TF-MVVFD-3G 3.6/6 kV & 6/10 kV Class 5 Flexible Rubber Symmetrical 3+3 MV VFD Motor Cable

TF-MVVFD-3G is a Class 5 finely stranded flexible medium-voltage VFD motor connection cable rated 3.6/6 kV (11 kV test) and 6/10 kV (17 kV test), combining enhanced-dielectric EPR phase insulation, individual tinned-copper wire braid screens on each phase, three symmetrically split bare protective earth conductors in the interstices (3×16+3×16/3 to 3×240+3×120/3 mm²) and an oil-resistant red flame-retardant rubber outer sheath (LOI above 29, IEC 60332-3-24).

Product information
SKU
TF-MVVFD-3G
Brand
TEBAOFLEX
Product overview

TF-MVVFD-3G flexible medium-voltage VFD motor cable connects 3.3 kV, 4.16 kV, 6 kV, 6.6 kV and 10 kV PWM frequency converters to high-power induction and synchronous motors across 3×16+3×16/3 to 3×240+3×120/3 mm², pairing Class 5 flexible copper, semiconductive-screened EPR insulation, per-phase tinned-copper wire braids, three split earth cores and a red FR rubber sheath (-40 °C to +90 °C).

Fixed Class 2 copper-tape cables such as 3GSEGCH or 3GSEGCY work well on long straight tray runs, but become difficult to dress inside compact skid-mounted MV drive houses, vibrating compressor bases, marine thruster rooms and motor test cells—and rigid copper tapes can fatigue under continuous machinery vibration. TF-MVVFD-3G replaces stiff Class 2 conductors and helically lapped copper tapes with Class 5 fine-wire copper and flexible tinned-copper wire braids over each semiconductive-screened EPR core, while placing three equal bare earth conductors in the outer interstices so high-frequency dV/dt capacitive currents return symmetrically without inducing shaft voltages across motor bearings.

Select the 3.6/6 kV schedule or 6/10 kV schedule according to your converter's phase-to-earth waveform stress and motor voltage class (published capacitance 310 to 840 nF/km and inductance 0.27 to 0.40 mH/km support drive output filter calculations). For fixed tray/buried Class 2 installations see 3GSEGCH / 3GSEGCY, and for portable mining couplers with ground-check pilots see 5–15 kV Mining VFD-GC.

Explore the heavy-duty industrial cable range for related configurations.

Construction

TF-MVVFD-3G Flexible 3+3 MV VFD Cable Construction

TF-MVVFD-3G is built around symmetrical 120-degree phase-and-ground geometry to contain PWM harmonics and dV/dt spikes.

Clean 2D engineering cross-section of TF-MVVFD-3G 3+3 MV VFD cable showing three Class 5 copper phase cores with inner semiconductive, EPR insulation, outer semiconductive and tinned copper braid rings, three bare copper earth cores in the outer interstices and a red rubber outer sheath
TF-MVVFD-3G cross-section: symmetrical 3+3 MV VFD core geometry with individual phase braids and interstitial earths.
TF-MVVFD-3G 3.6/6 kV & 6/10 kV Class 5 Flexible Rubber Symmetrical 3+3 MV VFD Motor Cable construction
ComponentMaterial and construction
1. Phase conductorsPlain annealed multi-stranded copper, class 5 to EN / IEC 60228 (16 mm² to 240 mm²).
2. Conductor & insulation screensInner semiconductive rubber stress-control layer, enhanced-dielectric neutral-colour EPR insulation, and outer semiconductive rubber plus semiconductive tape.
3. Individual phase braids & 3 split earthsTinned copper wire braid over each insulated phase core, laid up symmetrically with three bare copper protective conductors in the outer interstices.
4. SeparatorSemiconductive wrapping tape over the assembled 3+3 core bundle.
5. Outer sheathRed flame-retardant, UV- and oil-resistant heavy rubber compound with limiting oxygen index (LOI) above 29; OD tolerance ±5 %.

