TF-MVVFD-3G 3.6/6 kV & 6/10 kV Class 5 Flexible Rubber Symmetrical 3+3 MV VFD Motor Cable
TF-MVVFD-3G is a Class 5 finely stranded flexible medium-voltage VFD motor connection cable rated 3.6/6 kV (11 kV test) and 6/10 kV (17 kV test), combining enhanced-dielectric EPR phase insulation, individual tinned-copper wire braid screens on each phase, three symmetrically split bare protective earth conductors in the interstices (3×16+3×16/3 to 3×240+3×120/3 mm²) and an oil-resistant red flame-retardant rubber outer sheath (LOI above 29, IEC 60332-3-24).
TF-MVVFD-3G flexible medium-voltage VFD motor cable connects 3.3 kV, 4.16 kV, 6 kV, 6.6 kV and 10 kV PWM frequency converters to high-power induction and synchronous motors across 3×16+3×16/3 to 3×240+3×120/3 mm², pairing Class 5 flexible copper, semiconductive-screened EPR insulation, per-phase tinned-copper wire braids, three split earth cores and a red FR rubber sheath (-40 °C to +90 °C).
Fixed Class 2 copper-tape cables such as 3GSEGCH or 3GSEGCY work well on long straight tray runs, but become difficult to dress inside compact skid-mounted MV drive houses, vibrating compressor bases, marine thruster rooms and motor test cells—and rigid copper tapes can fatigue under continuous machinery vibration. TF-MVVFD-3G replaces stiff Class 2 conductors and helically lapped copper tapes with Class 5 fine-wire copper and flexible tinned-copper wire braids over each semiconductive-screened EPR core, while placing three equal bare earth conductors in the outer interstices so high-frequency dV/dt capacitive currents return symmetrically without inducing shaft voltages across motor bearings.
Select the 3.6/6 kV schedule or 6/10 kV schedule according to your converter's phase-to-earth waveform stress and motor voltage class (published capacitance 310 to 840 nF/km and inductance 0.27 to 0.40 mH/km support drive output filter calculations). For fixed tray/buried Class 2 installations see 3GSEGCH / 3GSEGCY, and for portable mining couplers with ground-check pilots see 5–15 kV Mining VFD-GC.
Explore the heavy-duty industrial cable range for related configurations.
TF-MVVFD-3G Flexible 3+3 MV VFD Cable Construction
TF-MVVFD-3G is built around symmetrical 120-degree phase-and-ground geometry to contain PWM harmonics and dV/dt spikes.

| Component | Material and construction |
|---|---|
| 1. Phase conductors | Plain annealed multi-stranded copper, class 5 to EN / IEC 60228 (16 mm² to 240 mm²). |
| 2. Conductor & insulation screens | Inner semiconductive rubber stress-control layer, enhanced-dielectric neutral-colour EPR insulation, and outer semiconductive rubber plus semiconductive tape. |
| 3. Individual phase braids & 3 split earths | Tinned copper wire braid over each insulated phase core, laid up symmetrically with three bare copper protective conductors in the outer interstices. |
| 4. Separator | Semiconductive wrapping tape over the assembled 3+3 core bundle. |
| 5. Outer sheath | Red flame-retardant, UV- and oil-resistant heavy rubber compound with limiting oxygen index (LOI) above 29; OD tolerance ±5 %. |
TF-MVVFD-3G Designation and Size Code Breakdown
- TF-MVVFD-3G: TEBAOFLEX Class 5 flexible rubber symmetrical 3-phase + 3-ground MV VFD motor cable
- 3.6/6 kV or 6/10 kV: Rated phase-to-earth / phase-to-phase voltage class (11 kV or 17 kV AC factory test)
- 3x16 to 3x240: Three Class 5 finely stranded plain copper phase conductors (mm²)
- +3x16/3 to +3x120/3: Total protective-earth cross-section split equally into three interstitial bare conductors
- LOI > 29 Red Rubber: Oil- and UV-resistant flame-retardant rubber sheath passing EN/IEC 60332-3-24
TF-MVVFD-3G Medium-Voltage Converter Motor Applications
TF-MVVFD-3G is engineered for industrial and heavy-duty medium-voltage variable-speed motor drives requiring flexible routing and low transfer impedance.

