MINING & TUNNELING CABLES TEBAOFLEX

(N)TSCGEWÖU / (N)TSCGEWOEU 3.6/6–12/20 kV Mine Distribution Cable

(N)TSCGEWÖU (also written (N)TSCGEWOEU, (N)TSCGEWOU or NTSCGEWÖU) is a flexible 3-core plus earth medium-voltage rubber mine distribution cable engineered to VDE 0250 Part 813 across 3.6/6 kV, 6/10 kV, 8.7/15 kV and 12/20 kV (11 to 29 kV AC test) in sizes 25 to 185 mm², combining Class 5 tinned-copper conductors, dual semiconductive field screens, rubber inner/outer sheaths and a polyester anti-torsion braid for semi-mobile routes up to 20 m/min and ±25°/m torsion.

Product information
SKU
TF-NTSCGEW-U
Brand
TEBAOFLEX
Product overview

(N)TSCGEWÖU (transliterated internationally as (N)TSCGEWOEU, (N)TSCGEWOU or NTSCGEWOU) is a flexible 3-phase plus earth medium-voltage rubber power cable built with reference to VDE 0250 Part 813 across four standard voltage classes—3.6/6 kV, 6/10 kV, 8.7/15 kV and 12/20 kV—covering 25 mm² through 185 mm² phase cross-sections for mine distribution and semi-mobile material-handling feeders.

Standard armoured mine roadway cables crack when repeatedly relocated alongside advancing conveyors or skid substations, yet purchasing a high-speed motorized drum-reeling cable adds unnecessary cost on static or low-speed routes. (N)TSCGEWÖU bridges that gap with IEC 60228 Class 5 tinned-copper phase and earth conductors, inner and outer semiconductive rubber stress-control screens, a semiconductive-on-polyester central profile filler, a vulcanised rubber inner sheath, an embedded polyester anti-torsion braid and an oil- and flame-retardant (IEC/EN 60332-1-2) heavy-duty rubber outer sheath rated up to 20 m/min travel speed and ±25°/m torsion.

Respect dynamic duty boundaries when specifying: use this (N)TSCGEWÖU distribution build for mine feeders, overland conveyors and semi-fixed equipment relocations (fixed bend radius 6 x OD); step up to dedicated R-(N)TSCGEWÖU for continuous motorized drum reeling or TBM advance, F-(N)TSCGEWÖU for festoon loops, or single-core NTMCGCWÖU for tight switchgear jumpers. Minimum order quantity is 50 m with a 7 to 45 working days lead time.

Explore the mining and tunneling cable range for related configurations.

Construction

(N)TSCGEWÖU Semiconductive Field-Controlled & Anti-Torsion Construction

The horizontal sample illustrates a 3-core + split-earth medium-voltage (N)TSCGEWÖU distribution cable: three IEC 60228 Class 5 tinned-copper phase cores with semiconductive tape, rubber dielectric and semiconductive outer screens laid with Class 5 tinned-copper earth conductors around a semiconductive-polyester central filler, enclosed by a rubber inner sheath, open-weave polyester anti-torsion braid and a red heavy-duty rubber outer jacket.

2D axial cross-section of (N)TSCGEWÖU medium-voltage mine distribution cable showing three large Class 5 tinned-copper phase cores with inner and outer black semiconductive layers, three split interstitial tinned-copper earth cores, semiconductive-textile central filler, rubber inner sheath, polyester anti-torsion braid ring and red heavy-duty rubber outer jacket
Radial MV field-control geometry of (N)TSCGEWÖU: dual semiconductive layers + stabilised central filler maintain dielectric integrity across 3.6/6 to 12/20 kV.
(N)TSCGEWÖU / (N)TSCGEWOEU 3.6/6–12/20 kV Mine Distribution Cable construction
ComponentMaterial and construction
1. Phase Conductors (3x)Flexible fine-stranded tinned copper, Class 5 to VDE 0295 / IEC 60228 / EN 60228 (25 to 185 mm²).
2. Conductor ScreenSemiconductive tape and inner semiconductive rubber layer smoothing electric-field stress at the conductor surface.
3. Medium-Voltage InsulationOzone- and heat-resistant rubber dielectric compound to VDE 0207 Part 20 sized to 3.6/6, 6/10, 8.7/15 or 12/20 kV.
4. Insulation ScreenOuter semiconductive rubber layer establishing radial electric-field containment across every phase core.
5. Protective Earth ConductorClass 5 flexible tinned-copper earth conductor(s) arranged in the outer interstices for continuous fault-path earthing.
6. Central Support FillerSemiconductive compound extruded over a textile polyester support maintaining circular core geometry under bending.
7. Inner SheathVulcanised rubber inner bedding compound protecting the laid-up MV core assembly.
8. Anti-Torsion ReinforcementEmbedded polyester braid limiting axial twist to within ±25°/m during route handling and equipment repositioning.
9. Heavy-Duty Outer SheathAbrasion-, oil- (IEC 60811-2-1) and flame-retardant (IEC/EN 60332-1-2) rubber outer sheath to VDE 0207 Part 21 (red or black per order drawing).