TF-MVVFD-3G Designation and Size Code Breakdown

  • TF-MVVFD-3G: TEBAOFLEX Class 5 flexible rubber symmetrical 3-phase + 3-ground MV VFD motor cable
  • 3.6/6 kV or 6/10 kV: Rated phase-to-earth / phase-to-phase voltage class (11 kV or 17 kV AC factory test)
  • 3x16 to 3x240: Three Class 5 finely stranded plain copper phase conductors (mm²)
  • +3x16/3 to +3x120/3: Total protective-earth cross-section split equally into three interstitial bare conductors
  • LOI > 29 Red Rubber: Oil- and UV-resistant flame-retardant rubber sheath passing EN/IEC 60332-3-24
Applications

TF-MVVFD-3G Medium-Voltage Converter Motor Applications

TF-MVVFD-3G is engineered for industrial and heavy-duty medium-voltage variable-speed motor drives requiring flexible routing and low transfer impedance.

Industrial compressor house showing a red flexible TF-MVVFD-3G medium-voltage VFD power cable sweeping smoothly into an EMC-glanded 6 kV motor terminal box
Typical duty: flexible 3.6/6 or 6/10 kV converter-to-motor lead entering a high-power industrial motor.
  • Converter-to-motor power leads on 3.3 kV, 4.16 kV, 6 kV, 6.6 kV and 10 kV industrial VFD blowers, boiler feed pumps, Banbury mixers and rolling mills.
  • Skid-mounted compressors, slurry pump stations, test-bed dynamometers and vibrating machinery frames where Class 2 tape-screened cables are too stiff.
  • Indoor cable trays, tight-bend motor terminal boxes (10 x OD) and outdoor UV/oil-exposed industrial plant pipe racks (-40 °C to +90 °C).

TF-MVVFD-3G vs Fixed 3GSEGCH and Mining VFD-GC Cables

TF-MVVFD-3G (Class 5 Flexible Rubber 3+3) vs 3GSEGCH / 3GSEGCY vs Mining VFD-GC vs 2XSLCYK-J
Cable familyConductor & screenVoltage ratingPrimary installation
TF-MVVFD-3G (this page)Class 5 Cu + per-phase tinned Cu braid + 3 split earths3.6/6 kV & 6/10 kVFlexible MV VFD motor leads, vibrating skids, tight cabinets
3GSEGCH / 3GSEGCYClass 2 Cu + copper tapes + overall wire screen3.6/6 (conv.) / 6/10 kVFixed industrial trays, ducts and buried (3GSEGCY) feeders
Mining VFD-GC (5–15 kV)Flexible Cu + metallic shield + 3 grounds + GC pilot5 kV, 8 kV, 15 kVPortable mine VFD shovels and drills with ground-check
2XSLCYK-J / 2YSLCYK-JBClass 5 Cu + foil + tinned Cu braid0.6/1 kVLow-voltage 400–690 V inverter motors

Selection tip: many 3.3–4.16 kV multi-level drives specify 3.6/6 kV insulation while 6–6.6 kV drives or ungrounded/resonant-earthed converters specify 6/10 kV walls to accommodate reflected-wave voltage doubling.

TF-MVVFD-3G Medium-Voltage VFD Cable RFQ Checklist

  • Voltage series (3.6/6 kV or 6/10 kV), converter nominal output voltage, DC-bus link voltage and switching frequency.
  • Conductor and split-earth size from 3x16+3x16/3 up to 3x240+3x120/3 mm² (note both 3x35+3x16/3 and 3x35+3x25/3 options).
  • Run length between VFD output cabinet and motor terminal box (to check C = 310–840 nF/km charging current).
  • EMC cable gland brass cone sizing (nominal OD ±5 %) and indoor/outdoor tray grouping.
  • Total meterage, cut-length schedule and target delivery (MOQ 50 m; 7 to 45 working days).

Related selection resources

TF-MVVFD-3G Flexible MV VFD Cable FAQ

Why does TF-MVVFD-3G use a 3+3 symmetrical layout on MV VFD motors?

3 split interstitial earth conductors arranged at 120 degrees alongside 3 individually braided phases cancel magnetic asymmetry, returning high-frequency PWM common-mode currents evenly instead of through motor bearings.

