(N)TSCGEWÖU / (N)TSCGEWOEU 3.6/6–12/20 kV Mine Distribution Cable
(N)TSCGEWÖU (also written (N)TSCGEWOEU, (N)TSCGEWOU or NTSCGEWÖU) is a flexible 3-core plus earth medium-voltage rubber mine distribution cable engineered to VDE 0250 Part 813 across 3.6/6 kV, 6/10 kV, 8.7/15 kV and 12/20 kV (11 to 29 kV AC test) in sizes 25 to 185 mm², combining Class 5 tinned-copper conductors, dual semiconductive field screens, rubber inner/outer sheaths and a polyester anti-torsion braid for semi-mobile routes up to 20 m/min and ±25°/m torsion.
(N)TSCGEWÖU (transliterated internationally as (N)TSCGEWOEU, (N)TSCGEWOU or NTSCGEWOU) is a flexible 3-phase plus earth medium-voltage rubber power cable built with reference to VDE 0250 Part 813 across four standard voltage classes—3.6/6 kV, 6/10 kV, 8.7/15 kV and 12/20 kV—covering 25 mm² through 185 mm² phase cross-sections for mine distribution and semi-mobile material-handling feeders.
Standard armoured mine roadway cables crack when repeatedly relocated alongside advancing conveyors or skid substations, yet purchasing a high-speed motorized drum-reeling cable adds unnecessary cost on static or low-speed routes. (N)TSCGEWÖU bridges that gap with IEC 60228 Class 5 tinned-copper phase and earth conductors, inner and outer semiconductive rubber stress-control screens, a semiconductive-on-polyester central profile filler, a vulcanised rubber inner sheath, an embedded polyester anti-torsion braid and an oil- and flame-retardant (IEC/EN 60332-1-2) heavy-duty rubber outer sheath rated up to 20 m/min travel speed and ±25°/m torsion.
Respect dynamic duty boundaries when specifying: use this (N)TSCGEWÖU distribution build for mine feeders, overland conveyors and semi-fixed equipment relocations (fixed bend radius 6 x OD); step up to dedicated R-(N)TSCGEWÖU for continuous motorized drum reeling or TBM advance, F-(N)TSCGEWÖU for festoon loops, or single-core NTMCGCWÖU for tight switchgear jumpers. Minimum order quantity is 50 m with a 7 to 45 working days lead time.
Explore the mining and tunneling cable range for related configurations.
(N)TSCGEWÖU Semiconductive Field-Controlled & Anti-Torsion Construction
The horizontal sample illustrates a 3-core + split-earth medium-voltage (N)TSCGEWÖU distribution cable: three IEC 60228 Class 5 tinned-copper phase cores with semiconductive tape, rubber dielectric and semiconductive outer screens laid with Class 5 tinned-copper earth conductors around a semiconductive-polyester central filler, enclosed by a rubber inner sheath, open-weave polyester anti-torsion braid and a red heavy-duty rubber outer jacket.

| Component | Material and construction |
|---|---|
| 1. Phase Conductors (3x) | Flexible fine-stranded tinned copper, Class 5 to VDE 0295 / IEC 60228 / EN 60228 (25 to 185 mm²). |
| 2. Conductor Screen | Semiconductive tape and inner semiconductive rubber layer smoothing electric-field stress at the conductor surface. |
| 3. Medium-Voltage Insulation | Ozone- and heat-resistant rubber dielectric compound to VDE 0207 Part 20 sized to 3.6/6, 6/10, 8.7/15 or 12/20 kV. |
| 4. Insulation Screen | Outer semiconductive rubber layer establishing radial electric-field containment across every phase core. |
| 5. Protective Earth Conductor | Class 5 flexible tinned-copper earth conductor(s) arranged in the outer interstices for continuous fault-path earthing. |
| 6. Central Support Filler | Semiconductive compound extruded over a textile polyester support maintaining circular core geometry under bending. |
| 7. Inner Sheath | Vulcanised rubber inner bedding compound protecting the laid-up MV core assembly. |
| 8. Anti-Torsion Reinforcement | Embedded polyester braid limiting axial twist to within ±25°/m during route handling and equipment repositioning. |
| 9. Heavy-Duty Outer Sheath | Abrasion-, oil- (IEC 60811-2-1) and flame-retardant (IEC/EN 60332-1-2) rubber outer sheath to VDE 0207 Part 21 (red or black per order drawing). |
(N)TSCGEWÖU / (N)TSCGEWOEU Designation Breakdown
- (N)T: flexible trailing and movable distribution cable built with reference to VDE 0250-813
- S: heavy-duty mining and industrial mechanical duty class
- CGE: semiconductive elastomer inner/outer electric-field control layers over individual MV phase cores
- WÖU (WOEU / WOU): oil-resistant, flame-retardant heavy-duty rubber sheath system reinforced with polyester anti-torsion braid
(N)TSCGEWÖU Mine Distribution Applications & Movement Boundaries
Specify (N)TSCGEWÖU across surface open-pit and underground mine MV power networks where semi-flexible routing, periodic relocation and radial field screening are required within a 20 m/min speed envelope.

