UL 5359 Mica-Glass Wire, 600V 200/450°C
UL 5359 is a UL-certified mica-insulated wire rated 600 V AC, with 200°C and 450°C construction options. This page includes a detailed 450°C single-conductor selection table for high-temperature equipment leads protected from mechanical damage.
- Voltage: 600 V AC
- Temperature: 200°C or 450°C by construction
- Insulation / covering: mica tape and treated fiberglass braid
- Size selection: 30 AWG–4/0 AWG style range; table: 26 AWG–4/0 AWG
- Certification: UL-certified AWM; UL 758
UL 5359 wire selection
UL 5359 is a UL-certified mica-insulated wire rated 600 V AC, with 200°C and 450°C construction options. This page includes a detailed 450°C single-conductor selection table for high-temperature equipment leads protected from mechanical damage.
The 18 dimensioned configurations cover 26 AWG through 4/0 AWG. Each row combines UL 5359 with the conductor size and lists stranding, mica thickness, fiberglass-braid thickness and finished diameter. The wall schedule increases in steps as the conductor becomes larger, so the table supports both electrical size selection and the practical fit of sleeves, clamps and equipment entries.
For heater, oven or process-equipment wiring, choose the required temperature grade before comparing diameters. The 200°C and 450°C constructions are separate selections under the same style number. Installation should avoid repeated flexing and protect the mica-and-braid system from mechanical abuse. The operating current must be assessed for the selected conductor, ambient conditions, grouping and complete equipment application.
See the Specifications tab for the model and size tables. Browse the high-temperature cable range for related constructions. Compare MGT mica-glass wire for the existing 5107/5128 lead wire construction.
Construction
UL 5359 uses the following conductor and insulation system. The diagram illustrates the layer sequence; select the conductor construction and covering shown in the required size specification.

| Component | Construction detail |
|---|---|
| Conductor | Stranded nickel-coated copper or nickel, selected for the required construction |
| Insulation | Mica tape |
| Outer covering | Treated fiberglass braid |
Applications
UL 5359 is used for protected internal leads in high-temperature equipment, including heaters and ovens. Keep the mica-insulated lead supported and avoid locations with repeated bending or rubbing.

UL 5359 replacement selection
For replacement enquiries, include the existing wire marking and the equipment connection drawing so the conductor, insulation and terminal arrangement can be matched.
Specifications
| Parameter | Specification |
|---|---|
| UL style | UL 5359 |
| Voltage rating | 600 V AC |
| Temperature rating | 200°C or 450°C by construction |
| Insulation / covering | mica tape and treated fiberglass braid |
| Conductor size coverage | 30 AWG–4/0 AWG style range; table: 26 AWG–4/0 AWG |
| Temperature choices | 200°C or 450°C, according to construction |
| Voltage rating | 600 V AC |
| Installation | Protected internal wiring without repeated flexing |
450°C single-conductor dimensional reference. Nominal construction dimensions are for selection; the quotation drawing defines the supplied configuration.
| Model and conductor size | Stranding (No./mm) | Mica wall (mm) | Braid wall (mm) | Nominal OD / tolerance (mm) |
|---|---|---|---|---|
| UL 5359 26 AWG | 7/0.16 | 0.41 | 0.18 | 1.8±0.1 |
| UL 5359 24 AWG | 7/0.2 | 0.41 | 0.18 | 1.9±0.1 |
| UL 5359 22 AWG | 7/0.254 | 0.41 | 0.18 | 2.1±0.2 |
| UL 5359 20 AWG | 10/0.254 | 0.41 | 0.18 | 2.2±0.2 |
| UL 5359 18 AWG | 16/0.254 | 0.41 | 0.18 | 2.5±0.2 |
| UL 5359 16 AWG | 26/0.254 | 0.41 | 0.18 | 2.8±0.2 |
| UL 5359 14 AWG | 41/0.254 | 0.41 | 0.18 | 3.2±0.3 |
| UL 5359 12 AWG | 65/0.254 | 0.41 | 0.18 | 3.6±0.3 |
| UL 5359 10 AWG | 103/0.254 | 0.51 | 0.38 | 5.1±0.5 |
| UL 5359 8 AWG | 163/0.254 | 0.51 | 0.38 | 6.0±0.5 |
| UL 5359 6 AWG | 260/0.254 | 0.51 | 0.38 | 7.1±0.5 |
| UL 5359 4 AWG | 413/0.254 | 0.51 | 0.38 | 8.2±0.5 |
| UL 5359 2 AWG | 168/0.5 | 0.64 | 0.51 | 10.5±0.8 |
| UL 5359 1 AWG | 212/0.5 | 0.64 | 0.51 | 11.5±0.8 |
| UL 5359 1/0 AWG | 268/0.5 | 0.64 | 0.51 | 12.7±0.8 |
| UL 5359 2/0 AWG | 342/0.5 | 0.64 | 0.51 | 14.0±0.8 |
| UL 5359 3/0 AWG | 430/0.5 | 0.64 | 0.51 | 15.4±0.8 |
| UL 5359 4/0 AWG | 538/0.5 | 0.64 | 0.51 | 17.0±0.8 |
Style construction thicknesses are shown in mils; 1 mil = 0.0254 mm. Nominal finished dimensions are listed separately.
| Model and conductor group | Minimum average mica wall (mils) | Minimum average treated braid (mils) |
|---|---|---|
| UL 5359 30–12 AWG | 16 | 7 |
| UL 5359 11–4 AWG | 20 | 15 |
| UL 5359 3–4/0 AWG | 25 | 20 |
Selecting the specified construction
Specify UL 5359, AWG, 600 V AC and the required 200°C or 450°C construction. The dimension table below applies to the 450°C mica/fiberglass version.
Standards
TEBAOFLEX UL 5359 wire is UL-certified appliance wiring material.
| Item | Requirement or reference |
|---|---|
| Certification | UL-certified AWM |
| Style designation | UL 5359 |
| Construction standard | UL 758 — Appliance Wiring Material |
| Style flame classification | Horizontal flame |
Identify the UL style, conductor size, voltage and temperature grade on the purchasing specification. Include the required product identification and certification documents with the enquiry.
Request a cable recommendation and quotation
Send the required services, cable length, mechanical duty, environment, termination and quantity. Our team will review the application before quoting.
- Include the product name or SKU plus the required cable length and quantity.
- Attach a specification, drawing or data sheet when available.