How does TF-MVVFD-3G differ from 3GSEGCH / 3GSEGCY?

Class 5 flexible copper conductors, flexible tinned-copper wire braids and a red rubber sheath (-40 °C to +90 °C) replace the rigid Class 2 conductors, copper tapes and polyolefin/PVC sheaths of fixed 3GSEGCH / 3GSEGCY cables.

Does TF-MVVFD-3G pass bunched-cable flame testing?

Yes. The red flame-retardant rubber outer sheath has a limiting oxygen index (LOI) above 29 and complies with both EN/IEC 60332-1-2 and bunched flame test EN/IEC 60332-3-24.

What size range is offered in TF-MVVFD-3G 3.6/6 kV vs 6/10 kV?

10 sizes from 3x16+3x16/3 to 3x185+3x95/3 mm² in 3.6/6 kV (11 kV test), and 11 sizes up to 3x240+3x120/3 mm² in 6/10 kV (17 kV test).

What are the MOQ and lead time for TF-MVVFD-3G?

50 m minimum order quantity with a manufacturing lead time of 7 to 45 working days.

Specifications

TF-MVVFD-3G 3.6/6 kV & 6/10 kV Technical Data and Schedule

TF-MVVFD-3G Key Dielectric, EMC and Thermal Ratings

  • Symmetrical 3+3 EMC layout: Three individually braided-screened EPR phases plus three interstitial bare earth conductors equalize common-mode return currents
  • Class 5 flexible routing: Multi-stranded EN/IEC 60228 class 5 copper accepts 10 x OD bending into cramped MV motor and drive cabinets
  • 3.6/6 kV & 6/10 kV series: 10 sizes at 3.6/6 kV (up to 185 mm²) and 11 sizes at 6/10 kV (up to 240 mm²) with published C and L data
  • Bunched-flame FR rubber: Red oil-resistant rubber sheath with oxygen index above 29, tested to EN/IEC 60332-1-2 and 60332-3-24
  • Project production: Custom cut lengths and gland-matched OD control from MOQ 50 m in 7 to 45 working days
TF-MVVFD-3G 3.6/6 kV & 6/10 kV Class 5 Flexible Rubber Symmetrical 3+3 MV VFD Motor Cable technical data
ParameterValue
Rated voltage3.6/6 kV (11 kV AC test) and 6/10 kV (17 kV AC test) MV converter duty
Conductor and earth rangeClass 5 copper 3x16+3x16/3 to 3x185+3x95/3 (3.6/6 kV) and up to 3x240+3x120/3 (6/10 kV)
EMC screeningSemiconductive rubber and tape plus tinned copper wire braid on each phase and 3 symmetrical earths
Insulation and sheathEnhanced-parameter EPR phase dielectric and red oil-resistant FR rubber sheath (LOI above 29)
Temperature limits-40 °C to +90 °C operating ambient; 90 °C max conductor; 250 °C max short-circuit (5 s)
Minimum bend radius10 x cable outer diameter (425 mm on 3.6/6 kV 3x16 up to 802 mm on 6/10 kV 3x240)
Supply termsMOQ 50 m; manufacturing lead time 7 to 45 working days

