MYPTJ Monitored Medium-Voltage Mining Trailing Cable (3.6/6–8.7/10 kV)
Medium-voltage metallic-screened and pilot-monitored flexible rubber mining trailing cables (MYPTJ 3.6/6 kV, MYPTJ 6/10 kV and MYPTJ 8.7/10 kV) manufactured to MT/T 818.6-2009 for mobile underground substations, longwall power centers and high-voltage mining machinery. Features Class 5 tinned copper conductors, triple-extruded semiconductive/EPR dielectric system, composite metallic phase screens, split interstitial earth cores and a 3-core ground-continuity monitoring circuit.
MYPTJ monitored medium-voltage mining trailing cable delivers 3.6/6 kV, 6/10 kV and 8.7/10 kV feeder power to mobile flameproof substations, longwall face transformers and heavy underground mining equipment. Designed to MT/T 818.6-2009 (GB/T 12972.6), the cable integrates three metallic-screened power cores, split interstitial grounding cores and insulated ground-continuity monitoring (pilot) cores within a double-sheathed, braid-reinforced elastomer body.
Each power core is constructed from Class 5 flexible tinned copper strands, an extruded conductor semiconductive screen, +90 °C ethylene-propylene rubber (EPR) medium-voltage insulation, an extruded insulation semiconductive screen and a tinned-copper wire/synthetic-yarn composite metallic shield. The interstitial valleys house split tinned-copper earth conductors and a 3 × 2.5 mm² monitoring core group (suffix J) that continuously verifies earth-loop integrity and trips the feeder breaker on pilot open-circuit or short-circuit faults.
For coal mining operations in China, certificate holder Jiangsu Tebaoli'er Special Cable Co., Ltd. (江苏特宝利尔特种电缆有限公司) holds valid China National Mine Product Safety Mark (MA) certificates MIA230260 for MYPTJ-3.6/6 (25–150) mm², MIA230259 for MYPTJ-6/10 (25–150) mm², and MIA230261 for MYPTJ-8.7/10 (25–150) mm². These MA approvals apply to Chinese coal mines for the certified models and 25–150 mm² cross-sections.
Include the system voltage (3.6/6 kV, 6/10 kV or 8.7/10 kV), power core cross-section (25 mm² to 150 mm²), flameproof coupler type and required run length in your RFQ. TEBAOFLEX manufactures MYPTJ trailing cables from a 50 m minimum order quantity with a standard lead time of 7–45 working days.
Explore the mining and tunneling cable range for related configurations.
For lower-voltage underground coal trailing cables and open-pit medium-voltage shovel cables, compare these specifications: MYP & MYPT Screened Flexible Coal Mining Cable (0.38/0.66–1.9/3.3 kV) (for 0.38/0.66 kV to 1.9/3.3 kV screened flexible cables on underground face equipment); UGF & UGEFP High-Voltage Open-Pit Mining Trailing Cable (3.6/6–6/10 kV) (for 3.6/6 kV to 6/10 kV open-pit excavators and draglines exposed to sunlight and cold down to -40°C). Check system voltage (3.6/6 kV, 6/6 kV, or 8.7/10 kV) and ground-monitoring relay settings before ordering.
Construction
The representative construction illustrates MYPTJ 6/10 kV 3×50 + 3×16/3 + 3×2.5 mm²: three equal Class 5 tinned-copper power cores in trefoil with conductor semiconductive screen, thick +90 °C EPR insulation, insulation semiconductive screen and tinned-copper composite metallic shield, accompanied in the three outer interstitial valleys by split bare tinned-copper grounding elements and insulated monitoring pilot cores, enclosed in a light-grey inner elastomer bedding, open-weave reinforcing braid and heavy-duty red or black flame-retardant polychloroprene outer sheath.