- Converter-to-motor power leads on 3.3 kV, 4.16 kV, 6 kV, 6.6 kV and 10 kV industrial VFD blowers, boiler feed pumps, Banbury mixers and rolling mills.
- Skid-mounted compressors, slurry pump stations, test-bed dynamometers and vibrating machinery frames where Class 2 tape-screened cables are too stiff.
- Indoor cable trays, tight-bend motor terminal boxes (10 x OD) and outdoor UV/oil-exposed industrial plant pipe racks (-40 °C to +90 °C).
TF-MVVFD-3G vs Fixed 3GSEGCH and Mining VFD-GC Cables
| Cable family | Conductor & screen | Voltage rating | Primary installation |
|---|---|---|---|
| TF-MVVFD-3G (this page) | Class 5 Cu + per-phase tinned Cu braid + 3 split earths | 3.6/6 kV & 6/10 kV | Flexible MV VFD motor leads, vibrating skids, tight cabinets |
| 3GSEGCH / 3GSEGCY | Class 2 Cu + copper tapes + overall wire screen | 3.6/6 (conv.) / 6/10 kV | Fixed industrial trays, ducts and buried (3GSEGCY) feeders |
| Mining VFD-GC (5–15 kV) | Flexible Cu + metallic shield + 3 grounds + GC pilot | 5 kV, 8 kV, 15 kV | Portable mine VFD shovels and drills with ground-check |
| 2XSLCYK-J / 2YSLCYK-JB | Class 5 Cu + foil + tinned Cu braid | 0.6/1 kV | Low-voltage 400–690 V inverter motors |
Selection tip: many 3.3–4.16 kV multi-level drives specify 3.6/6 kV insulation while 6–6.6 kV drives or ungrounded/resonant-earthed converters specify 6/10 kV walls to accommodate reflected-wave voltage doubling.
TF-MVVFD-3G Medium-Voltage VFD Cable RFQ Checklist
- Voltage series (3.6/6 kV or 6/10 kV), converter nominal output voltage, DC-bus link voltage and switching frequency.
- Conductor and split-earth size from 3x16+3x16/3 up to 3x240+3x120/3 mm² (note both 3x35+3x16/3 and 3x35+3x25/3 options).
- Run length between VFD output cabinet and motor terminal box (to check C = 310–840 nF/km charging current).
- EMC cable gland brass cone sizing (nominal OD ±5 %) and indoor/outdoor tray grouping.
- Total meterage, cut-length schedule and target delivery (MOQ 50 m; 7 to 45 working days).
Related selection resources
- Industrial power, VFD motor and flexible rubber cable catalog
- Engineering guide: VFD cable insulation, symmetrical 3-ground geometry and shields
- Engineering guide: why flexible power cables use EPR insulation
- Engineering guide: spiral vs braided tinned-copper shields in flexing cables
- 3GSEGCH / 3GSEGCY Class 2 fixed medium-voltage VFD cable
- 5 kV to 15 kV portable mining VFD-GC drive cable
- 2XSLCYK-J 0.6/1 kV low-voltage XLPE VFD motor cable
TF-MVVFD-3G Flexible MV VFD Cable FAQ
Why does TF-MVVFD-3G use a 3+3 symmetrical layout on MV VFD motors?
3 split interstitial earth conductors arranged at 120 degrees alongside 3 individually braided phases cancel magnetic asymmetry, returning high-frequency PWM common-mode currents evenly instead of through motor bearings.
How does TF-MVVFD-3G differ from 3GSEGCH / 3GSEGCY?
Class 5 flexible copper conductors, flexible tinned-copper wire braids and a red rubber sheath (-40 °C to +90 °C) replace the rigid Class 2 conductors, copper tapes and polyolefin/PVC sheaths of fixed 3GSEGCH / 3GSEGCY cables.
