Type G-GC Cable 2000V Portable Mining Power Cable
Type G-GC cable (also written Type GGC or GGC cable) is a round 2000V portable mining power cable for mobile equipment circuits that require three phase conductors, two grounding conductors and a separate ground-check conductor.
- Voltage and sizes: 2000V; 3/C, 8 AWG through 500 kcmil
- Construction: rope-lay stranded tinned copper, 90°C EPR insulation, reinforced mold-cured black CPE jacket
- Ampacity (40°C ambient): 59 A at 8 AWG to 487 A at 500 kcmil — view sizes, OD and ampacity
- Standards and marking: manufactured to ICEA S-75-381 / NEMA WC 58; MSHA marking stated for the current construction
- Supply: MOQ 50 m, cut to length, typical lead time 7–45 working days
For an RFQ, send conductor size, length, equipment, movement pattern, reel layers, terminations and required mine documentation.
Type G-GC Cable for 2000V Mining Equipment
Type G-GC cable is a round three-conductor 2 kV portable mining power cable with two grounding conductors and a separate insulated ground-check conductor. The supplied construction uses flexible rope-lay stranded tinned-copper conductors, 90°C EPR insulation, textile reinforcement and a heavy-duty black CPE jacket. It is intended for mobile surface or underground equipment that requires grounding and protective ground-continuity monitoring.
The ground-check conductor is part of the monitoring circuit, not a substitute for the equipment grounding conductors. Confirm the protection scheme, conductor size, route length, current, termination space and movement duty before treating one portable mining cable type as interchangeable with another.
Cable schedules write this family several ways: Type G-GC, Type GGC, G-GC cable or GGC mining cable. “Ground check” and “ground-check” describe the same yellow monitoring conductor.
- Suitable for: blast-hole drills, continuous miners, cutters, loaders, shuttle cars, pumps and similar relocatable equipment.
- Choose by: 2000V circuit requirements, AWG/kcmil size, ampacity, voltage drop, overall diameter and reel conditions.
- Confirm before ordering: grounding layout, ground-check conductor, drum layers, cable length, marking and documentation.
- Use another construction when: the project specifies shielded medium-voltage cable or does not use a ground-check circuit.
Download the Type G-GC cable datasheet (PDF) or use the mining cable comparison guide before requesting a quotation.
Type G-GC Cable Construction
The supplied round Type G-GC cable combines three power conductors with two grounding conductors and one ground-check conductor. Each layer below is taken from the supplied TEBAOFLEX 2 kV datasheet; final conductor identification and marking follow the approved order drawing.

| Component | Supplied construction | Buyer relevance |
|---|---|---|
| Power conductors | Three flexible rope-lay stranded tinned-copper conductors | Provides the flexible phase-conductor system for mobile 2 kV equipment connections. |
| Insulation | Heat-, moisture- and ozone-resistant 90°C ethylene-propylene rubber (EPR) | The insulation system supports the stated conductor temperature and portable mining duty. |
| Grounding conductors | Two flexible rope-lay stranded tinned-copper grounding conductors | These conductors provide the equipment-grounding path defined by the circuit design. |
| Ground-check conductor | Flexible tinned-copper conductor with yellow polypropylene insulation | Connects to the protective ground-continuity monitoring circuit specified for the equipment. |
| Separator | Non-conductive separator tape over the cabled core assembly | Separates and binds the assembled cable core. |
| Reinforcement | Textile reinforcement embedded beneath the outer jacket | Adds mechanical support for severe trailing service. |
| Outer jacket | Heavy-duty reinforced mold-cured thermosetting chlorinated polyethylene (CPE), black | Provides the outer protection stated for abrasion, flexing, moisture, ozone and weather exposure. |
| Cable shape | Round three-conductor construction with grounding and ground-check conductors | Overall diameter and termination fit must be checked against the selected size. |
Type G-GC Cable Applications
Type G-GC cable is used for 2000V portable power circuits on mobile or relocatable mining equipment when the protection scheme requires both equipment grounding conductors and a separate ground-check conductor. The supplied datasheet names blast-hole drills, continuous miners, pumps, cutters, loading machines and shuttle cars. Suitability still depends on the route, termination system, monitoring circuit, ampacity, voltage drop and mechanical handling.

