(N)TSCGEW11Y 6/10 kV Shore Power Reeling Cable
(N)TSCGEW11Y is a 6/10 kV halogen-free shore-power reeling cable with power, pilot and optical-fibre elements.
(N)TSCGEW11Y 6/10 kV shore power reeling cable
TEBAOFLEX (N)TSCGEW11Y is a halogen-free high-voltage shore-power reeling cable for connecting a vessel to the main grid when berthed at a harbour quay. The supplied application covers high-voltage shore connection (HVSC) systems for ships at berth, including container vessels, and cable-crane or mobile-carrier systems for cruise-liner operation.
The supplied design combines three EPR-insulated main power cores, a ground conductor, screened pilot cores and a 12-fibre multimode optical-fibre element around a central support element. A double-layer thermoplastic inner sheath and TPU outer sheath support the stated reeling duty. Confirm voltage system, crane/reeling geometry, termination, tensile loading, vessel interface, fibre requirement and site approval before final selection.
- Rated voltage: 6/10 kV.
- Ambient temperature: fixed −40°C to +90°C; reeling −30°C to +90°C.
- Maximum conductor temperature: +90°C; short-circuit conductor temperature +200°C.
- Bending radius: fixed 6× cable diameter; free movement 10×; reeling 12×.
Send the required (N)TSCGEW11Y configuration, shore-power interface, length and documentation requirement for a technical quotation.
Construction
| Main cores | Finely stranded tinned copper, IEC 60228 Class 5; triple extruded insulation with inner semi-conductive stress-control layer, EPR insulation and outer semi-conductive layer |
|---|---|
| Ground conductor | Finely stranded tinned copper, IEC 60228 Class 5, semi-conductive layer |
| Pilot cores | Finely stranded tinned copper, IEC 60228 Class 5; twisted around filler, screened EPR compound, white cores with black numerals 1–8 |
| Optical fibre | 12 fibres in G62.5/125 multimode arrangement |
| Core arrangement | Main cores around central support element with ground conductor and screened pilot/optical-fibre cores in interstices |
| Double-layer sheath | Thermoplastic inner sheath and thermoplastic polyurethane TPU outer sheath to EN 50363-10-2; black or other requested colour |


Applications
(N)TSCGEW11Y is supplied for vessel-to-grid connection at harbour quays in high-voltage shore connection systems. The stated applications include ships at berth, container-vessel on-board systems and single-operator cable-crane or mobile-carrier systems for cruise liners.
Use the application-specific reeling and tensile-load data only after confirming the actual crane, cable route and shore-power system design.

Specifications
| Configuration | Outer diameter min.–max. | Approx. weight |
|---|---|---|
| 3×70 + 2×35/2 + 1×(8×2.5)C + FO | 66–69 mm | 6,505 kg/km |
| 3×95 + 2×50/2 + 1×(8×2.5)C + FO | 68–71 mm | 7,440 kg/km |
| 3×120 + 2×70/2 + 1×(8×2.5)C + FO | 71–74 mm | 8,465 kg/km |
| 3×185 + 2×95/2 + 1×(8×2.5)C + FO | 74–77 mm | 10,000 kg/km |
| AC test voltage | 21 kV |
|---|---|
| Maximum permissible AC voltage | 6.9/12 kV |
| Maximum permissible DC voltage | 9/18 kV |
| Optical-fibre attenuation | Maximum 3.5 dB/km at 850 nm; 1.5 dB/km at 1300 nm |
Standards
| Shore-power reference | IEC/ISO/IEEE 80005-1 |
|---|---|
| Current-carrying-capacity reference | DIN VDE 0298-4 |
| Oil resistance | DIN EN / IEC 60811-404 |
| Fire behaviour | DIN EN / IEC 60332-1-2 |
| Fibre standard | ITU-T G.651; colour code according to ANSI/TIA/EIA 598-A |
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
Type G Cable 2 kV Portable Mining Power Cable
A related cable option for a different application or duty profile.
View productNSHTOEU 0.6/1kV LHD Mining Reeling Cable
A related cable option for a different application or duty profile.
View productType SHD-CGC 5 kV Shielded Portable Mining Power Cable
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.