(N)TSCGEWÖU / (N)TSCGEWOEU Designation Breakdown

  • (N)T: flexible trailing and movable distribution cable built with reference to VDE 0250-813
  • S: heavy-duty mining and industrial mechanical duty class
  • CGE: semiconductive elastomer inner/outer electric-field control layers over individual MV phase cores
  • WÖU (WOEU / WOU): oil-resistant, flame-retardant heavy-duty rubber sheath system reinforced with polyester anti-torsion braid
Applications

(N)TSCGEWÖU Mine Distribution Applications & Movement Boundaries

Specify (N)TSCGEWÖU across surface open-pit and underground mine MV power networks where semi-flexible routing, periodic relocation and radial field screening are required within a 20 m/min speed envelope.

Red (N)TSCGEWÖU medium-voltage flexible rubber mine distribution feeder routed along rock-wall support brackets and heavy cable tray into a skid-mounted underground mine transformer substation
Semi-mobile mine MV power distribution and conveyor feed: rated up to 20 m/min and ±25°/m torsion (use R-(N)TSCGEWÖU for continuous motorized drum reeling).
  • 3.6/6 kV to 12/20 kV mine power distribution feeders linking portal substations, skid-mounted transformers and section switchhouses.
  • Overland belt-conveyor drive stations, crusher skids, stacker transfer houses and semi-mobile material-handling routes.
  • Low-speed mobile or periodically repositioned mining machinery operating within 20 m/min travel speed and ±25°/m torsional stress.
  • Cold-climate surface pit distribution (-40 °C to +80 °C static; -25 °C to +80 °C mobile) requiring flexible Class 5 tinned-copper terminations.

(N)TSCGEWÖU vs R-(N)TSCGEWÖU Reeling, F-(N)TSCGEWÖU & Single-Core MV

(N)TSCGEWÖU Mine Distribution Cable vs Reeling, Festoon, Single-Core & GOST MV Cables
Model FamilyVoltage SpanDynamic Duty BoundaryTarget Mining / Industrial Route
(N)TSCGEWÖU (this page)3.6/6 to 12/20 kVSemi-mobile distribution up to 20 m/min & ±25°/m; 6xOD fixedMine MV feeders, conveyor drives & skid-substation interconnects
R-(N)TSCGEWÖU3.6/6 to 18/30 kVDedicated continuous motorized drum reeling & TBM advanceStacker-reclaimers, TBM reels, electric shovels & crane drums
F-(N)TSCGEWÖU3.6/6 to 18/30 kVCyclic festoon trolley loops & conveyor catenary suspensionOverhead MV festoon beams & long-travel conveyor bridges
NTMCGCWÖU (Single-Core)3.6/6 to 18/30 kVFlexible single-core phase tails in non-magnetic cleatsCompact MV switchgear bays & mobile transformer jumpers
KGE / KGESh / KGETSh1.14 to 6 kVGOST cold-climate (-50 °C) excavator trailing serviceOpen-pit rope shovels, walking draglines & rotary drills

Outer diameter, finished cable mass and current rating vary strongly across the 3.6/6, 6/10, 8.7/15 and 12/20 kV insulation wall thicknesses and are issued on the quotation datasheet for your exact voltage class.

