High Temperature Cables TEBAOFLEX

KGG, KGGR, KGGP, KGGRP & KGG22/KGG32 450/750 V Silicone Rubber Control & Armoured Cable

KGG, flexible KGGR, copper-braid-screened KGGP / KGGRP, copper-tape-screened KGGP2, and steel-armoured KGG22 / KGG32 (TF-KGG-KGGR-750V) are 450/750 V metallurgical silicone rubber control cables rated from -60 °C to +180 °C. Available from 2×0.75 mm² up to 61×2.5 mm² for blast-furnace, EAF, boiler and coking-plant PLC, interlock and valve circuits.

Product information
SKU
TF-KGG-KGGR-750V
Brand
TEBAOFLEX
Product overview

KGG, Class 5 flexible KGGR, EMC-screened KGGP / KGGRP / KGGP2 and steel-armoured KGG22 / KGG32 450/750 V silicone rubber control cables safeguard multi-channel PLC I/O, limit switches, burner interlocks and hydraulic valve solenoids from -60 °C to +180 °C across 2×0.75 mm² drops up to 61×2.5 mm² marshalling trunks.

In blast-furnace hot-blast stove galleries, EAF melt shops, utility coal/biomass boilers and coking ovens, PVC control cables (KVV / KVVP) soften above +70 °C and release corrosive HCl gas, whereas European 300/500 V SiHF cables stop at 24–25 cores and lack heavy steel-tape (22) or vertical-shaft steel-wire (32) armour options. KGG-series control cables pair white-numbered high-tear silicone cores with non-hygroscopic fiberglass lappings, >= 80 % tinned-copper EMC braids or galvanized steel armour under a halogen-free silicone jacket.

Specify KGG or KGGP for fixed tray and conduit marshalling; specify KGGR or KGGRP (6× OD bend radius) on moving furnace dampers, lance carriages and vibrating screens; specify KGG22 for crush/rodent protection in hot cable trenches, or KGG32 where vertical furnace tower risers impose tensile load; for hot acid/solvent immersion up to +260 °C, switch to KFF / KFFP fluoroplastic control cable. MOQ 50 m (100 m on light unarmoured <= 10-core sizes), 7 to 45 working days.

Explore the high-temperature wire and cable range for related configurations.

Construction

KGG, KGGR, KGGP & KGG22/KGG32 450/750 V Construction

Engineered to GB/T 9330 metallurgical silicone control geometry with IEC 60228 copper conductors and 2,500 V AC 5-minute dielectric verification.

Clean 2D engineering cross-section of 19-core KGGP 450/750 V screened silicone control cable showing brick-red silicone sheath, concentric tinned-copper braid screen, fiberglass binder and 1+6+12 closely packed black silicone control cores
19-core KGGP 450/750 V cross-section: 1+6+12 concentric silicone control cores, thermal fiberglass wrap, tinned-copper braid screen and silicone outer sheath.
KGG, KGGR, KGGP, KGGRP & KGG22/KGG32 450/750 V Silicone Rubber Control & Armoured Cable construction
ComponentMaterial and construction
1. Solid/Stranded (KGG) or Class 5 Fine-Stranded Copper (KGGR)IEC 60228 Class 1 or Class 2 bare/tinned copper on fixed KGG / KGGP / KGG22 / KGG32, or Class 5 extra-flexible bare/tinned copper on KGGR and KGGRP.
2. 450/750 V Extruded Silicone Rubber Core InsulationHigh-purity silicone rubber cores clearly numbered in permanent heat-cured white digits (1, 2, 3...) or colour-coded on 2–5 core sizes.
3. Fiberglass Bedding + Optional Screen (P / P2) + Steel Armour (22 / 32)Concentric multi-layer core lay wrapped in E-glass tape; >= 80 % tinned-copper wire braid (KGGP/KGGRP), overlapped copper tape (KGGP2), double steel tape (KGG22) or fine galvanized steel wires (KGG32).
4. Halogen-Free Brick-Red or Black Silicone Rubber Outer SheathOzone-, UV- and thermal-aging-resistant silicone rubber jacket rated -60 °C to +180 °C continuous (+200 °C short-term).

KGG, KGGR, KGGP & KGG22/KGG32 Code Breakdown

  • K: Industrial control, signalling and interlock cable family (450/750 V)
  • G + G: Silicone rubber core insulation (G) + silicone rubber outer sheath (G)
  • R (in KGGR / KGGRP): Extra-flexible IEC 60228 Class 5 fine-stranded copper conductors
  • P / P2: Tinned-copper wire braid EMC screen (P) or overlapped copper-tape electrostatic screen (P2)
  • 22 / 32: Double galvanized steel-tape armour (22) or fine galvanized round steel-wire armour (32)
Applications

KGG & KGGP Blast-Furnace, EAF, Coking & Boiler Circuits

Designed for 24 V DC to 450/750 V AC control, signalling, protection-relay and actuator circuits in high-temperature industrial plants.

