|---|---|---|---|
| CSA Type G-BGC | 2000 V (2 kV) | Unshielded phase cores | Geometrically balanced low-induced-voltage BGC pilot pair | Long 2 kV trailing runs in Canadian potash and hard-rock mines using sensitive GWM relays |
| CSA Type SHC-GC | 2000 V (2 kV) | Overall common tinned copper braid shield over core assembly | Single 8 AWG insulated ground-check (GC) pilot | 2 kV portable load centers, pumps and drills requiring common metallic fault screening |
| Type G-GC / Type G-CGC | 2000 V (2 kV) | Unshielded phase cores | Single asymmetric interstitial GC (or center CGC) pilot | Standard shorter 2 kV portable power feeders without induced-EMF relay tripping |
| CSA Type SHD-BGC / SHD-GC | 2 kV to 25 kV | Individual copper tape/braid shield over each phase core | Balanced BGC pilot pair (SHD-BGC) or single GC pilot (SHD-GC) | High-capacity longwall shearers, shovels and medium-voltage trailing feeders |
Select Type G-BGC when induced pilot voltage on long 2000 V runs causes nuisance ground-wire monitor trips; select Type SHC-GC when provincial rules require metallic fault shielding in a compact 2 kV cable.
Related selection resources
- Mining and tunneling cable engineering solutions
- North American portable mining cable comparison and selection guide
- Type G-CGC 2000V round portable mining cable with center ground-check
- Type SHD-PCG 2 kV shielded portable mining power and control cable
- AS/NZS 1802 Type 245F and 241F Electro-Optic Mining Cable
CSA Type G-BGC and SHC-GC 2000V Frequently Asked Questions
Why do Canadian potash and hard-rock mines specify CSA Type G-BGC instead of standard Type G-GC?
On long 2000 V trailing cable runs carrying high phase current, asymmetric single-pilot Type G-GC cables experience longitudinal electromagnetic induction into the off-center pilot wire, which can exceed Canadian ground-wire monitor (GWM) voltage thresholds. CSA Type G-BGC uses a geometrically balanced low-induced-voltage pilot assembly in the third interstice to cancel induced EMF.
How does CSA Type SHC-GC differ from Type SHD-GC at 2000 V?
Type SHC-GC (Shielded Common with Ground-Check) applies one flexible overall tinned copper braid shield around the complete cabled core assembly beneath the reinforced CPE jacket, providing metallic fault containment with a smaller outside diameter and tighter bend radius than individually phase-shielded Type SHD-GC.
Are CSA Type G-BGC and Type SHC-GC rated for -40 °C Arctic surface and underground service?
Yes. Both cables use a reinforced dual-layer thermoset Chlorinated Polyethylene (CPE) outer jacket and 90 °C EPR insulation that pass CSA C22.2 No. 0.3 cold-bend and cold-impact tests at -40 °C as well as CSA FT1/FT4 and MSHA flame tests.
What are the MOQ and manufacturing lead time for CSA Type G-BGC and Type SHC-GC?
All sizes from 8 AWG to 500 kcmil are manufactured from a 50 m minimum order quantity (MOQ) with a 7 to 45 working day lead time, available in black or high-visibility yellow/orange CPE jackets.
CSA Type G-BGC and SHC-GC 2000V Technical Specifications
CSA Type G-BGC and SHC-GC 2000V Key Specifications
- Standard & Models: CSA C22.2 No. 96-23 Type G-BGC (balanced ground-check) and Type SHC-GC (overall common braid shield)
- Voltage & Size Range: 2000 V (2 kV) AC three-phase; 8 AWG through 500 kcmil rope-lay tinned copper phase conductors
- Ground & Pilot Design: Two split grounding conductors + low-induced-voltage BGC pilot pair (Type G-BGC) or 8 AWG GC pilot (Type SHC-GC)
- Jacket & Cold Rating: Reinforced dual-layer thermoset CPE jacket rated -40 °C CSA cold impact, CSA FT1/FT4 and MSHA flame resistant
- Bend Radius & Supply: 6 x O.D. minimum dynamic bending radius; MOQ 50 m; manufacturing lead time 7 to 45 working days
