Case 22 · Peru · Mine Power Distribution · 8 kV SHD-GC Class 6 Trailing Cable
SHD-GC 8 kV 3×4/0+2×1+1×8 AWG Class 6 Mining Power Cable (200 m) for Peru
Peruvian copper and polymetallic mines standardize on ANSI/ICEA S-75-381 Type SHD-GC shielded trailing cables for mobile shovels, drills and pit skid substations, yet frequently order in metric drum lengths with custom core identification and Spanish sheath legends. Following an on-site factory visit by the buyer’s inspection representative in Taicang, TEBAOFLEX manufactured and factory-tested an initial 200 m continuous drum of SHD-GC 8 kV 3×4/0 AWG + 2×1 AWG + 1×8 AWG built with Class 6 extra-flexible tinned copper, orange-red 150 mil EPR insulation and a 250 mil heavy-duty black jacket.

Project at a glance
This Peruvian mining supply order produced a 200 m continuous drum of SHD-GC 8 kV 3×4/0 + 2×1 + 1×8 AWG (ICEA S-75-381) with Class 6 tinned copper, recording 0.17360 Ω/km 20 °C phase DC resistance, 70.94 mm finished caliper diameter (against 69.9 mm nominal) and 321 A 40 °C free-air rating.
| Order item | Verified engineering detail |
|---|---|
| Destination & buyer profile | Peru — mining electrical distributor supplying open-pit and underground mine operations |
| Cable designation & standard | Type SHD-GC 8 kV 3×4/0 AWG + 2×1 AWG + 1×8 AWG, built to ANSI/ICEA S-75-381 (formerly NEMA WC 58) |
| Order quantity & follow-on | 200 m continuous uncut first drum (~20-day production run; 500 m repeat inquiry under review) |
| Conductor stranding | Class 6 extra-flexible annealed tinned copper across phases, grounds and ground-check |
| Dielectric & colour code | 150 mil (3.8 mm) nominal 90 °C orange-red EPR phase insulation + semiconductive/copper-braid phase shields; yellow 8 AWG GC |
| Outer jacket & Spanish print | 250 mil (6.4 mm) black extra-heavy-duty CPE jacket printed every metre: TEBAOFLEX TRIPOLAR SHD-GC 8kV 3×4/0AWG+2x1AWG+1x8AWG ICEA S-75-381 Standard 2026 |
| Verified factory test readings | Phase R20 = 173.60 mΩ/km (0.17360 Ω/km); 8 AWG GC R20 = 2,153.9 mΩ/km; finished caliper OD = 70.94 mm (nominal 2.75 in / 69.9 mm) |
| Packing & trade basis | Wound with moisture-sealed ends onto a lagged wooden export drum for FOB Shanghai sea dispatch with Certificate of Quality (COQ) |
How is SHD-GC 8 kV 3×4/0+2×1+1×8 AWG constructed, and why choose Class 6 copper?
SHD-GC 8 kV 3×4/0+2×1+1×8 AWG pairs three individually shielded 150 mil EPR power phases with two interstitial 1 AWG grounding conductors and one yellow 8 AWG ground-check pilot. Upgrading conductor stranding to IEC 60228 Class 6 reduces bending stiffness on a ~70 mm trailing cable during pit handling and coupler make-up.
Whereas our earlier Peru 2 kV SHD-GC 3×6 AWG project supplied compact 32.8 mm orange TPU trailing cable for lighter mobile machinery, stepping up to 8 kV primary pit distribution at 3×4/0 AWG more than doubles cable outside diameter to ~70 mm. During technical clarification, the Peruvian distributor specifically asked whether TEBAOFLEX builds this cross-section with Class 5 or Class 6 stranding (IEC 60228 / conductor stranding classes).
- 3 × 4/0 AWG Class 6 extra-flexible tinned copper phase conductors (QJ36B-2 bridge verified at 173.60 mΩ/km = 0.17360 Ω/km at 20 °C)
- Semiconductive conductor stress-control shield over each stranded phase bundle
- 150 mil (3.8 mm) nominal 90 °C EPR medium-voltage dielectric tinted high-visibility orange-red per buyer specification
- Semiconductive insulation shield plus composite tinned-copper/polyamide metallic shield over each phase
- 2 × 1 AWG flexible tinned-copper equipment grounding conductors positioned symmetrically in two outer interstices
- 1 × 8 AWG yellow-insulated flexible tinned-copper ground-check (pilot) conductor in the third interstice (verified at 2.1539 Ω/km at 20 °C)
- 250 mil (6.4 mm) nominal extra-heavy-duty black CPE outer jacket printed TEBAOFLEX TRIPOLAR SHD-GC 8kV
Every element in the 3×4/0 + 2×1 + 1×8 AWG construction serves a specific electrical or mechanical duty under ANSI/ICEA S-75-381:
- Class 6 extra-flexible tinned copper: Finer individual tinned wires lower elastic springback when mine electricians dress the three 4/0 AWG phases inside medium-voltage mining trailing cable couplers and reduce flex fatigue over cable-boat guide horns.