- 3.6/6 kV to 12/20 kV mine power distribution feeders linking portal substations, skid-mounted transformers and section switchhouses.
- Overland belt-conveyor drive stations, crusher skids, stacker transfer houses and semi-mobile material-handling routes.
- Low-speed mobile or periodically repositioned mining machinery operating within 20 m/min travel speed and ±25°/m torsional stress.
- Cold-climate surface pit distribution (-40 °C to +80 °C static; -25 °C to +80 °C mobile) requiring flexible Class 5 tinned-copper terminations.
(N)TSCGEWÖU vs R-(N)TSCGEWÖU Reeling, F-(N)TSCGEWÖU & Single-Core MV
| Model Family | Voltage Span | Dynamic Duty Boundary | Target Mining / Industrial Route |
|---|---|---|---|
| (N)TSCGEWÖU (this page) | 3.6/6 to 12/20 kV | Semi-mobile distribution up to 20 m/min & ±25°/m; 6xOD fixed | Mine MV feeders, conveyor drives & skid-substation interconnects |
| R-(N)TSCGEWÖU | 3.6/6 to 18/30 kV | Dedicated continuous motorized drum reeling & TBM advance | Stacker-reclaimers, TBM reels, electric shovels & crane drums |
| F-(N)TSCGEWÖU | 3.6/6 to 18/30 kV | Cyclic festoon trolley loops & conveyor catenary suspension | Overhead MV festoon beams & long-travel conveyor bridges |
| NTMCGCWÖU (Single-Core) | 3.6/6 to 18/30 kV | Flexible single-core phase tails in non-magnetic cleats | Compact MV switchgear bays & mobile transformer jumpers |
| KGE / KGESh / KGETSh | 1.14 to 6 kV | GOST cold-climate (-50 °C) excavator trailing service | Open-pit rope shovels, walking draglines & rotary drills |
Outer diameter, finished cable mass and current rating vary strongly across the 3.6/6, 6/10, 8.7/15 and 12/20 kV insulation wall thicknesses and are issued on the quotation datasheet for your exact voltage class.
(N)TSCGEWÖU 3.6/6–12/20 kV Mine Feeder RFQ Checklist
- System rated voltage U0/U (3.6/6 kV, 6/10 kV, 8.7/15 kV or 12/20 kV) and phase cross-section (25 to 185 mm²).
- Earth-conductor split arrangement (e.g., 3x split interstitial earth vs 2+1 earth/pilot check) and sheath colour (red or black).
- Route kinematics: confirm static tray/ground laying vs periodic relocation within 20 m/min and ±25°/m (specify R-(N)TSCGEWÖU if drum-reeled).
- Load current (A), three-phase fault current/clearing time, route length (m) for voltage-drop check, and maximum ambient temperature (10 to 80 °C).
- Ordered drum cut lengths (MOQ 50 m; manufacturing lead time 7 to 45 working days) and required AC test report scope.