| Parameter | Value |
|---|---|
| Governing standard reference | Engineered to CSA C22.2 No. 96 Portable Power Cables and ICEA S-75-381 / NEMA WC 58 dimensional schedules |
| Rated operating voltage | 2000 V (2 kV) phase-to-phase AC 60 Hz continuous portable and trailing mining service |
| Type G-BGC vs Type SHC-GC architecture | Type G-BGC is unshielded with a balanced low-induced-voltage pilot; Type SHC-GC adds an overall common tinned copper braid shield |
| Thermal and Arctic cold rating | 90 C continuous conductor rating, 250 C short-circuit rating and -40 C CSA cold bend and cold impact rating |
| Flame resistance and jacket durability | Meets CSA FT1, CSA FT4 and MSHA 30 CFR Part 7 flame test criteria; oil, ozone, sunlight, alkali and abrasion resistant |
| Minimum bending radius and supply terms | 6 x overall cable diameter minimum bending radius; MOQ 50 m with 7 to 45 working days manufacturing lead time |
| Selection boundary vs G-GC & SHD-BGC | Choose Type G-BGC/SHC-GC for 2000 V unshielded-balanced or common-shielded service; choose standard Type G-GC for asymmetric 2 kV circuits; choose Type SHD-BGC for individually phase-shielded 2 kV to 25 kV cables. |
CSA Type G-BGC 2000 V Balanced Ground-Check Size Schedule (8 AWG–500 kcmil)
| Phase Size | Phase Stranding | Grounding Conductors | Balanced GC Pilot | Nom. Insulation Wall (in / mm) | Nom. Jacket Wall (in / mm) | Nom. Overall O.D. (in / mm) | Approx. Net Weight (lbs/1000 ft / kg/km) | Ampacity 30 °C Ambient (A) | Min. Bend Radius (mm) | Next step |
|---|---|---|---|---|---|---|---|---|---|---|
| 8 AWG | 133 | 2 x 10 AWG | 2 x 12 AWG BGC Pair | 0.060 / 1.52 | 0.125 / 3.18 | 0.94 / 23.9 | 580 / 863 | 72 | 143 | Request this size |
| 6 AWG | 259 | 2 x 10 AWG | 2 x 12 AWG BGC Pair | 0.060 / 1.52 | 0.140 / 3.56 | 1.05 / 26.7 | 760 / 1131 | 95 | 160 | Request this size |
| 4 AWG | 259 | 2 x 8 AWG | 2 x 10 AWG BGC Pair | 0.060 / 1.52 | 0.140 / 3.56 | 1.19 / 30.2 | 1040 / 1548 | 125 | 181 | Request this size |
| 2 AWG | 259 | 2 x 6 AWG | 2 x 10 AWG BGC Pair | 0.060 / 1.52 | 0.155 / 3.94 | 1.34 / 34.0 | 1460 / 2173 | 165 | 204 | Request this size |
| 1 AWG | 259 | 2 x 5 AWG | 2 x 10 AWG BGC Pair | 0.080 / 2.03 | 0.170 / 4.32 | 1.51 / 38.4 | 1850 / 2753 | 190 | 230 | Request this size |
| 1/0 AWG | 266 | 2 x 4 AWG | 2 x 10 AWG BGC Pair | 0.080 / 2.03 | 0.185 / 4.70 | 1.65 / 41.9 | 2240 / 3333 | 220 | 251 | Request this size |
| 2/0 AWG | 342 | 2 x 3 AWG | 2 x 10 AWG BGC Pair | 0.080 / 2.03 | 0.190 / 4.83 | 1.75 / 44.5 | 2680 / 3988 | 255 | 267 | Request this size |
| 3/0 AWG | 418 | 2 x 2 AWG | 2 x 10 AWG BGC Pair | 0.080 / 2.03 | 0.205 / 5.21 | 1.89 / 48.0 | 3260 / 4851 | 295 | 288 | Request this size |
| 4/0 AWG | 532 | 2 x 1 AWG | 2 x 10 AWG BGC Pair | 0.080 / 2.03 | 0.210 / 5.33 | 2.04 / 51.8 | 3950 / 5878 | 340 | 311 | Request this size |
| 250 kcmil | 608 | 2 x 1/0 AWG | 2 x 8 AWG BGC Pair | 0.095 / 2.41 | 0.220 / 5.59 | 2.22 / 56.4 | 4680 / 6965 | 375 | 338 | Request this size |
| 350 kcmil | 855 | 2 x 2/0 AWG | 2 x 8 AWG BGC Pair | 0.095 / 2.41 | 0.235 / 5.97 | 2.48 / 63.0 | 6190 / 9212 | 455 | 378 | Request this size |
| 500 kcmil | 1221 | 2 x 4/0 AWG | 2 x 8 AWG BGC Pair | 0.095 / 2.41 | 0.265 / 6.73 | 2.84 / 72.1 | 8450 / 12575 | 560 | 433 | Request this size |
CSA Type SHC-GC 2000 V Common-Shielded Size Schedule (8 AWG–500 kcmil)
| Phase Size | Phase Stranding | Grounding Conductors | GC Pilot Size | Overall Shield Type | Nom. Insulation Wall (in / mm) | Nom. Overall O.D. (in / mm) | Approx. Net Weight (lbs/1000 ft / kg/km) | Ampacity 30 °C Ambient (A) |
|---|---|---|---|---|---|---|---|---|
| 8 AWG | 133 | 2 x 10 AWG | 8 AWG | Common Tinned Cu Braid | 0.060 / 1.52 | 1.01 / 25.7 | 650 / 967 | 72 |