- 150 mil (3.8 mm) orange-red EPR + dual semiconductive stress control: At 8 kV, inner and outer semiconductive layers smooth radial electric stress across the 150 mil EPR dielectric while the composite tinned-copper/polyamide shield provides continuous fault-current containment. Tinting the EPR orange-red gives unmistakable visual contrast against the black semiconductive screen during field stripback.
- Symmetrical 2 × 1 AWG grounds + 1 × 8 AWG yellow ground-check: Two bare/tinned 1 AWG ground conductors occupy two outer valleys, while the yellow-insulated 8 AWG pilot core completes the fail-safe continuity loop detailed in our mining cable ground-check trip troubleshooting guide.


Why 8 kV 3×4/0 AWG is rated 321 A (not 211 A): verifying ICEA S-75-381 dimensions
Under the ICEA S-75-381 / TEBAOFLEX 8 kV SHD-GC schedule at 90 °C conductor temperature and 40 °C ambient air, 3×4/0 AWG carries 321 A in free air with 150 mil insulation, 250 mil jacket and 2.75 in (69.9 mm) nominal OD. The 211 A figure sometimes copied in draft paperwork belongs to 8 kV 3×1/0 AWG.
One of the most common documentation mistakes in medium-voltage mining tenders is copying an ampacity value from an adjacent gauge row on a multi-page datasheet. Cross-checking against our published SHD-GC 2 kV–25 kV mining power cable specification table and medium-voltage mining cable selection guide confirms the exact progression across 8 kV gauges (and note that reeling on multi-layer drums requires additional layer derating):
| 8 kV SHD-GC size identifier | EPR wall | Jacket wall | Nominal OD (in / mm) | 40 °C free-air ampacity | Application note |
|---|---|---|---|---|---|
| SHD-GC 3×1/0 + 2×4 + 1×8 AWG · 8 kV | 150 mil / 3.8 mm | 220 mil / 5.6 mm | 2.32 in / 58.9 mm | 211 A | Reference row often confused in drafts |
| SHD-GC 3×2/0 + 2×3 + 1×8 AWG · 8 kV | 150 mil / 3.8 mm | 235 mil / 6.0 mm | 2.46 in / 62.5 mm | 243 A | Intermediate shovel / drill feeder |
| SHD-GC 3×3/0 + 2×2 + 1×8 AWG · 8 kV | 150 mil / 3.8 mm | 250 mil / 6.4 mm | 2.62 in / 66.5 mm | 279 A | Heavy skid / substation feeder |
| SHD-GC 3×4/0 + 2×1 + 1×8 AWG · 8 kV (This order) | 150 mil / 3.8 mm | 250 mil / 6.4 mm | 2.75 in / 69.9 mm (70.94 mm measured) | 321 A | Peru 200 m Class 6 production build |
| SHD-GC 3×250 kcmil + 2×1/0 + 1×6 AWG · 8 kV | 150 mil / 3.8 mm | 250 mil / 6.4 mm | 2.89 in / 73.4 mm | 355 A | Steps ground-check up to 1×6 AWG |
Factory Kelvin bridge resistance, 70.94 mm caliper check and 200 m export drum preparation
Prior to winding the continuous 200 m export reel, factory inspection recorded 173.60 mΩ/km (0.17360 Ω/km) 20 °C DC resistance on the 4/0 AWG Class 6 phase conductor, 2,153.9 mΩ/km on the 8 AWG ground-check core and 70.94 mm finished outside diameter beside the Spanish TRIPOLAR print line.