| Component | Material and construction |
|---|---|
| Power conductors | Three Class 5 flexible rope-lay stranded tinned copper conductors complying with GB/T 3956 / IEC 60228 (25 mm² to 150 mm²). |
| Conductor & insulation screens | Extruded inner semiconductive elastomer layer over the conductor and extruded outer semiconductive elastomer layer over the EPR insulation to eliminate partial-discharge voids. |
| Medium-voltage insulation | High-dielectric-strength +90 °C ethylene-propylene rubber (EPR) with nominal wall thickness of 4.5 mm (3.6/6 kV), 5.5 mm (6/10 kV) and 6.0 mm (8.7/10 kV). |
| Metallic phase shield | Tinned-copper wire and polyester-fibre composite metallic braid/spiral shield applied over each semiconductive-screened power core. |
| Split earth & monitoring cores | Three split flexible tinned-copper grounding conductors (3×16/3 or 3×25/3 mm²) plus three EPR-insulated 2.5 mm² monitoring pilot cores (J) laid in the interstitial valleys. |
| Inner sheath & reinforcing braid | Extruded elastomeric inner sheath/bedding with open-weave synthetic reinforcing braid to resist axial tension and torsional twisting. |
| Outer jacket | Heavy-duty flame-retardant polychloroprene (PCP / XH-03A) thermosetting rubber outer sheath in red or black, resistant to abrasion, impact, mine water, oil and flame propagation. |
Applications
Select the voltage grade (3.6/6 kV, 6/10 kV or 8.7/10 kV) and conductor cross-section according to transformer feeder load, voltage drop over roadway runs and pilot-monitoring relay compatibility.

- Medium-voltage movable power feeders connecting underground main substations to mobile flameproof longwall transwitch units (KBSGZY).
- Monitored trailing feeders for 6 kV and 10 kV underground coal-mine pump stations, haulage winches and high-capacity shearer supply transformers.
- Tunneling and shaft-sinking medium-voltage mobile power distribution requiring continuous ground-check pilot monitoring.
- Roadway monorail suspension systems and motorized cable reels operating at a minimum bending radius of 12 × cable outside diameter.
When selecting medium-voltage trailing cables across MT 818 and DIN VDE 0250-813 standards, consult these resources: Medium Voltage Mining Cable Selection Guide (for engineering comparisons of semi-conductive vs metallic core screens, voltage classes, and reeling duty); (N)TSKCGEWÖU 3.6/6kV Medium Voltage Mining Trailing Cable (for VDE 3.6/6 kV heavy-duty reeling and trailing cables with anti-torsion braid). Confirm earth-continuity pilot resistance and minimum drum bend radius for your mobile substation or reel.
Specifications
| Parameter | Value |
|---|---|
| Rated voltage (U0/U) | 3.6/6 kV, 6/10 kV, 8.7/10 kV |
| Maximum continuous conductor temperature | +90 °C (+250 °C short-circuit, 5 s max.) |
| Core configuration | 3 power cores + 3 split interstitial earth cores + 3 × 2.5 mm² pilot monitoring cores |
| Power frequency AC test voltage | 11 kV / 5 min (3.6/6 kV), 16 kV / 5 min (6/10 kV), 22 kV / 5 min (8.7/10 kV) |
| Partial discharge level | ≤ 20 pC at 1.5 U0 in accordance with MT/T 818.6-2009 / GB/T 3048.12 |
| Minimum dynamic bending radius | 12 × cable outside diameter |
| China Coal Mine Safety Mark (MA) | MIA230260 (MYPTJ 3.6/6 kV, 25–150 mm²), MIA230259 (MYPTJ 6/10 kV, 25–150 mm²), MIA230261 (MYPTJ 8.7/10 kV, 25–150 mm²) held by Jiangsu Tebaoli'er Special Cable Co., Ltd. for Chinese coal mines |
| Commercial supply terms | Minimum order quantity 50 m; manufacturing lead time 7–45 working days |