Does TF-MVVFD-3G pass bunched-cable flame testing?
Yes. The red flame-retardant rubber outer sheath has a limiting oxygen index (LOI) above 29 and complies with both EN/IEC 60332-1-2 and bunched flame test EN/IEC 60332-3-24.
What size range is offered in TF-MVVFD-3G 3.6/6 kV vs 6/10 kV?
10 sizes from 3x16+3x16/3 to 3x185+3x95/3 mm² in 3.6/6 kV (11 kV test), and 11 sizes up to 3x240+3x120/3 mm² in 6/10 kV (17 kV test).
What are the MOQ and lead time for TF-MVVFD-3G?
50 m minimum order quantity with a manufacturing lead time of 7 to 45 working days.
TF-MVVFD-3G 3.6/6 kV & 6/10 kV Technical Data and Schedule
TF-MVVFD-3G Key Dielectric, EMC and Thermal Ratings
- Symmetrical 3+3 EMC layout: Three individually braided-screened EPR phases plus three interstitial bare earth conductors equalize common-mode return currents
- Class 5 flexible routing: Multi-stranded EN/IEC 60228 class 5 copper accepts 10 x OD bending into cramped MV motor and drive cabinets
- 3.6/6 kV & 6/10 kV series: 10 sizes at 3.6/6 kV (up to 185 mm²) and 11 sizes at 6/10 kV (up to 240 mm²) with published C and L data
- Bunched-flame FR rubber: Red oil-resistant rubber sheath with oxygen index above 29, tested to EN/IEC 60332-1-2 and 60332-3-24
- Project production: Custom cut lengths and gland-matched OD control from MOQ 50 m in 7 to 45 working days
| Parameter | Value |
|---|---|
| Rated voltage | 3.6/6 kV (11 kV AC test) and 6/10 kV (17 kV AC test) MV converter duty |
| Conductor and earth range | Class 5 copper 3x16+3x16/3 to 3x185+3x95/3 (3.6/6 kV) and up to 3x240+3x120/3 (6/10 kV) |
| EMC screening | Semiconductive rubber and tape plus tinned copper wire braid on each phase and 3 symmetrical earths |
| Insulation and sheath | Enhanced-parameter EPR phase dielectric and red oil-resistant FR rubber sheath (LOI above 29) |
| Temperature limits | -40 °C to +90 °C operating ambient; 90 °C max conductor; 250 °C max short-circuit (5 s) |
| Minimum bend radius | 10 x cable outer diameter (425 mm on 3.6/6 kV 3x16 up to 802 mm on 6/10 kV 3x240) |
| Supply terms | MOQ 50 m; manufacturing lead time 7 to 45 working days |
TF-MVVFD-3G 3.6/6 kV and 6/10 kV Symmetrical 3+3 Schedule
| Model, voltage and size | Rated U0/U | Nominal OD (mm) | Max. DC resistance at 20 °C (Ω/km) | Capacitance (nF/km) | Inductance (mH/km) | Current at 30 °C air (A) | Approx. weight (kg/km) | Next step |
|---|---|---|---|---|---|---|---|---|
| TF-MVVFD-3G 3.6/6 kV 3x16+3x16/3 | 3.6/6 kV | 42.5 | 1.24 | 340 | 0.39 | 109 | 2,540 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x25+3x16/3 | 3.6/6 kV | 46.0 | 0.795 | 390 | 0.37 | 141 | 3,185 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x35+3x16/3 | 3.6/6 kV | 48.2 | 0.565 | 440 | 0.34 | 174 | 3,555 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x35+3x25/3 | 3.6/6 kV | 48.2 | 0.565 | 440 | 0.34 | 174 | 3,575 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x50+3x25/3 | 3.6/6 kV | 52.6 | 0.393 | 490 | 0.33 | 215 | 4,335 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x70+3x35/3 | 3.6/6 kV | 56.5 | 0.277 | 560 | 0.31 | 266 | 5,300 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x95+3x50/3 | 3.6/6 kV | 60.2 | 0.210 | 640 | 0.30 | 318 | 6,500 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x120+3x70/3 | 3.6/6 kV | 63.8 | 0.164 | 690 | 0.29 | 367 | 7,600 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x150+3x70/3 | 3.6/6 kV | 68.7 | 0.132 | 770 | 0.28 | 418 | 8,790 | Request this size |