| 6 AWG | 259 | 2 x 10 AWG | 8 AWG | Common Tinned Cu Braid | 0.060 / 1.52 | 1.12 / 28.4 | 845 / 1257 | 95 |
| 4 AWG | 259 | 2 x 8 AWG | 8 AWG | Common Tinned Cu Braid | 0.060 / 1.52 | 1.26 / 32.0 | 1145 / 1704 | 125 |
| 2 AWG | 259 | 2 x 6 AWG | 8 AWG | Common Tinned Cu Braid | 0.060 / 1.52 | 1.42 / 36.1 | 1590 / 2366 | 165 |
| 1 AWG | 259 | 2 x 5 AWG | 8 AWG | Common Tinned Cu Braid | 0.080 / 2.03 | 1.59 / 40.4 | 2010 / 2991 | 190 |
| 1/0 AWG | 266 | 2 x 4 AWG | 8 AWG | Common Tinned Cu Braid | 0.080 / 2.03 | 1.73 / 43.9 | 2420 / 3601 | 220 |
| 2/0 AWG | 342 | 2 x 3 AWG | 8 AWG | Common Tinned Cu Braid | 0.080 / 2.03 | 1.84 / 46.7 | 2890 / 4301 | 255 |
| 3/0 AWG | 418 | 2 x 2 AWG | 8 AWG | Common Tinned Cu Braid | 0.080 / 2.03 | 1.98 / 50.3 | 3510 / 5223 | 295 |
| 4/0 AWG | 532 | 2 x 1 AWG | 8 AWG | Common Tinned Cu Braid | 0.080 / 2.03 | 2.13 / 54.1 | 4230 / 6295 | 340 |
| 250 kcmil | 608 | 2 x 1/0 AWG | 8 AWG | Common Tinned Cu Braid | 0.095 / 2.41 | 2.31 / 58.7 | 5010 / 7456 | 375 |
| 350 kcmil | 855 | 2 x 2/0 AWG | 8 AWG | Common Tinned Cu Braid | 0.095 / 2.41 | 2.58 / 65.5 | 6590 / 9807 | 455 |
| 500 kcmil | 1221 | 2 x 4/0 AWG | 8 AWG | Common Tinned Cu Braid | 0.095 / 2.41 | 2.94 / 74.7 | 8920 / 13274 | 560 |
Ampacities are based on 90 °C conductor temperature and 30 °C ambient air temperature for single three-conductor portable cable in free air per CSA C22.2 No. 96 / CE Code Part I; apply reel-layer derating factors (0.85 for 1 layer, 0.65 for 2 layers, 0.45 for 3 layers, 0.35 for 4 layers) when operated on reeling drums.
Type G-BGC balanced pilot conductors can be supplied as a symmetrical twisted pair or a low-reactance concentric balanced pilot depending on the mine ground-wire monitor (GWM) relay model; specify the relay type when ordering.
High-visibility yellow, orange or black thermoset CPE / Polychloroprene outer jackets are available to match provincial mine color-coding regulations.
ASCII part references for BOM and ERP entry: CSA G-BGC 3x8 AWG, CSA G-BGC 3x6 AWG, CSA G-BGC 3x4 AWG, CSA G-BGC 3x2 AWG, CSA G-BGC 3x1 AWG, CSA G-BGC 3x1/0 AWG, CSA G-BGC 3x2/0 AWG, CSA G-BGC 3x3/0 AWG, CSA G-BGC 3x4/0 AWG, CSA G-BGC 3x250 kcmil, CSA G-BGC 3x350 kcmil, CSA G-BGC 3x500 kcmil, CSA SHC-GC 3x4 AWG, CSA SHC-GC 3x2 AWG, CSA SHC-GC 3x2/0 AWG, CSA SHC-GC 3x4/0 AWG.
CSA Type G-BGC and SHC-GC 2000V Standards and Test References
| Standard or specification | Application |
|---|---|
| CSA C22.2 No. 96-23 | Canadian Standard for Portable Power Cables covering 2000 V Type G-BGC and Type SHC-GC construction, physical and electrical testing. |
| ICEA S-75-381 / NEMA WC 58 | Portable and Power Feeder Cables for Use in Mines and Similar Applications (conductor stranding, EPR dielectric and ampacity reference). |
| CSA C22.2 No. 0.3 (-40 °C Cold Test) | Low-temperature cold bend and cold impact testing at -40 °C for Arctic and Canadian surface/underground mining cables. |
| CSA FT1 / FT4 & MSHA 30 CFR Part 7 | Vertical tray flame propagation resistance and mine flame-resistance acceptance test criteria. |
Certifications and document support
TEBAOFLEX company certificates and quality system documentation
NEMA / ICEA S-75-381 & S-93-639 Medium-Voltage Mining and Shielded Power Cable Standards
IEC Webstore — IEC 60228 Class 5 Conductors and IEC 60332 Flame Testing Standards
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
Type G-GC Cable 2000V Portable Mining Power Cable
A related cable option for a different application or duty profile.
View productSHD-GC Cable 2kV-25kV Mining Power Cable
A related cable option for a different application or duty profile.
View productType G-CGC 2000V Round Portable Mining Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.