Brick-red KGGP and KGGR 450/750 V multi-core silicone control cables entering stainless EMC glands at the base of a blast-furnace hot-blast stove instrumentation cabinet
Hot-blast stove and furnace valve-control marshalling cabinets wired with EMC-screened KGGP and flexible KGGR 450/750 V silicone cables.
  • Blast-furnace hot-blast valve stands, tuyere stock instrumentation, top-charging bellless chute controls and torpedo-ladle track switches.
  • Electric arc furnace (EAF) and ladle furnace (LF) roof limit switches, oxy-fuel burner panels, baghouse damper actuators and fume-hood sensors.
  • Thermal power-plant boiler sootblower control loops, steam-turbine bypass valve cabinets, rotary kiln burner BMS wiring and glass-tank batch chargers.
  • Export EPC metallurgical, cement and chemical projects specifying KGG, KGGR, KGGP, KGGRP, KGGP2, KGG22 or KGG32 on design-institute schedules.

KGG / KGG22 (450/750 V) vs SiHF / SiHFC vs KFF / KFFP

KGG / KGGR / KGGP / KGG22 (450/750 V) vs SiHF / SiHF-C-Si (300/500 V) vs KFF / KFFP Fluoroplastic
Control FamilyVoltage & Max CoresShield / Armour & TempBest Engineering Fit
KGG / KGGR / KGGP / KGG22 / KGG32 (this page)450/750 V; 2 to 61 cores-60 to +180 °C silicone; Cu braid, Cu tape, STA (22) or SWA (32)Heavy metallurgical/power-plant 450/750 V trunks, trenches & vertical shafts
SiHF & SiHFC / SiHF-C-Si300/500 V; 2 to 25 cores-60 to +180 °C EN 50525-2-83 Class 5 tinned Cu (unscreened or Cu braid)Compact European 24 V DC / 230 V AC machine and oven control drops
SiHF-P (GSWB Braided)300/500 V; 2 to 24 cores-60 to +180 °C silicone + external galvanized steel wire braidFlexible external abrasion guard on dry 300/500 V machine drops
KFF / KFFP / KFFP2-22450/750 V; 2 to 37 cores-60 to +200/+260 °C FEP or PFA + Cu screen / steel-tape armourHot acid mist, hydraulic ester oil, solvent immersion or +200 to +260 °C zones

Need individual pair shields for 4–20 mA analog transmitters or RS-485 signals in hot zones? Specify DJGPGP (silicone computer cable) or DJFPFP (+200/+260 °C fluoroplastic computer cable) on your RFQ.

KGG, KGGR, KGGP & KGG22/KGG32 Control Cable RFQ Checklist

  • Exact sub-model (KGG, KGGR, KGGP, KGGRP, KGGP2, KGG22 or KGG32) and core count × cross-section (0.75 to 6.0 mm²).
  • Conductor class and finish: Class 1/2 fixed vs Class 5 flexible, bare vs tinned copper.
  • Flame-retardant category if required (standard IEC 60332-1-2 or bunched tray ZRC / ZRB / ZRA per IEC 60332-3).
  • Total project meterage and drum cut schedule (MOQ 50 m on >= 12C / screened / armoured, 100 m on light <= 10C; 7 to 45 working days).

Related selection resources

KGG, KGGR, KGGP & KGG22/KGG32 Control Cable FAQ

How does 450/750 V KGG / KGGR differ from 300/500 V SiHF silicone control cable?

KGG and KGGR carry a thicker 450/750 V silicone insulation wall (tested at 2,500 V AC vs 2,000 V AC on SiHF), scale up to 61 control cores per trunk, and offer heavy double steel-tape armour (KGG22) and vertical-shaft fine steel-wire armour (KGG32) not covered by EN 50525-2-83 SiHF.

When should I specify KGG22 steel-tape armour versus KGG32 fine steel-wire armour?

Specify KGG22 for horizontal cable trenches, furnace catwalks and floor ducts requiring radial crush and rodent protection; specify KGG32 whenever the cable hangs in a vertical blast-furnace shaft, boiler tower or long pull duct because helical steel wires carry longitudinal tensile load that steel tape cannot.

Should I choose KGGP / KGGRP copper braid or KGGP2 copper tape screening?

Choose KGGRP or KGGP (>= 80 % tinned-copper wire braid) whenever the cable flexes, vibrates or requires low high-frequency transfer impedance against VFD and EAF arc noise; choose KGGP2 overlapped copper tape only on strictly fixed runs.