| TF-MVVFD-3G 3.6/6 kV 3x185+3x95/3 | 3.6/6 kV | 74.5 | 0.108 | 840 | 0.27 | 477 | 10,520 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x16+3x16/3 | 6/10 kV | 44.3 | 1.24 | 310 | 0.40 | 109 | 2,800 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x25+3x16/3 | 6/10 kV | 47.7 | 0.795 | 350 | 0.38 | 141 | 3,360 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x35+3x16/3 | 6/10 kV | 49.9 | 0.565 | 400 | 0.35 | 174 | 3,740 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x35+3x25/3 | 6/10 kV | 49.9 | 0.565 | 400 | 0.35 | 174 | 3,760 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x50+3x25/3 | 6/10 kV | 54.3 | 0.393 | 440 | 0.34 | 215 | 4,535 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x70+3x35/3 | 6/10 kV | 58.2 | 0.277 | 500 | 0.32 | 266 | 5,515 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x95+3x50/3 | 6/10 kV | 62.9 | 0.210 | 580 | 0.30 | 318 | 6,875 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x120+3x70/3 | 6/10 kV | 65.5 | 0.164 | 620 | 0.29 | 367 | 7,845 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x150+3x70/3 | 6/10 kV | 70.5 | 0.132 | 690 | 0.28 | 418 | 9,050 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x185+3x95/3 | 6/10 kV | 76.2 | 0.108 | 760 | 0.27 | 477 | 10,800 | Request this size |
| TF-MVVFD-3G 6/10 kV 3x240+3x120/3 | 6/10 kV | 80.2 | 0.0817 | 810 | 0.27 | 552 | 12,800 | Request this size |
Current-carrying capacities apply to a single cable in free air at 30 °C ambient; apply grouping and ambient derating factors for enclosed trays or multi-cable racks.
Outer diameter tolerance is ±5 %; minimum installation bend radius is 10 x nominal cable outer diameter.
ASCII part references: TF-MVVFD-3G 3.6/6 kV 3x50+3x25/3; TF-MVVFD-3G 3.6/6 kV 3x95+3x50/3; TF-MVVFD-3G 6/10 kV 3x70+3x35/3; TF-MVVFD-3G 6/10 kV 3x185+3x95/3; TF-MVVFD-3G 6/10 kV 3x240+3x120/3.
TF-MVVFD-3G Standards and Flame Test References
| Standard or specification | Application |
|---|---|
| EN / IEC 60228 | Class 5 multi-stranded flexible annealed copper conductors. |
| IEC 60502-2 (reference) | Medium-voltage EPR dielectric, semiconductive field control and 11 kV / 17 kV AC voltage test basis. |
| EN / IEC 60332-1-2 & 60332-3-24 | Single-cable and Category C bunched-cable vertical flame propagation resistance (LOI above 29). |
| EN / IEC 60811-404 | Oil resistance verification of the red elastomer outer sheath. |
Certifications and document support
TEBAOFLEX ISO quality assurance and routine factory test reports
IEC Webstore — IEC 60228 conductor, IEC 60332 flame and IEC 60811 oil test references
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
Medium Voltage VFD Motor Cable — 3GSEGCH / 3GSEGCY
A related cable option for a different application or duty profile.
View product5kV to 15kV Mining VFD, VFD-GC and VFD-BGC Drive Cable
A related cable option for a different application or duty profile.
View productMVFP and MYPTJ-JS Metallic-Shielded Mine VFD Inverter and Feeder Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.