TF-MVVFD-3G 3.6/6 kV and 6/10 kV Symmetrical 3+3 Schedule

TF-MVVFD-3G 3.6/6 kV and 6/10 kV Class 5 flexible rubber MV VFD cable — nominal outer diameter (±5 %), DC resistance at 20 °C, capacitance, inductance, 30 °C single-cable air ampacity and weight
Model, voltage and sizeRated U0/UNominal OD (mm)Max. DC resistance at 20 °C (Ω/km)Capacitance (nF/km)Inductance (mH/km)Current at 30 °C air (A)Approx. weight (kg/km)Next step
TF-MVVFD-3G 3.6/6 kV 3x16+3x16/33.6/6 kV42.51.243400.391092,540Request this size
TF-MVVFD-3G 3.6/6 kV 3x25+3x16/33.6/6 kV46.00.7953900.371413,185Request this size
TF-MVVFD-3G 3.6/6 kV 3x35+3x16/33.6/6 kV48.20.5654400.341743,555Request this size
TF-MVVFD-3G 3.6/6 kV 3x35+3x25/33.6/6 kV48.20.5654400.341743,575Request this size
TF-MVVFD-3G 3.6/6 kV 3x50+3x25/33.6/6 kV52.60.3934900.332154,335Request this size
TF-MVVFD-3G 3.6/6 kV 3x70+3x35/33.6/6 kV56.50.2775600.312665,300Request this size
TF-MVVFD-3G 3.6/6 kV 3x95+3x50/33.6/6 kV60.20.2106400.303186,500Request this size
TF-MVVFD-3G 3.6/6 kV 3x120+3x70/33.6/6 kV63.80.1646900.293677,600Request this size
TF-MVVFD-3G 3.6/6 kV 3x150+3x70/33.6/6 kV68.70.1327700.284188,790Request this size
TF-MVVFD-3G 3.6/6 kV 3x185+3x95/33.6/6 kV74.50.1088400.2747710,520Request this size
TF-MVVFD-3G 6/10 kV 3x16+3x16/36/10 kV44.31.243100.401092,800Request this size
TF-MVVFD-3G 6/10 kV 3x25+3x16/36/10 kV47.70.7953500.381413,360Request this size
TF-MVVFD-3G 6/10 kV 3x35+3x16/36/10 kV49.90.5654000.351743,740Request this size
TF-MVVFD-3G 6/10 kV 3x35+3x25/36/10 kV49.90.5654000.351743,760Request this size
TF-MVVFD-3G 6/10 kV 3x50+3x25/36/10 kV54.30.3934400.342154,535Request this size
TF-MVVFD-3G 6/10 kV 3x70+3x35/36/10 kV58.20.2775000.322665,515Request this size
TF-MVVFD-3G 6/10 kV 3x95+3x50/36/10 kV62.90.2105800.303186,875Request this size
TF-MVVFD-3G 6/10 kV 3x120+3x70/36/10 kV65.50.1646200.293677,845Request this size
TF-MVVFD-3G 6/10 kV 3x150+3x70/36/10 kV70.50.1326900.284189,050Request this size
TF-MVVFD-3G 6/10 kV 3x185+3x95/36/10 kV76.20.1087600.2747710,800Request this size
TF-MVVFD-3G 6/10 kV 3x240+3x120/36/10 kV80.20.08178100.2755212,800Request this size

Current-carrying capacities apply to a single cable in free air at 30 °C ambient; apply grouping and ambient derating factors for enclosed trays or multi-cable racks.

Outer diameter tolerance is ±5 %; minimum installation bend radius is 10 x nominal cable outer diameter.

ASCII part references: TF-MVVFD-3G 3.6/6 kV 3x50+3x25/3; TF-MVVFD-3G 3.6/6 kV 3x95+3x50/3; TF-MVVFD-3G 6/10 kV 3x70+3x35/3; TF-MVVFD-3G 6/10 kV 3x185+3x95/3; TF-MVVFD-3G 6/10 kV 3x240+3x120/3.

Standards

TF-MVVFD-3G Standards and Flame Test References

TF-MVVFD-3G 3.6/6 kV & 6/10 kV Class 5 Flexible Rubber Symmetrical 3+3 MV VFD Motor Cable standards and test references
Standard or specificationApplication
EN / IEC 60228Class 5 multi-stranded flexible annealed copper conductors.
IEC 60502-2 (reference)Medium-voltage EPR dielectric, semiconductive field control and 11 kV / 17 kV AC voltage test basis.
EN / IEC 60332-1-2 & 60332-3-24Single-cable and Category C bunched-cable vertical flame propagation resistance (LOI above 29).
EN / IEC 60811-404Oil resistance verification of the red elastomer outer sheath.

Certifications and document support

TEBAOFLEX ISO quality assurance and routine factory test reports

IEC Webstore — IEC 60228 conductor, IEC 60332 flame and IEC 60811 oil test references

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    MOQ 50 m · Engineering reply within 24 hours

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.