Related selection resources
- Mining and tunneling cable engineering solutions
- R-(N)TSCGEWÖU 3.6/6–18/30 kV Continuous Motorized Reeling Cable
- F-(N)TSCGEWÖU 3.6/6–18/30 kV Festoon & Conveyor Medium-Voltage Cable
- NTMCGCWÖU 3.6/6–18/30 kV Single-Core Medium-Voltage Substation Cable
- KGE, KGESh & KGETSh 1.14–6 kV Cold-Climate GOST Excavator Cable
(N)TSCGEWÖU Mine Distribution Cable Frequently Asked Questions
Can standard (N)TSCGEWÖU mine distribution cable be used on continuous motorized reeling drums?
No—this (N)TSCGEWÖU mine-distribution build is bounded at 20 m/min working speed, ±25°/m torsional stress and 6 x OD fixed bending radius for semi-mobile feeders and equipment relocation; for continuous motorized drum reeling or tunnel-boring machine (TBM) advance, specify dedicated R-(N)TSCGEWÖU.
What voltage classes and factory AC test voltages apply to (N)TSCGEWÖU?
Four VDE 0250 Part 813 voltage classes are covered: 3.6/6 kV (11 kV AC test), 6/10 kV (17 kV AC test), 8.7/15 kV (24 kV AC test) and 12/20 kV (29 kV AC test).
Why are outer diameter and weight confirmed per quotation drawing on this (N)TSCGEWÖU page?
Because a single conductor size such as 3x95 mm² carries substantially thicker MV rubber insulation and screen walls at 12/20 kV than at 3.6/6 kV; issuing the exact OD, kg/km weight and ampacity on the order datasheet prevents MV gland or coupler sizing errors.
How much does high ambient temperature reduce (N)TSCGEWÖU current capacity?
Relative to 1.00 at 30 °C ambient, the current de-rating factor is 1.15 at 10 °C, 0.91 at 40 °C, 0.82 at 50 °C, 0.71 at 60 °C and 0.41 at 80 °C.
What minimum order quantity and delivery lead time apply to (N)TSCGEWÖU cables?
50 m minimum order quantity (MOQ), with a 7 to 45 working days factory manufacturing lead time shipped on export wooden drums.
(N)TSCGEWÖU (25–185 mm²) Voltage-Drop, Resistance & De-Rating Tables
(N)TSCGEWÖU 3.6/6–12/20 kV Key Electrical & Mechanical Summary
- Voltage & test classes: U0/U 3.6/6 kV (11 kV test), 6/10 kV (17 kV test), 8.7/15 kV (24 kV test) and 12/20 kV (29 kV test) per VDE 0250-813
- MV field control: IEC 60228 Class 5 tinned-copper phase cores with semiconductive conductor/insulation screens and Class 5 earth continuity
- Anti-torsion jacket: Stabilised semiconductive-textile central filler, rubber inner sheath, polyester anti-torsion braid and heavy-duty rubber outer sheath
- Movement boundary: Up to 20 m/min working travel speed, ±25°/m max torsional stress, and 6 x OD fixed minimum bending radius
- Thermal envelope: -40 °C to +80 °C static installation, -25 °C to +80 °C mobile service, and +250 °C short-circuit conductor limit
| Parameter | Value |
|---|---|
| Rated voltage | 3.6/6 kV (11 kV test), 6/10 kV (17 kV test), 8.7/15 kV (24 kV test) and 12/20 kV (29 kV test) |
| Conductor and earth build | IEC 60228 Class 5 tinned-copper phase cores (25 to 185 mm²) + Class 5 tinned-copper protective earth |
| Field control and braid | Inner/outer semiconductive rubber screens + semiconductive/polyester central filler + polyester anti-torsion braid |
| Dynamic and bending limits | Max working speed 20 m/min; max torsional stress ±25°/m; fixed minimum bending radius 6 x overall diameter |
| Thermal operating envelope | -40 °C to +80 °C static installation; -25 °C to +80 °C mobile operation; +250 °C max short-circuit conductor temperature |