| Model & voltage rating | Nominal cross-section (power + earth + pilot, mm²) | Nominal EPR insulation thickness (mm) | Nominal outside diameter min–max (mm) | Continuous ampacity at 25 °C ambient (A) | Approx. weight (kg/km) | AC test voltage / 5 min (kV) | MA certificate no. (China coal mines) |
|---|---|---|---|---|---|---|---|
| MYPTJ-3.6/6 kV | 3×25 + 3×16/3 + 3×2.5 | 4.5 | 46.8 – 51.5 | 113 | 3,120 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×35 + 3×16/3 + 3×2.5 | 4.5 | 49.4 – 54.2 | 138 | 3,640 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×50 + 3×16/3 + 3×2.5 | 4.5 | 53.2 – 58.4 | 173 | 4,390 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×70 + 3×16/3 + 3×2.5 | 4.5 | 57.6 – 63.0 | 215 | 5,420 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×95 + 3×25/3 + 3×2.5 | 4.5 | 62.4 – 68.2 | 260 | 6,680 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×120 + 3×25/3 + 3×2.5 | 4.5 | 66.2 – 72.3 | 300 | 7,860 | 11 | MIA230260 |
| MYPTJ-3.6/6 kV | 3×150 + 3×25/3 + 3×2.5 | 4.5 | 70.8 – 77.2 | 345 | 9,280 | 11 | MIA230260 |
| MYPTJ-6/10 kV | 3×25 + 3×16/3 + 3×2.5 | 5.5 | 51.2 – 56.2 | 113 | 3,580 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×35 + 3×16/3 + 3×2.5 | 5.5 | 53.8 – 59.0 | 138 | 4,140 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×50 + 3×16/3 + 3×2.5 | 5.5 | 57.6 – 63.1 | 173 | 4,920 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×70 + 3×16/3 + 3×2.5 | 5.5 | 62.0 – 67.8 | 215 | 6,010 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×95 + 3×25/3 + 3×2.5 | 5.5 | 66.8 – 73.0 | 260 | 7,310 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×120 + 3×25/3 + 3×2.5 | 5.5 | 70.6 – 77.1 | 300 | 8,540 | 16 | MIA230259 |
| MYPTJ-6/10 kV | 3×150 + 3×25/3 + 3×2.5 | 5.5 | 75.2 – 82.0 | 345 | 10,020 | 16 | MIA230259 |
| MYPTJ-8.7/10 kV | 3×25 + 3×16/3 + 3×2.5 | 6.0 | 53.6 – 58.8 | 113 | 3,860 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×35 + 3×16/3 + 3×2.5 | 6.0 | 56.2 – 61.6 | 138 | 4,430 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×50 + 3×16/3 + 3×2.5 | 6.0 | 60.0 – 65.7 | 173 | 5,240 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×70 + 3×16/3 + 3×2.5 | 6.0 | 64.4 – 70.5 | 215 | 6,350 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×95 + 3×25/3 + 3×2.5 | 6.0 | 69.2 – 75.6 | 260 | 7,680 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×120 + 3×25/3 + 3×2.5 | 6.0 | 73.0 – 79.7 | 300 | 8,950 | 22 | MIA230261 |
| MYPTJ-8.7/10 kV | 3×150 + 3×25/3 + 3×2.5 | 6.0 | 77.6 – 84.6 | 345 | 10,460 | 22 | MIA230261 |
Continuous current-carrying capacities are based on +90 °C conductor temperature at +25 °C ambient air in free underground ventilation.
Each power core undergoes routine AC voltage withstand and partial-discharge testing prior to dispatch.
MA certificates MIA230260, MIA230259 and MIA230261 are held by Jiangsu Tebaoli'er Special Cable Co., Ltd. (江苏特宝利尔特种电缆有限公司) and apply to coal mines in China for the certified 25–150 mm² cross-sections.
Standards
| Standard or specification | Application |
|---|---|
| MT/T 818.6-2009 / GB/T 12972.6 | Coal mine movable metallic-screened and monitored medium-voltage elastomeric-sheathed flexible cables (Type MYPTJ 3.6/6 kV, 6/10 kV and 8.7/10 kV). |
| GB/T 3956 / IEC 60228 | Class 5 flexible tinned copper conductors for mobile medium-voltage trailing cables. |
| MT 386 | Flame-retardant performance testing for coal mining cables. |
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
SHD-GC Cable 2kV-25kV Mining Power Cable
A related cable option for a different application or duty profile.
View productType MP-GC 15kV Mine Power Feeder Cable
A related cable option for a different application or duty profile.
View productMYP & MYPT Screened Flexible Coal Mining Cable (0.38/0.66–1.9/3.3 kV)
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.