When should I switch from KGG silicone control cable to KFF / KFFP fluoroplastic control cable?

Switch to KFF or KFFP when continuous ambient temperature exceeds +180 °C (up to +260 °C on PFA) or when cables contact pressurized synthetic hydraulic oils, concentrated pickling acids or aromatic solvents that swell silicone rubber.

What is the minimum order quantity and delivery lead time for KGG-series cables?

50 m per specification on 12-core through 61-core, screened or armoured constructions (100 m on 2-core to 10-core unscreened sizes), delivered in 7 to 45 working days.

Specifications

KGG, KGGR, KGGP, KGG22 & KGG32 Dimensional Schedule

KGG & KGGR 450/750 V Core Range, Armour & Drum Summary

  • 450/750 V & up to 61 control cores: Higher 450/750 V insulation rating (2,500 V AC test) and high-density 2-core to 61-core trunking beyond 300/500 V European SiHF control cables
  • Fixed Class 1/2 or Class 5 flex: KGG / KGGP for rigid terminal-block termination in furnace galleries, or KGGR / KGGRP with IEC 60228 Class 5 fine copper for vibrating damper actuators
  • EMC braid or copper-tape shields: KGGP and KGGRP (>= 80 % tinned-copper braid) or KGGP2 (helical copper tape) block thyristor rectifier, EAF arc and VFD switching interference
  • KGG22 tape & KGG32 wire armour: Double galvanized steel tape (KGG22) for horizontal hot trenches, or fine galvanized steel wire armour (KGG32) for vertical furnace shafts and tension pulls
  • 50 m / 100 m factory drums: Supplied in 100 m drums on light 2–10 core builds and 50 m drums on >= 12-core, screened or armoured trunks in 7 to 45 working days
KGG, KGGR, KGGP, KGGRP & KGG22/KGG32 450/750 V Silicone Rubber Control & Armoured Cable technical data
ParameterValue
Rated voltage450/750 V AC with 2500 V AC 5-minute routine dielectric withstand test between cores and screen
Core count and cross-sections2, 3, 4, 5, 7, 8, 10, 12, 14, 16, 19, 24, 27, 30, 37, 44, 48, 52 and 61 cores in 0.75, 1.0, 1.5, 2.5, 4.0 and 6.0 mm2
Screening and armouring optionsUnscreened (KGG, KGGR), tinned-copper braid (KGGP, KGGRP), copper tape (KGGP2), steel-tape armoured (KGG22) and fine steel-wire armoured (KGG32)
Operating temperature and bend radius-60 C to +180 C continuous; minimum bend radius 6x OD (unarmoured KGG and KGGR), 10x OD (screened KGGP and KGGP2) and 12x OD (armoured KGG22 and KGG32)
Minimum order and lead time50 m on 12-core and above, screened or armoured builds (100 m on 2 to 10 core unarmoured sizes); 7 to 45 working days
Insulation resistanceAt least 100 MOhm*km at +20 C and at least 12 MOhm*km at +70 C hot-state verification
Halogen-free fire safetyHalogen-free per IEC 60754-1, low smoke acidity per IEC 60754-2 and flame-retardant per IEC 60332-1-2

KGG & KGGR 450/750 V Unscreened Silicone Control Schedule

KGG (Class 1/2 Fixed) & KGGR (Class 5 Flexible) 450/750 V Unscreened Silicone Rubber Control Cable — Dimensional Schedule
Model & Core × mm²Conductor Class (KGG / KGGR)Max. R at 20 °C Class 5 (Ω/km)Nom. OD KGG / KGGR (mm)Min. Bend RadiusApprox. Weight (kg/km)Drum MOQNext step
KGGR 3×0.75 mm²Class 1/2 or Class 526.08.0 / 8.46× OD86100 mRequest this size
KGGR 4×1.0 mm²Class 1/2 or Class 519.59.2 / 9.76× OD118100 mRequest this size
KGGR 4×1.5 mm²Class 1/2 or Class 513.310.2 / 10.86× OD152100 mRequest this size
KGGR 5×1.5 mm²Class 1/2 or Class 513.311.2 / 11.86× OD184100 mRequest this size
KGGR 7×1.5 mm²Class 1/2 or Class 513.312.4 / 13.16× OD238100 mRequest this size
KGGR 10×1.5 mm²Class 1/2 or Class 513.315.6 / 16.46× OD345100 mRequest this size
KGGR 12×1.5 mm²Class 1/2 or Class 513.316.2 / 17.06× OD39850 mRequest this size
KGGR 14×1.5 mm²Class 1/2 or Class 513.317.1 / 18.06× OD45250 mRequest this size
KGGR 19×1.5 mm²Class 1/2 or Class 513.319.2 / 20.26× OD59550 mRequest this size
KGGR 24×1.5 mm²Class 1/2 or Class 513.322.4 / 23.56× OD75550 mRequest this size
KGGR 37×1.5 mm²Class 1/2 or Class 513.326.2 / 27.66× OD1,11050 mRequest this size
KGG 10×2.5 mm²Class 1/2 or Class 57.9818.8 / 19.66× OD51550 mRequest this size
KGG 61×0.75 mm²Class 1/2 Fixed24.527.0 / —6× OD1,02050 mRequest this size