| Commercial and drawing basis | MOQ 50 m; 7 to 45 working days lead time; exact outer diameter, weight and ampacity confirmed on order datasheet per voltage class |
(N)TSCGEWÖU (25–185 mm²) Resistance & Three-Phase Voltage-Drop Schedule
| Model & Phase Size (mm²) | Max DC Resistance at 20 °C (Ω/km) | Voltage Drop PF 0.7 (V/A·km) | Voltage Drop PF 0.8 (V/A·km) | Voltage Drop PF 0.9 (V/A·km) | Voltage Drop PF 1.0 (V/A·km) | OD & Weight (mm / kg/km) | Next step |
|---|---|---|---|---|---|---|---|
| (N)TSCGEWÖU 3×25 mm² | 0.795 | 1.29 | 1.45 | 1.60 | 1.71 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×35 mm² | 0.565 | 0.95 | 1.06 | 1.16 | 1.23 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×50 mm² | 0.393 | 0.69 | 0.77 | 0.83 | 0.87 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×70 mm² | 0.277 | 0.51 | 0.56 | 0.60 | 0.61 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×95 mm² | 0.210 | 0.41 | 0.45 | 0.47 | 0.47 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×120 mm² | 0.164 | 0.34 | 0.36 | 0.38 | 0.36 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×150 mm² | 0.132 | 0.29 | 0.31 | 0.32 | 0.29 | Per voltage class order datasheet | Request this size |
| (N)TSCGEWÖU 3×185 mm² | 0.108 | 0.25 | 0.27 | 0.27 | 0.24 | Per voltage class order datasheet | Request this size |
(N)TSCGEWÖU Voltage Classes, Test Voltages & Ambient De-Rating Factors
| Parameter / Ambient Band | 3.6/6 kV | 10–25 °C | 6/10 kV | 30–45 °C | 8.7/15 kV | 50–65 °C | 12/20 kV | 70–80 °C |
|---|---|---|---|---|
| Routine AC test voltage (VDE 0250-813) | 11 kV AC | 17 kV AC | 24 kV AC | 29 kV AC |
| Ambient temperature step (°C) | 10 / 15 / 20 / 25 °C | 30 / 35 / 40 / 45 °C | 50 / 55 / 60 / 65 °C | 70 / 75 / 80 °C |
| Current de-rating factor | 1.15 / 1.12 / 1.08 / 1.04 | 1.00 / 0.96 / 0.91 / 0.87 | 0.82 / 0.76 / 0.71 / 0.65 | 0.58 / 0.50 / 0.41 |
ASCII part references: (N)TSCGEWOU / NTSCGEWOEU 3.6/6kV, 6/10kV, 8.7/15kV, 12/20kV in 3x25, 3x35, 3x50, 3x70, 3x95, 3x120, 3x150 and 3x185 mm2.
(N)TSCGEWÖU VDE 0250-813 & IEC Reference Standards
| Standard or specification | Application |
|---|---|
| Cable design standard | VDE 0250 Part 813 (flexible medium-voltage rubber trailing and distribution cables) |
| Conductor standards | VDE 0295, IEC 60228 and EN 60228 Class 5 flexible tinned copper |
| Insulation and sheath compounds | VDE 0207 Part 20 (MV rubber dielectric) and VDE 0207 Part 21 (heavy-duty rubber sheath) |
| Application & installation guide | VDE 0298 Part 3 mechanical routing, bending and dynamic movement guidance |
| Oil and flame test references | IEC 60811-2-1 oil resistance; IEC/EN 60332-1-2 vertical single-cable flame retardancy |
Certifications and document support
Review TEBAOFLEX ISO 9001 quality management and VDE 0250 voluntary VoC documentation
DIN Media — DIN VDE 0250-813 Medium-Voltage Flexible Rubber Mining Cables
Related cable options
Compare these cable options by service combination, movement, load, voltage and transmission requirement.
NTMCGCWÖU / NTMCGCWOEU Single-Core Medium-Voltage Cable (3.6/6–18/30 kV)
A related cable option for a different application or duty profile.
View productNTMCWOEU / NTMCWÖU 26/45 kV Zero-Halogen & 10/20 kV Switchgear Cable
A related cable option for a different application or duty profile.
View product35-CHVU 20/35 kV Open-Pit Mining Trailing Cable (3×50–3×95 mm²)
A related cable option for a different application or duty profile.
View productRequest a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.