(N)TSCGEWÖU 3.6/6–12/20 kV Mine Feeder RFQ Checklist

  • System rated voltage U0/U (3.6/6 kV, 6/10 kV, 8.7/15 kV or 12/20 kV) and phase cross-section (25 to 185 mm²).
  • Earth-conductor split arrangement (e.g., 3x split interstitial earth vs 2+1 earth/pilot check) and sheath colour (red or black).
  • Route kinematics: confirm static tray/ground laying vs periodic relocation within 20 m/min and ±25°/m (specify R-(N)TSCGEWÖU if drum-reeled).
  • Load current (A), three-phase fault current/clearing time, route length (m) for voltage-drop check, and maximum ambient temperature (10 to 80 °C).
  • Ordered drum cut lengths (MOQ 50 m; manufacturing lead time 7 to 45 working days) and required AC test report scope.

Related selection resources

(N)TSCGEWÖU Mine Distribution Cable Frequently Asked Questions

Can standard (N)TSCGEWÖU mine distribution cable be used on continuous motorized reeling drums?

No—this (N)TSCGEWÖU mine-distribution build is bounded at 20 m/min working speed, ±25°/m torsional stress and 6 x OD fixed bending radius for semi-mobile feeders and equipment relocation; for continuous motorized drum reeling or tunnel-boring machine (TBM) advance, specify dedicated R-(N)TSCGEWÖU.

What voltage classes and factory AC test voltages apply to (N)TSCGEWÖU?

Four VDE 0250 Part 813 voltage classes are covered: 3.6/6 kV (11 kV AC test), 6/10 kV (17 kV AC test), 8.7/15 kV (24 kV AC test) and 12/20 kV (29 kV AC test).

Why are outer diameter and weight confirmed per quotation drawing on this (N)TSCGEWÖU page?

Because a single conductor size such as 3x95 mm² carries substantially thicker MV rubber insulation and screen walls at 12/20 kV than at 3.6/6 kV; issuing the exact OD, kg/km weight and ampacity on the order datasheet prevents MV gland or coupler sizing errors.

How much does high ambient temperature reduce (N)TSCGEWÖU current capacity?

Relative to 1.00 at 30 °C ambient, the current de-rating factor is 1.15 at 10 °C, 0.91 at 40 °C, 0.82 at 50 °C, 0.71 at 60 °C and 0.41 at 80 °C.

What minimum order quantity and delivery lead time apply to (N)TSCGEWÖU cables?

50 m minimum order quantity (MOQ), with a 7 to 45 working days factory manufacturing lead time shipped on export wooden drums.

Specifications

(N)TSCGEWÖU (25–185 mm²) Voltage-Drop, Resistance & De-Rating Tables

(N)TSCGEWÖU 3.6/6–12/20 kV Key Electrical & Mechanical Summary

  • Voltage & test classes: U0/U 3.6/6 kV (11 kV test), 6/10 kV (17 kV test), 8.7/15 kV (24 kV test) and 12/20 kV (29 kV test) per VDE 0250-813
  • MV field control: IEC 60228 Class 5 tinned-copper phase cores with semiconductive conductor/insulation screens and Class 5 earth continuity
  • Anti-torsion jacket: Stabilised semiconductive-textile central filler, rubber inner sheath, polyester anti-torsion braid and heavy-duty rubber outer sheath
  • Movement boundary: Up to 20 m/min working travel speed, ±25°/m max torsional stress, and 6 x OD fixed minimum bending radius
  • Thermal envelope: -40 °C to +80 °C static installation, -25 °C to +80 °C mobile service, and +250 °C short-circuit conductor limit
(N)TSCGEWÖU / (N)TSCGEWOEU 3.6/6–12/20 kV Mine Distribution Cable technical data
ParameterValue
Rated voltage3.6/6 kV (11 kV test), 6/10 kV (17 kV test), 8.7/15 kV (24 kV test) and 12/20 kV (29 kV test)
Conductor and earth buildIEC 60228 Class 5 tinned-copper phase cores (25 to 185 mm²) + Class 5 tinned-copper protective earth
Field control and braidInner/outer semiconductive rubber screens + semiconductive/polyester central filler + polyester anti-torsion braid
Dynamic and bending limitsMax working speed 20 m/min; max torsional stress ±25°/m; fixed minimum bending radius 6 x overall diameter
Thermal operating envelope-40 °C to +80 °C static installation; -25 °C to +80 °C mobile operation; +250 °C max short-circuit conductor temperature
Commercial and drawing basisMOQ 50 m; 7 to 45 working days lead time; exact outer diameter, weight and ampacity confirmed on order datasheet per voltage class