KGGP, KGGRP, KGGP2, KGG22 & KGG32 Screened & Armoured Schedule

KGGP / KGGRP (Copper-Braid Screened), KGGP2 (Copper-Tape Screened) & KGG22 / KGG32 (Steel-Armoured) 450/750 V Control Schedule
Model & Core × mm²Screen / Armour ConstructionNom. OD (mm)Min. Bend RadiusApprox. Weight (kg/km)Primary Furnace DutyDrum MOQNext step
KGGP 4×1.5 mm²>=80% Tinned Cu Braid11.810× OD198Burner / valve EMC feedback100 mRequest this size
KGGRP 7×1.5 mm²Class 5 + Tinned Cu Braid14.810× OD312Mobile actuator EMC control50 mRequest this size
KGGRP 12×1.5 mm²Class 5 + Tinned Cu Braid18.610× OD495EAF / LF hydraulic rack I/O50 mRequest this size
KGGP 19×1.5 mm²>=80% Tinned Cu Braid21.010× OD695Hot-blast stove PLC trunk50 mRequest this size
KGGP 24×1.0 mm²>=80% Tinned Cu Braid20.810× OD610Multi-channel interlock trunk50 mRequest this size
KGGP2 14×1.5 mm²Helical Copper Tape Screen18.512× OD535Fixed cabinet electrostatic shield50 mRequest this size
KGG22 7×1.5 mm²Double Galv. Steel Tape16.812× OD430Hot cable trench / catwalk50 mRequest this size
KGG22 12×1.5 mm²Double Galv. Steel Tape20.412× OD645Crush-resistant kiln gallery50 mRequest this size
KGG22 19×1.5 mm²Double Galv. Steel Tape23.212× OD885Blast-furnace marshalling trench50 mRequest this size
KGG22 37×1.5 mm²Double Galv. Steel Tape29.812× OD1,460Main hot-zone control trunk50 mRequest this size
KGG32 12×1.5 mm²Fine Galv. Steel Wire Armour22.612× OD790Vertical furnace tower riser50 mRequest this size

All KGG-series sizes are available with tinned copper conductors (-Sn) at +180 °C for anti-oxidation terminal reliability, and in flame-retardant ZR-KGG / ZRC-KGGP bunched-tray grades (IEC 60332-3-24). Final OD and weight are confirmed on the quotation drawing.

ASCII part references for BOM and ERP entry: TF-KGG-7X1.5, TF-KGG-12X1.5, TF-KGGR-12X1.5, TF-KGGR-19X1.5, TF-KGGP-12X1.5, TF-KGGRP-12X1.5, TF-KGGP2-14X1.5, TF-KGG22-12X1.5, TF-KGG22-19X1.5, TF-KGG32-12X1.5.

Standards

KGG & KGGR Reference Standards (GB/T 9330 & IEC 60228)

KGG, KGGR, KGGP, KGGRP & KGG22/KGG32 450/750 V Silicone Rubber Control & Armoured Cable standards and test references
Standard or specificationApplication
GB/T 9330 & TICW Metallurgical Control Cable Reference450/750 V insulation wall thickness, core numbering, 2,500 V AC voltage test and 22 / 32 steel armouring dimensions.
IEC 60228 Class 1, Class 2 & Class 5Solid, stranded and extra-flexible annealed bare or tinned copper conductor DC resistance limits.
IEC 60332-1-2, IEC 60332-3-24 & IEC 60754Vertical flame retardance (ZR / ZRC bunched tray option) and zero-halogen low-corrosivity smoke compliance.

Certifications and document support

TEBAOFLEX ISO 9001 quality management and 2.5 kV control cable routine testing

IEC 60228 — Conductors of insulated cables (Class 1, Class 2 & Class 5)

IEC 60332-1-2 — Flame propagation testing of insulated control cables

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    MOQ 50 m · Engineering reply within 24 hours

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.

    Email or WhatsApp is enough. Please include the key cable or application details for review.