What does the ground-check conductor do?
The insulated ground-check conductor forms part of a protective monitoring circuit that checks continuity of the equipment-grounding path. If the project requires this function, the conductor, terminations and relay logic must be treated as one system. The ground-check conductor does not replace either grounding conductor, and cable selection alone does not establish the protection settings. Include the equipment electrical diagram or existing cable marking in the RFQ so the conductor functions can be matched before manufacture.
How does Type G-GC compare with other mining cables?
Type G-GC is an unshielded 2000V round portable mining cable with three power conductors, two grounding conductors and one insulated ground-check conductor. Type G is the related family without the separate ground-check conductor. Type W is a portable power cable selected by conductor count and route where no ground-check arrangement is specified. SHD-GC is the shielded family for the voltage and protection requirements stated by the project, and is not a name substitute for Type G-GC.
| Cable family | Selection difference |
|---|---|
| Type G-GC | Unshielded 2 kV portable cable with grounding conductors and a separate ground-check conductor. |
| Type G | Related portable mining family without the separate ground-check conductor; use only when the protection design permits it. |
| Type W cable | Portable power option selected by conductor count and route where a Type G-GC ground-check arrangement is not specified. |
| SHD-GC cable | Shielded mining cable family for the voltage and protection requirements stated by the project; not a name substitute for Type G-GC. |
What is the ampacity of Type G-GC cable?
The TEBAOFLEX datasheet publishes Type G-GC ampacity from 59 A for 3/C 8 AWG to 487 A for 3/C 500 kcmil, based on continuous duty at +90°C conductor temperature and +40°C ambient temperature. Reduce the published value by the reel correction factor when the cable is wound: 0.85 for one layer, 0.65 for two, 0.45 for three and 0.35 for four. These are nominal selection values; confirm derating, voltage drop and the applicable installation code for the project. For comparison with US catalogues, the table also lists the NEC Table 400.5(A)(2) reference values at +30°C ambient, 65 A to 536 A; these are code-table values, not TEBAOFLEX test results. See the size and ampacity table.
Is Type G-GC cable MSHA approved?
This construction is manufactured to ICEA S-75-381 / NEMA WC 58 and carries the MSHA marking stated for the current product construction. No MSHA approval number is published on this page; request the marking record and the mine documentation required by the project in the RFQ so the exact construction and marking can be confirmed before manufacture.
Type G-GC Cable Specifications and Ampacity
The values below reproduce the TEBAOFLEX round three-conductor 2 kV datasheet. They are nominal selection data; confirm the final drawing, applicable derating, voltage drop, reel geometry, termination dimensions and installation code before ordering.
Select a Type G-GC size
Twelve 3/C sizes from 8 AWG to 500 kcmil. Choose the size, check the overall diameter and ampacity, then send it with the required length for a quotation. Stranding, grounding conductors, ground-check size, insulation thickness and weight for every row are in the full table below.