Before the order entered final extrusion, the Peruvian buyer’s China-based representative visited our Taicang workshop to verify stranding and compounding controls. Upon completion of the 20-day manufacturing cycle, routine inspection documented the finished 200 m length in accordance with our cable factory acceptance test procedures:
- Precision Kelvin bridge DC resistance (
QJ36B-2): Measured on a 1 m specimen at 20.6 °C ambient, temperature-corrected 20 °C DC resistance on the 4/0 AWG Class 6 tinned-copper phase conductor read 173.60 mΩ/km (0.17360 Ω/km), and the 8 AWG yellow ground-check conductor read 2,153.9 mΩ/km (2.1539 Ω/km) at 20 °C (measured at 17.2 °C)—confirming full copper cross-section and clean tinning. - Finished diameter & Spanish TRIPOLAR marking: Digital caliper checks directly over the
TEBAOFLEX TRIPOLAR SHD-GC 8kV 3x4/0AWG+2x1AWG+1x8AWG ICEA S-75-381 Standard 2026metre-marked black jacket recorded 70.94 mm (within +1.5 % of the 69.9 mm / 2.75 in catalogue nominal, matching 8 kV coupler gland entry boots). - Export reel & COQ documentation: The uncut 200 m cable was end-sealed and wound onto a lagged wooden export drum for FOB Shanghai dispatch via the buyer’s nominated freight forwarder, accompanied by the Certificate of Quality (COQ). For mines operating DIN VDE equipment alongside North American shovels, compare our (N)TMCETMPU 6/10 kV to 14/25 kV mining trailing cable.




What to specify when ordering 5 kV, 8 kV, 15 kV or 25 kV SHD-GC for Latin American mines
To quote medium-voltage Type SHD-GC trailing cable without coupler or relay mismatches, confirm the voltage class (2 kV to 25 kV), phase/ground/pilot AWG sizes, Class 5 vs Class 6 stranding, EPR phase colour preference, jacket material/colour and exact metric or foot reel lengths.
- Rated voltage class (2 kV, 5 kV, 8 kV, 15 kV or 25 kV) and mine network phase-to-phase voltage (such as 4.16 kV, 6.9 kV, 7.2 kV or 13.8 kV)
- Exact conductor layout (for example 3×4/0 + 2×1 + 1×8 AWG) and whether Class 6 extra-flexible tinned stranding is required
- EPR phase insulation colour (orange-red vs. natural/coloured phases), outer jacket material/colour (black, yellow or orange CPE/TPU) and Spanish/English print legend
- Continuous drum lengths (200 m, 500 m or 1,000 ft), coupler gland entry ID range and FOB/CIF port documentation requirements
TEBAOFLEX manufactures custom Type SHD-GC cables from 2 kV through 25 kV from a 50 m minimum order quantity, with a standard manufacturing lead time of 7 to 45 working days as of November 2026 depending on voltage tier and order schedule. See mine-wide power architectures on our mining and tunneling cable solutions hub and full model listings under mining and tunneling cables.
Send your SHD-GC 8 kV–25 kV specification for a factory quote →
Frequently asked questions on SHD-GC 8 kV 3×4/0 AWG mining cables
What does 3×4/0 + 2×1 + 1×8 AWG mean on an 8 kV SHD-GC mining cable?
Under ANSI/ICEA S-75-381 (formerly NEMA WC 58), 3×4/0 AWG are the three individually shielded 8 kV power conductors, 2×1 AWG are two uninsulated flexible tinned-copper grounding conductors placed in two outer valleys to split fault return current symmetrically, and 1×8 AWG is the yellow-insulated ground-check pilot conductor occupying the third valley for continuous ground-loop monitoring.
What is the correct 40 °C ampacity of SHD-GC 8 kV 3×4/0 AWG—321 A or 211 A?
In the ICEA S-75-381 / TEBAOFLEX 8 kV SHD-GC specification table at 90 °C conductor temperature and 40 °C ambient air, 3×4/0 AWG is rated 321 A (single cable in free air), whereas 211 A belongs to the smaller 8 kV 3×1/0 AWG size. Cross-check conductor gauge before transcribing ampacity onto mine relay settings or shipping certificates.
Why did the Peruvian mining buyer request Class 6 tinned copper stranding instead of Class 5?
Class 6 stranding uses finer individual tinned copper wires than Class 5 at the same cross-section, lowering bending stiffness when a large 70 mm diameter 8 kV trailing cable is dragged across mine benches, looped into shovel cable boats or terminated inside compact 8 kV mining couplers.
Why is 8 kV SHD-GC built with 150 mil EPR insulation and metallic phase shields?
Above 2 kV, electric-field gradients across core air gaps would ionize air and erode unshielded rubber. ANSI/ICEA S-75-381 steps nominal EPR insulation thickness to 150 mil (3.8 mm) for 8 kV service and surrounds each core with inner/outer semiconductive shields plus a tinned-copper composite braid to confine radial dielectric stress and trip ground-fault protection immediately upon rock impact.
Can TEBAOFLEX manufacture 8 kV SHD-GC in custom metric drum lengths like 200 m and 500 m?
Yes. Alongside standard 1,000 ft reels, TEBAOFLEX produces custom continuous metric lengths such as 200 m and 500 m from a 50 m minimum order quantity, with a standard manufacturing lead time of 7 to 45 working days depending on voltage tier and factory schedule.