(N)TSCGEWÖU (25–185 mm²) Resistance & Three-Phase Voltage-Drop Schedule

(N)TSCGEWÖU 3.6/6–12/20 kV — IEC 60228 Class 5 Max DC Resistance at 20 °C & Preliminary Voltage-Drop Reference by Power Factor (V/A·km)
Model & Phase Size (mm²)Max DC Resistance at 20 °C (Ω/km)Voltage Drop PF 0.7 (V/A·km)Voltage Drop PF 0.8 (V/A·km)Voltage Drop PF 0.9 (V/A·km)Voltage Drop PF 1.0 (V/A·km)OD & Weight (mm / kg/km)Next step
(N)TSCGEWÖU 3×25 mm²0.7951.291.451.601.71Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×35 mm²0.5650.951.061.161.23Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×50 mm²0.3930.690.770.830.87Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×70 mm²0.2770.510.560.600.61Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×95 mm²0.2100.410.450.470.47Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×120 mm²0.1640.340.360.380.36Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×150 mm²0.1320.290.310.320.29Per voltage class order datasheetRequest this size
(N)TSCGEWÖU 3×185 mm²0.1080.250.270.270.24Per voltage class order datasheetRequest this size

(N)TSCGEWÖU Voltage Classes, Test Voltages & Ambient De-Rating Factors

(N)TSCGEWÖU — VDE 0250-813 Voltage Classes, Routine AC Test Voltages & Ambient Temperature Correction Factors (Base 30 °C = 1.00)
Parameter / Ambient Band3.6/6 kV | 10–25 °C6/10 kV | 30–45 °C8.7/15 kV | 50–65 °C12/20 kV | 70–80 °C
Routine AC test voltage (VDE 0250-813)11 kV AC17 kV AC24 kV AC29 kV AC
Ambient temperature step (°C)10 / 15 / 20 / 25 °C30 / 35 / 40 / 45 °C50 / 55 / 60 / 65 °C70 / 75 / 80 °C
Current de-rating factor1.15 / 1.12 / 1.08 / 1.041.00 / 0.96 / 0.91 / 0.870.82 / 0.76 / 0.71 / 0.650.58 / 0.50 / 0.41

ASCII part references: (N)TSCGEWOU / NTSCGEWOEU 3.6/6kV, 6/10kV, 8.7/15kV, 12/20kV in 3x25, 3x35, 3x50, 3x70, 3x95, 3x120, 3x150 and 3x185 mm2.

Standards

(N)TSCGEWÖU VDE 0250-813 & IEC Reference Standards

(N)TSCGEWÖU / (N)TSCGEWOEU 3.6/6–12/20 kV Mine Distribution Cable standards and test references
Standard or specificationApplication
Cable design standardVDE 0250 Part 813 (flexible medium-voltage rubber trailing and distribution cables)
Conductor standardsVDE 0295, IEC 60228 and EN 60228 Class 5 flexible tinned copper
Insulation and sheath compoundsVDE 0207 Part 20 (MV rubber dielectric) and VDE 0207 Part 21 (heavy-duty rubber sheath)
Application & installation guideVDE 0298 Part 3 mechanical routing, bending and dynamic movement guidance
Oil and flame test referencesIEC 60811-2-1 oil resistance; IEC/EN 60332-1-2 vertical single-cable flame retardancy

Certifications and document support

Review TEBAOFLEX ISO 9001 quality management and VDE 0250 voluntary VoC documentation

DIN Media — DIN VDE 0250-813 Medium-Voltage Flexible Rubber Mining Cables

Compare by duty

Related cable options

Compare these cable options by service combination, movement, load, voltage and transmission requirement.

Engineering-led quotation

Request a cable recommendation and quotation

Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.

  • Include the product name or SKU plus the required cable length and quantity.
  • Attach a specification, drawing or data sheet when available.

    MOQ 50 m · Engineering reply within 24 hours

    By submitting this form, you agree that TEBAOFLEX may use the contact information and files provided to review and respond to your enquiry. Files are used for quotation and engineering communication related to your request. See our Privacy Policy for current data handling and retention information.