| Size | Overall diameter in / mm | Ampacity A (40°C) | Ampacity A (30°C, NEC reference) | Full data | Next step |
|---|---|---|---|---|---|
| Type G-GC 3/C 8 AWG | 0.97 / 24.6 | 59 | 65 | View row | Request this size |
| Type G-GC 3/C 6 AWG | 1.05 / 26.7 | 79 | 87 | View row | Request this size |
| Type G-GC 3/C 4 AWG | 1.19 / 30.2 | 104 | 114 | View row | Request this size |
| Type G-GC 3/C 2 AWG | 1.34 / 34.0 | 138 | 152 | View row | Request this size |
| Type G-GC 3/C 1 AWG | 1.51 / 38.4 | 161 | 177 | View row | Request this size |
| Type G-GC 3/C 1/0 AWG | 1.65 / 41.9 | 186 | 205 | View row | Request this size |
| Type G-GC 3/C 2/0 AWG | 1.75 / 44.5 | 215 | 237 | View row | Request this size |
| Type G-GC 3/C 3/0 AWG | 1.89 / 48.0 | 249 | 274 | View row | Request this size |
| Type G-GC 3/C 4/0 AWG | 2.04 / 51.8 | 287 | 316 | View row | Request this size |
| Type G-GC 3/C 250 kcmil (250 MCM) | 2.39 / 60.7 | 320 | 352 | View row | Request this size |
| Type G-GC 3/C 350 kcmil (350 MCM) | 2.68 / 68.1 | 394 | 433 | View row | Request this size |
| Type G-GC 3/C 500 kcmil (500 MCM) | 3.03 / 77.0 | 487 | 536 | View row | Request this size |
Dimensions, Weight and Ampacity
| Size | Power strands | Grounding conductors / strands | Ground-check AWG | Insulation mil / mm | Overall diameter in / mm | Weight lb/kft / kg/km | Ampacity A, 40°C ambient (TEBAOFLEX datasheet) | Ampacity A, 30°C ambient (NEC Table 400.5(A)(2) reference) |
|---|---|---|---|---|---|---|---|---|
| Type G-GC 3/C 8 AWG | 133 | 2 × 10 AWG / 49 | 10 | 60 / 1.52 | 0.97 / 24.6 | 600 / 893 | 59 | 65 |
| Type G-GC 3/C 6 AWG | 259 | 2 × 10 AWG / 49 | 10 | 60 / 1.52 | 1.05 / 26.7 | 750 / 1116 | 79 | 87 |
| Type G-GC 3/C 4 AWG | 259 | 2 × 8 AWG / 133 | 10 | 60 / 1.52 | 1.19 / 30.2 | 1070 / 1592 | 104 | 114 |
| Type G-GC 3/C 2 AWG | 259 | 2 × 7 AWG / 133 | 10 | 60 / 1.52 | 1.34 / 34.0 | 1480 / 2202 | 138 | 152 |
| Type G-GC 3/C 1 AWG | 259 | 2 × 6 AWG / 133 | 8 | 80 / 2.03 | 1.51 / 38.4 | 1890 / 2813 | 161 | 177 |
| Type G-GC 3/C 1/0 AWG | 266 | 2 × 5 AWG / 133 | 8 | 80 / 2.03 | 1.65 / 41.9 | 2340 / 3482 | 186 | 205 |
| Type G-GC 3/C 2/0 AWG | 323 | 2 × 4 AWG / 259 | 8 | 80 / 2.03 | 1.75 / 44.5 | 2750 / 4092 | 215 | 237 |
| Type G-GC 3/C 3/0 AWG | 418 | 2 × 2 AWG / 259 | 8 | 80 / 2.03 | 1.89 / 48.0 | 3377 / 5026 | 249 | 274 |
| Type G-GC 3/C 4/0 AWG | 532 | 2 × 2 AWG / 259 | 8 | 80 / 2.03 | 2.04 / 51.8 | 3980 / 5923 | 287 | 316 |
| Type G-GC 3/C 250 kcmil (250 MCM) | 627 | 2 × 2 AWG / 259 | 6 | 95 / 2.41 | 2.39 / 60.7 | 5000 / 7441 | 320 | 352 |
| Type G-GC 3/C 350 kcmil (350 MCM) | 888 | 2 × 1/0 AWG / 266 | 6 | 95 / 2.41 | 2.68 / 68.1 | 6750 / 10046 | 394 | 433 |
| Type G-GC 3/C 500 kcmil (500 MCM) | 1221 | 2 × 2/0 AWG / 323 | 6 | 95 / 2.41 | 3.03 / 77.0 | 8900 / 13245 | 487 | 536 |
Reel Correction Factors
Apply the supplied multiplying factor to the published ampacity when the cable is wound on a reel. The actual project review must also consider reel ventilation, duty cycle and the applicable code.
| Number of wound layers | Multiplying factor |
|---|---|
| 1 | 0.85 |
| 2 | 0.65 |
| 3 | 0.45 |
| 4 | 0.35 |
Rating summary
| Parameter | Supplied value |
|---|---|
| Rated voltage | 2000V |
| Maximum conductor temperature | +90°C |
| Ambient temperature for published ampacity | +40°C |
| Power conductors | Three |
| Grounding conductors | Two |
| Ground-check conductor | One insulated conductor |
| Published phase-conductor range | 8 AWG through 500 kcmil |
Source Notes
- Metric dimensions and weights are rounded conversions of the supplied imperial values.
- The 40°C ampacity column is based on continuous duty at +90°C conductor temperature and +40°C ambient temperature per the TEBAOFLEX datasheet.
- The 30°C column reproduces NEC Table 400.5(A)(2) (90°C conductor, 30°C ambient) as published for Type G-GC by North American manufacturers. These are normative code-table values for this cable type, not a TEBAOFLEX performance statement. The 40°C values correspond, within rounding, to the 30°C values multiplied by the 0.91 ambient correction factor of NEC Table 310.15(B)(1).
- Outside-diameter tolerance: +/-0.030 in for 8-1 AWG; +/-0.040 in for 1/0-2/0 AWG.
- Outside-diameter tolerance: +/-0.050 in for 3/0-4/0 AWG; +/-0.060 in for 250-500 kcmil.
Supply and ordering
- Minimum order quantity: 50 m, for standard and custom constructions.
- Cut lengths: supplied cut to the ordered length; state the required length per drum in the RFQ.
- Typical lead time: 7–45 working days depending on size, construction and order details; the written quotation governs.
- Jacket colour: black as standard; other colours on request.
- Packing and marking: drum size, cable marking and the document package are confirmed at quotation.
Type G-GC Cable Standards
The TEBAOFLEX datasheet lists the following cable, conductor and Canadian standard references for this round three-conductor 2 kV construction. These are the standards this construction is designed and manufactured to. They are not certifications TEBAOFLEX holds for this product, and nothing in this table should be read as a UL Listing, a CSA certification or an MSHA approval.
| Reference | Relationship stated in supplied material |
|---|---|
| ICEA S-75-381 / NEMA WC 58 | Primary cable standard |
| ASTM B172 | Flexible rope-lay stranded copper conductor reference |
| ASTM B33 | Tinned soft or annealed copper conductor reference |
| CAN/CSA C22.2 No. 96 | Canadian portable power cable standard reference |
| MSHA marking | Marking stated for the current product construction; no approval number is published on this page. Request the marking record and mine documentation in the RFQ. |
| UL / CSA listing status | Not claimed for this construction. TEBAOFLEX holds UL and cUL certificates for UL 62 flexible cord (ZJCZ) and CSA C22.2 No. 49 (ZJCZ7) only; CAN/CSA C22.2 No. 96 is a design reference here, not a certification. |
Documents to define in the RFQ
- Required cable marking, mine reference and standard edition
- Final construction drawing, conductor identification and dimensional table
- Routine inspection, electrical test and third-party documentation required by the project
- Drum length, packaging, identification and delivery documentation
- Phase colour code, minimum bending radius and jacket print legend for the ordered size
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
SHD-GC Cable 2kV-25kV Mining Power Cable
A related cable option for a different application or duty profile.
View productType W Cable 600V-2000V Portable Mining Power Cable
A related cable option for a different application or duty profile.
View productFour Conductor Flat Type W Cable 600/2000V for Mining Equipment
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.